ML17263A492

From kanterella
Jump to navigation Jump to search
Forwards Insp Rept 50-244/93-21 on 931004-13 & Notice of Violation
ML17263A492
Person / Time
Site: Ginna 
Issue date: 12/10/1993
From: Durr J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Mecredy R
ROCHESTER GAS & ELECTRIC CORP.
Shared Package
ML17263A494 List:
References
NUDOCS 9312170010
Download: ML17263A492 (3)


See also: IR 05000244/1993021

Text

OEC lO m

Docket No. 50-244

Dr. Robert C. Mecredy

Vice President,

Ginna Nuclear Production

Rochester

Gas and Electric Corporation

89 East Avenue

Rochester,

New York 14649

Dear Dr. Mecredy:

SUBJECT:

NOTICE OF VIOLATION(NRC INSPECTION REPORT NO. 50-244/93-21)

This refers to an announced

inspection conducted by Mr. L. Scholl of this office on

October 4, 1993 to October 13, 1993.

The inspection included a review of activities

authorized for your R. E. Ginna facility. At the conclusion of the inspection, the findings

were discussed with those members of your staff identified in Attachment

1 of the enclosed

report.

Areas important to public health and safety were examined during the inspection and are

identified in the NRC Region I inspection report, which is enclosed with this letter.

Within

these areas,

the inspection consisted of selective examinations of procedures

and

representative

records, and interviews with personnel.

The purpose of the inspection was to

determine whether activities authorized by the license were conducted safely and in

accordance with NRC requirements.

We found that your staff has continued to resolve issues identified during the Electrical

Distribution System Functional Inspection performed in 1991.

The electrical system

calculations and changes

to procedures

that were identified as necessary

during that

inspection have been completed and were found to be thorough and of high quality. Your

review and followup of electrical distribution system deficiencies identified at other facilities

was generally good.

However, based on the results of this inspection, the testing of the emergency diesel

generators

appeared

to be in violation of the plant Technical Specifications,

as specified in

the enclosed Notice of Violation (Notice).

The emergency bus load shed function has not

been tested.

The verification of the proper operation of this circuitry during periodic testing

is important since the failure to shed loads during an accident could result in the overload

and subsequent

loss of the EDG.

This violation is of particular concern because,

although

the adequacy of EDG testing has been the subject of recent NRC Information Notices, the

deficiency was not identified by your staff.

9312170010

931210

PDR

ADOCK 05000244

PDR

~gollit

OEG

I 0

1993

Rochester

Gas and Electric

Corporation

4

You are required to respond to this letter and should follow the instructions specified in the

enclosed Notice when preparing

your response.

In your response,

you should document the

specific actions taken and any additional actions you plan to prevent recurrence.

In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice," a copy of this letter and

its enclosures willbe placed in the NRC Public Document Room.

The responses

directed by this letter and the enclosed Notice are not subject to the clearance

procedures of the Office of Management and Budget as required by the Paperwork Reduction

Act of 1980, Pub. L. No. 96.511.

Sincerely,

Jacque P. Durr, Chief

Engineering Branch

Division of Reactor Safety

Enclosures:

1. Notice of Violation

2. NRC Inspection Report No. 50-244/93-21

cc w/encl:

R. Smith, Senior Vice President, Production and Engineering

Central Records (5 copies)

Director, Energy and Water Division

State of New York, Department of Law

N. Reynolds, Esquire

Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

K. Abraham, PAO (2)

NRC Resident Inspector

State of New York, SLO Designee

t

Rochester Gas,and Electric

Corporation

bcc w/encl:

Region I Docket Room (with concurrences)

W. I mrus, DRP

D. Lew, DRP

bcc w/encl (VIAE-MAIL):

A. Johnson, PM, NRR

V. McCree, OEDO

W. Butler, NRR

RI:DRS

Sch

1

11/qo/93

RI:DRSA"

Ruland ~<

12/o zl93

RI:DRS

Durr

12/2 /93

OFFICIALRECORD COPY

A:GIN9321.INS