Forwards MOV Insp Rept 50-244/95-06 on 950327-31 & 0419-20. Insp Found That Util Making Satisfactory Progress to Complete MOV Program by 950628
ML17263B088
Person / Time
Site: Ginna 
Issue date: 06/16/1995
From: Eugene Kelly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Mecredy R
ROCHESTER GAS & ELECTRIC CORP.
Shared Package
ML17263B089 List:
References
GL-89-10, NUDOCS 9506280550
Download: ML17263B088 (5)


See also: IR 05000244/1995006

Text

PRIORj:T'Y 2

REGULATORYI-CRASRkt'KSQE&TSTRKISOTION SYSTEM (RIDS)

ESSION NBR:9506280550

DOC.DATE: 95/06/16

NOTARIZED: NO

IL:50-244 Robert

Emmet Ginna Nuclear Plant, Unit 1, Rochester

G

TH.NAME

AUTHOR AFFILIATION

KELLY,E.M.

Region

1 (Post

820201)

RECIP.NAME

RECIPIENT AFFILIATION

MECREDY,R.C.

Rochester

Gas

6 Electric Corp.

DOCKET

N

05000244

SUBJECT:

Forwards

MOV insp rept 50-244/95-06

on 950327-31

& 0419-20.

Insp found that util making satisfactory progress

to

complete

MOV program by 950628.

DZSTRZBUTZON CODE:

ZEOZD

COPIES

RECEIVED:LTR L ENCLl SIZE: 2 +'ICP

TITLE: General

(50 Dkt)-Insp Rept/Notice of Violation Response

NOTES:License

Exp date in accordance

with 10CFR2,2.109(9/19/72).

05000244

C

RECIPIENT

ID CODE/NAME

PDl-1

PD

INTERNAL: AEOD/DEIB

AEOD/

TE

NRR

DORS

OEAB

NUDOCS-ABSTRACT

OGC/HDS3

EXTERNAL

LITCO BRYCEP J

H

NRC PDR

COPIES

LTTR ENCL

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

RECIPIENT

ID CODE/NAME

JOHNSON,A

AEOD/SPD/RAB

DEDRO

NRR/DISP/PIPB

NRR/DRCH/HHFB

OE DIR

RGN1

FILE

01

NOAC

COPIES

LTTR ENCL

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

D

U

N

VOTE TO ALL"RIDS" RECIPIENT S:.

PLEASE HELP US TO REDL'CE iVASTE!CONTACTTHE DOCLifEYTCOiTROL

DESK, ROOif Pl 37 (EYT. 504 20S3

) TO ELlifliA'I'Ei'Of:R iAifE FROif

DISTRIB!."I'IOiLISTS FOR DOCI.'NlEilS YOL'Oi "I'

EED!

TOTAL NUMBER OF COPIES

REQUIRED:

LTTR

17

ENCL

17

June

16,

1995

Dr. Robert

C. Mecredy

Vice President,

Ginna Nuclear Production

Rochester

Gas

and Electric Corporation

89 East Avenue

Rochester,

New York

14649

SUBJECT:

GINNA MOTOR-OPERATED VALVE INSPECTION 95-06

Dear Dr. Mecredy:

This letter transmits

the report of an inspection of the Ginna Nuclear

Power

Plant motor-operated

valve

(MOV) program conducted

by Mr. L. Prividy and

others of this office from March 27-31

and April 19-20,

1995.

The inspectors

focused

on areas

important to public health

and safety,

performing

an

independent

evaluation of MOV program procedures,

calculations,

and test

results associated

with NRC Generic Letter (GL) 89-10,

"Safety-Related

Motor-

Operated

Valve Testing

and Surveillance."

The preliminary findings were

discussed

with Mr. J.

Widay and other members of your staff by telephone

on

May 1,

1995.

Our inspection

found that you were making satisfactory

progress

to complete

the

MOV program

by June

28,

1995.

We recognize your efforts to refurbish

valve actuators

and dynamically test over 60X of the

MOV population,

including

most risk-significant valves;

however, test data still need to be evaluated

for verification of the design-basis

capability of all

GL 89-10

MOVs.

Inconsistencies

were found between

MOV program documents

and calculations,

as

well as with test procedures,

reflecting weaknesses

in administrative

controls.

Some

key technical

issues

also

need to be resolved for MOV program

completion,

such

as

stem lubrication degradation

and your grouping

methodology,

which was not consistent with,Generic Letter 89-10,

Supplement

6.

No response

to this letter is required.

Your cooperation

in these matters is

appreciated,

and

we would be pleased

to discuss

any questions

you have

concerning this inspection.

Sincerely,

Eugene

M. Kelly, Chief

Systems

Section

Division of Reactor Safety

Docket

No. 50-244

Enclosure:

Inspection

Report

No. 50-244/95-06

9506280550

'F50626

PDR

ADOCK 05000244

8

PDR

Dr. Robert

C. NcCredy

2

cc w/encl:

R. Smith, Senior Vice President,

Customer Operations

Central

Records

(7 copies)

Director,

Energy

and Water Division

State of New York, Department of Law

N. Reynolds,

Esquire

D. Screnci,

PAO (2)

NRC Resident

Inspector

State of New York,

SLO Designee

Distribution w/encl:

Region I Docket

Room (with concurrences)

PUBLIC

Nuclear Safety Information Center

(NSIC)

J. Wiggins,

DRS

W. Lazarus,

DRP

S. Stewart,

DRP

H. Oprendek,

ORP

DRS File (1)

Distribution w/encl

(VIA E-NAIL):

T. Scarbrough,

NRR,

ENEB

C. Casto,

RII

J. Jacobsen,

RIII

E. Collins,

RIV

A. Johnson,

PH,

NRR

W. Dean,

OEDO

T. Harsh,

NRR

Inspection

Program Branch,

NRR (IPAS)

M. Campion,

ORA

June

16,

1995

OOCUNENT NAME:

A:GIN9506. INS

To receive a copy of this document, indicate in the box: 'C'

Copy without attachment/enclosure

E ~ Copy with attachment

nclosurc

'N

~ No copy

OFFICE

RI/DRS

LPrivid

06/07/

5

NRR/EMEB

RWessmamt%

RI/ORP

06/

/95

06/ I

/95

OFFICIAL RECORD

COPY

RI/DRS

EKell

06/

/95

RI/

06/

/95