ML17266A124
| ML17266A124 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie |
| Issue date: | 01/07/1980 |
| From: | Randy Hall BROOKHAVEN NATIONAL LABORATORY |
| To: | Ferguson R Office of Nuclear Reactor Regulation |
| References | |
| NUDOCS 8001140339 | |
| Download: ML17266A124 (8) | |
Text
REOULATOIINFORMATION DISTRIBUTION QTEM (RIBS)
ACCESSION NBH;6001140339 DOC ~ DATE: 80/01/07 NOTARIZED:
NO PACLLibQ"335 St. Lucia Plantr Unit lr P'loiida Power K Light Co.
"'"'0 389 St.
Luc'ie P'lantr On'it 2r F'lor'id'ower K L"ight Lo.
AU I'H ~ tIAI'lE AUl'HOA AFF ILIA'fION HACL,R,'E,.
Brookhaven Net'ional Laborato.ry
,AELIP.AAItlE RECIPIEltl'FFILIATION FEACUSOHER,L.
Po~er Systems Oranch DOCKET 0
05000333 OSOQO389 SUBJECTS Forwards review Controller 8'ti did not meet req controllers.not DISTRIBUTION COOK:
A006S "TIYLB: Fir'e P
NO KS ~
~
OTKS.
comments re SERrSection 9rFire Pump 1
791003 response,"Util fire pump -controllers uiiements of NFPA 2'oncludes fire pump equal to UL listed units, COP1ES HECEI VED: LTH ENCL SIlE:
/
rotection" In'formation (Afte'r Issuance of OP. Cic.)
ACTION ~
1NTERNAL'XTERNAL:
HEC IP IKNT IO t:OOEiHA~E 05 OCL ~R ~
ts ILK 0
12 AUXIL 5YS UH 19 WAlUlHACR OELO
3 LPDR Z2 ACAS COPIES L(YTH RNCI 1
1 2
?
?
i i
0 1
16 16 RECIPIENT r6 CUOEiNA~E 02 NRC POR 1'i TAiEOO iA PLANi'YS BR 20 AUHAAARArR 04 NSIC COPIES L'tr'A"EACL 1
1i 5i 1
1 JAN y6
$980 TOTAL, NUMBER OF COPIES HKQUIHKO:
I TTR ~
ENCL
h
~
hh
~
h h
IjH KO CL Department of Nuclear Energy BROOKHAVEN NATIONALLABORATORY ASSOCIATED UNIVERSITIES, INC.
Upton, New York 11973 (516) 345-2144 January 7,
1980 Mr. Robert L. Ferguson Plant Systems Branch U.S. Nuclear Regulatory, Commission Washington, D.C.
20555 RE:
St. Lucie Fire Protection Review Item 4.3.1.2; 9.0
Dear Bob:
Attached is our ccmments on the fire pump controller for the St. Lucie plant.
Resp ctfully yours, REH: EAM: sd attachment cc.:
R. Cerbone-W. Kato E. MacDougall V. Panciera E. Sylvester wo/att.
- obert E. Hall, Group Leader React or Eng i neeri ng Anal ys i s
LE 11 L'
Ct g
pp'4"'7 E
St. Lucie Fire Protection Review Fire Pum Controller 4.3.1.2 9.0 The letter to Florida Power and Light Company dated August 17, 1979 acccmpanyi ng the Safety Evaluation Report of the same
- date, requested the licensee to provide additional information needed to resolve issues raised by the fire protection consultant.
One of these items was the staff's request that the licensee prepare a point-by-point evaluation of the St. Lucie Unit No.
1 fire pump controller in ccmparison to the requirements of NFPA No. 20, which is the standard for Centrifugal Fire Pumps.
The licensee was also asked to state which parts of the controllers were U.L. listed and which parts were not.
Attachment B of Florida Power and Light's letter L-79-280 dated October 3, 1979 provides this comparison.
The licensee's letter did not, however, state which parts of the existing fire pump controllers are U.L. listed and which parts are not.
Florida Power and Light's point-by-point canparison indicated several instances where the existi ng fire pump controllers did not meet the require-ments of NFPA-20 nor possess other ccmpensating characteristics in lieu of the code requirements.
Specific paragraphs contained in NFPA 20 which the existing control equi pment does not meet includes:
1-5.1, 7-1.1.1, 7-1.1.2, 7-2.1, 7-3.5, 7-5.2.3 and 7-5.2.4.
The licensee defended some of these dif-ferences with the code by stating that the control equi pment at St. Luci e 1
was purchased to nuclear grade IE.
The licensee did not, however, explain in detail how the Class IE requirements are more stringent than the NFPA-20 re-quirements.
One of the requirements of NFPA-20 contained in paragraph 7-5.2.3 states that manual control stations located remote frcm the controller must not be operable to stop the fire pump motor.
Paragraph 7-2.1 of NFPA-20 also re-quiress the controller to be located as close as practical to the fire pump motors and within sight of the motors.
The existing arrangement at St. Lucie 1, however, has the control equi pment located in another area of the plant and a control switch is provided in the control room for stopping the fire pumps.
These deficienci es result in a fire protection water supply system which may not be dependable under all conditions.
The licensee has also stated that the fire pumps will automatically operate upon drop of pressure in the fire water distribution system; except under engineered safety features actuation signal (ESFAS) conditions.
Based on the review of the submitted evaluation, we conclude that the existing electric motor driven fire pump controllers are not equal in reli-ability to U.L. listed units conforming to NFPA-20 requirements.
Of greater importance than the technical quality level of the components, however, is the basic arrangement of the control system which could allow the fire pumps to be inoperable under some conditions.
The resulting loss of fire protection water could negate both automatic and manual firefighting systems in the plant.
1 II I
0
In order to correct this deficiency, and to insure a dependable water sup-ply for fire protection, the existing electric motor driven fire pumps should be supplemented with an additional 2,500 gpm diesel engine driven fire pump which will be independent of the plant power systems even under ESFAS con-ditions.
With the addition of this pump a redundant fire water supply is provided and the criticality of the existing electric motor driven fire pumps is reduced.
Based on this, the existing electric fire pump controller is con-sidered acceptable with the implementation of the licensees proposed modifi-cation of upgrading and relocating the sensing lines and pressure switches to a location near the. pump discharge.
If the recommendation for the additional diesel engine driven fire pump is not implemented, the existing controller arrangement for the electric motor driven fire pumps is not acceptable.
In this case, an alternate solution would be the replacement of both existing controllers with new controllers approved by U.L. and meeting all the require-ments of NFPA-20.
The electric driven fire pumps must be available in the case of loss of off-site power.
We recommend that the requirements of Section A-4 of Appendix A of BTP 9.5-1 be met.
e) 1 f