ML17265A139

From kanterella
Jump to navigation Jump to search
Informs That Util No Longer Requires Exemption for Absence of Continuous fire-rated Barrier at Common Boundary Between Fire Areas Abi & Abbm at Refueling Water Storage Tank
ML17265A139
Person / Time
Site: Ginna Constellation icon.png
Issue date: 01/13/1998
From: Mecredy R
ROCHESTER GAS & ELECTRIC CORP.
To: Vissing G
NRC (Affiliation Not Assigned), NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9801230068
Download: ML17265A139 (5)


Text

CATEGORY j.

REGULA Y INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9801230068 DOC.DATE: 98/01/13 NOTARIZED: NO DOCKET ¹ FACIL:50-244 Robert Emmet Ginna Nuclear Plant, Unit 1, Rochester G

05000244 AUTH.NAME AUTHOR AFFILIATION MECREDY,R.C.

Rochester Gas

&, Electric Corp.

RECIP.NAME RECIPIENT AFFILIATION VISSING,G.S.

SUBJECT:

Informs that util no longer recpxires exemption for absence of continuous fire-rated barrier at common boundary between fire areas ABI & ABBM at refueling water storage tank.

DISTRIBUTION CODE: A006D COPIES RECEXVED:LTR ENCL SIZE:

TITLE: OR/Licensing Submittal: Fire Protection

- App R - GL-88-12 NOTES:License Exp date in accordance with 10CFR2,2.109(9/19/72).

05000244E RECIPIENT ID CODE/NAME PD1-1 LA VISSING,G.

COPIES RECIPIENT LTTR ENCL 'D CODE/NAME 1

0 PD1-1 PD 1

1 COPXES LTTR ENCL 1

1 INTERNAL.

1 NUDOCS -ABSTRACT EXTERNAL: NOAC 2

1 1

1 1

NRR/DSSA/SPLB OGC/HDS3 NRC PDR 1

1 1

0 1

1 D

E NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD)

ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED:

LTTR 10 ENCL 8

a zi

AND ROCHESTER GASANDELECTRIC CORPORATION ~ 89 FASTAVENUE, ROCHESTER, N. Y Id6d9-000I ARFA CODE716 546-2700 ROBERT C. MECREDY Vice President Nvcteor operations January 13, 1998 U.S. Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate I-1 Washington, DC 20555

Subject:

Exemption to Section III.G of Appendix R R.E. Ginna Nuclear Power Plant Docket No. 50-244 Ref.(a):

Letter from J. Zwolinski, NRC, to R. Kober, RG&E, dated 3/21/85,

Subject:

Exemptions to Section III.G of Appendix R

(b):

Letter from R.C. Mecredy, RG&E, to A. Johnson, NRC, dated 12/4/95,

Subject:

Fire Barrier Penetration Seal (c):

Facility Operating License No. DPR-18, Date of Issuance December 10,

1984, as amended

Dear Mr. Vissing:

Rochester Gas and Electric was granted an exemption from the requirements of Section III.G of Appendix R to 10CFR50 for the absence of a continuous fire-rated barrier at the common boundary between Fire Areas ABI and ABBM, at the Refueling Water Storage Tank.

This exemption is listed as the first. request in Reference (a), which documents that this exemption was granted.

In Reference (b),

RG&E notified the NRC that the fire barrier was temporarily degraded by removal of the 8 foot high concrete block shield wall, and that the barrier was being sealed by insertion of a 12 inch minimum depth of kaowool into a 6 inch gap, and closure of the gap by a 3/4 inch thick steel plate.

These references are enclosed.

This permanent installation has been completed.

Therefore, RG&E no longer requires an exemption for the absence of a continuous fire-rated barrier in this location.

Very ruly yours, Robert C.

Mec edy Enclosures GJW4489

'tt80i230068 'tt80ii3 PDR ADQCK 05000244 F

PDR llllllllllllllilllllllllllllllllllllllll

t

xc:

Mr. Guy Vissing (Mail Stop 14B2)

Project Directorate I-1 Washington, D.C.

20555 U.S. Nuclear Regulatory Commission Region I 475 Allendale Road King of Prussia, PA 19406 Ginna Senior Resident Inspector