Forwards Response to IE Bulletin 80-15, Possible Loss of Emergency Notification Sys (ENS) W/Loss of Offsite Power. Test Verified Operability of All Sys
ML17319A612
Person / Time
Site: Cook  
Issue date: 09/04/1980
From: Maloney G
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
AEP:NRC:0438, IEB-80-15, NUDOCS 8009260094
Download: ML17319A612 (4)


Text

INDIANA & MICHIGAN ELECTRiC COMPANY P, O. 8OX 18 8OWLING GREEN STATION NEW YORK, N. Y. 10004 September 4,

1980 AEP:NRC:0438 Donald C. Cook Nuclear Plant Unit Nos'.

1 and 2

Docket Nos. 50-315 and 50-316 License Nos.

DPR-58 and DPR-74 Mr. James G. Keppler, Director.

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Region III Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

This letter responds to your letter of June 18, 1980 which transmitted to us IE Bulletin No. 80-15 entitled "Possible Loss of Emergency Notification System (ENS) With Loss of Offsite Power.",.

We received your letter on June 27, 1980.

Attachment 1 to this letter contains the written report required by Item 6 of this bulletin; attachment 2 contains an estimate of the manpower expended to conduct the review and to prepare the report as requested by your letter.

This information is being submitted in accordance with the provisions of 10 CFR 50.54(f).

Very truly yours, cc:

R.

C. Callen G. Charnoff John E. Dolan - Columbus R. S. Hunter R.

W. Jurgensen D. V. Shaller - Bridgman H. R. Denton - NRC, Washington

. Malo ey V'ice Presi en 80P9Q60009<

.SF.P 8

em

STATE OF NEW YORK COUNTY OF NEW YORK G.

P. Maloney, being duly sworn, deposes and says that he is the Vice President of Licensee Indiana 5 Michigan Electric Company, that he has read the foregoing response to I.E. Bulletin No. 80-15 entitled "Possible Loss of Emergency Notification System with Loss of Offsite Power" and knows the contents thereof; and that said contents are true to the best of his knowledge and belief.

C G.

P.

M 1 o 'ey Subscribed and sworn to before me this tt day of

!7i /

, 19 ~C..

Notary Public SUSAN S. BROVPif NOTARY PUBLIC, State of Notv Yet!a No. 60.4677376 Jun!iftcd in Wc:tchaator Coant7 CcrtUioate filed in Netv Yot:t Coant7 Coaxaussfon Exputes March 30, 1997.

ATTACHttENT 1 Itme 1:

TO AEP:NRC:0438 In accordance with the action required by item 1 to IE Bulletin No. 80-15, the PBX room of the Donald C. Cook Nuclear Plant was inspected on June 27, 1980 in conjunction with the Mid-Michigan Telephone Company District Manager.

With the exception of the lights and bells of the resident inspector's

phone, the Emergency Notification System (ENS) was determined to be powered by the local telephone company.

This is in agreement with Enclosure 1 to the aforementioned bulletin.

Item 3:

, In accordance with the action required by item 3, a test was conducted

" at our facility on August 8, 1980 to verify that all extensions of the ENS would remain fully operable from the site to the NRC Operations Center in the event of a. loss of offsite power to our facility.

The test was performed by removing site-supplied power from the r esident inspector's telephone system and verifying that each ENS phone to the NRC Operations center remained operable.

As expected, the resident inspector's telephone did not ring at the plant site.

It is possible to modify the resident inspector 's telephone so that its ring is supplied by local excha'nge power, although the resident inspector did not deem this necessary since the extension remained operational.

The NRC Operations Center was kept informed of the expected and actual results of each test conducted on August 8, 1980.

Item 5:

In accordance with action required by item 5,, Plant Procedure PMS0.034 has been revised to -indicate that'otification to the NRC Operations Center is required within one hour of the time that any extension of the-ENS is found to be inoperable.

Items 2 and 4 of IE Bulletin No. 80-15 are not applicable to our facility.

0 ATTACHMENT 2 TO AEP:NRC:0438 The following estimate of the manpower expended to conduct the review and preparation of the report required by the bulletin is provided below:

1.

Revi.ew (Item 1) 2; Testing (Item 3) 3.

Preparation of report (Item 6) and issuance of the letter MANHQURS 3