Amend 72 to License NPF-21,changing Tech Spec Table 3.8.4.2-1, Primary Containment Penetration Conductor Protective Devices by Changing Backup Protection Device for 480-volt Ac Fused Disconnects to Permit Plant Restart
ML17285A688
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 08/16/1989
From: Knighton G
Office of Nuclear Reactor Regulation
To:
Shared Package
ML17285A689 List:
References
TAC-74196, NUDOCS 8908280159
Download: ML17285A688 (8)


Text

gP,R REOI

+4 Po

<<**++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 WASHINGTON PUBLIC POWER SUPPLY SYSTEM DOCKET NO. 50-397 NUCLEAR PROJECT NO.

2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No; 72 License No.

NPF-21 1.

The Nuclear Regulatory Commission (the Commission or the NRC) has found that:

A.

The application for amendment filed by the Washington Public Power Supply System (the licensee),

dated August 13, 1989, and supplemental letter dated August 14, 1989, comply with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities wi 11 be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

8908280i59 85000397 ep816 PDR ADOCN P

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and paragraph 2.C.(2) of Facility Operating License No. NPF-21 is hereby amended to read as follows:

(2)

Technical S ecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 72, and the Environmental Protection Plan contained in Appendix 8, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This amendment is effective as of the date of issuance.

FOR THE NUCLEAR REGULATORY CONt<ISSION

Attachment:

Changes to the Technical Specifications Date of Issuance:

August 16, 1989 c Ag George N

Knighton; Director Project Directorate V

Division of Reactor Projects - III, IV, V and Special Projects

I J

I

ENCLOSURE TO LICENSE AMENDMENT NO. 72 FACILITY OPERATING LICENSE NO. NPF-21 DOCKET NO. 50-397 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page.

The revised page is identified by Amendment number and contains a vertical line indicating the areas of change.

Also to be replaced is the following overleaf page.

AMENDMENT PAGE 3/4 8-23 OVERLEAF PAGE 3/4 8-24

t k

P,

~

Ij

TABLE 3,8.4.2-1 PRIMARY CONTAINMENT PENETRATION CONDUCTOR OV RCUR ENT PROTEC VE DEV CES

~EUI PMENT PRIMARY PROTECTION a.

6900V Circuit Breakers BACKUP PROTECTION RRC-P-lA RRC-P-1B E-CB-RRA (Rel ay)

E-CB-RRB (Rel ay E-CB-S5 (Relay)

E-CB-N2/5 (Relay)

E-CB-S6 (Relay)

E-CB-N2/6 (Relay) b.

480VAC Fused Disconnects MS-V-16 RWCU-V-1 RHR-V-9 RCIC-V-63 RCC-V-40 RHR-V-123B RCIC-V-76 RHR-V-123A MC-SB-A MC-SB-A MC-SB-A MC-SB-.A MC-8B-A MC-8B-A MC-SB-A MC-SB-A Fused Fused Fused Fused Fused Fused Fused Fused MC-SB MC-SB MC-SB MC".8B MC-SB MC-SB MC-SB MC-SB Fused Fused Fused F.used Fused Fused Fused Fused WASHINGTON NUCLEAR - UNIT 2 3/4 8"23 Amendment No. 72

l l

l

)

I I

I I

I Il