ML17261B162

From kanterella
Jump to navigation Jump to search
Response to Request for Regulatory Conference and Probabilistic Risk Assessment Information
ML17261B162
Person / Time
Site: Cooper Entergy icon.png
Issue date: 09/14/2017
From: Jason Kozal
NRC/RGN-IV/DRP/RPB-C
To: Dent J
Nebraska Public Power District (NPPD)
Jason Kozal
References
EA-17-057
Download: ML17261B162 (32)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION REGION IV 1600 E. LAMAR BLVD.

ARLINGTON, TX 76011-4511 September 14, 2017 EA-17-057 Mr. John Dent Vice President-Nuclear and CNO Nebraska Public Power District Cooper Nuclear Station 72676 648A Avenue P.O. Box 98 Brownville, NE 68321

SUBJECT:

COOPER NUCLEAR STATION - RESPONSE TO REQUEST FOR REGULATORY CONFERENCE AND PROBABILISTIC RISK ASSESSMENT INFORMATION

Dear Mr. Dent:

On August 14, 2017, the U.S. Nuclear Regulatory Commission (NRC) issued NRC Inspection Report 05000298/2017011 in which we identified a finding with preliminary low-to-moderate (White) safety significance. In your response letter dated August 23, 2017, you indicated your request for a regulatory conference in order to present your perspective on the facts and assumptions the NRC used to arrive at the finding and assess its significance. You requested that the scheduling of the regulatory conference be extended so that you can complete inspection and testing and present finalized engineering analysis. This letter is to inform you of our decision to schedule the regulatory conference for November 7, 2017. Further details regarding this meeting will be issued in a public meeting notice prior to the meeting. As stated in our letter discussed above, we encourage you to submit supporting documentation at least one week prior to the conference in an effort to make the conference more efficient and effective.

Additionally, on August 21, 2017, Mr. O. Olson of your staff requested probabilistic risk assessment information related to the preliminary significance determination associated with the preliminary White finding referenced above. This request was made via e-mail and is included as Attachment 6 to this letter. We are providing the requested information as Attachments 1 through 5 to this letter, with these attachments corresponding to the numbered items in your request.

In accordance with 10 CFR 2.390 of the NRCs Rules of Practice and Procedure, a copy of this letter and its attachments will be made available electronically for public inspection in the

J. Dent 2 NRC Public Document Room and in the NRCs Agencywide Documents Access and Management System (ADAMS), accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html.

Please contact me at 817-200-1144 with any questions you have regarding this letter.

Sincerely,

/RA/

Jason W. Kozal, Chief Project Branch C Division of Reactor Projects Docket No.: 50-298 License No: DPR-46 Attachments  :

(1) Cutsets for the base case SPAR internal events PRA (2) Cutsets for the case that represents the performance deficiency (3) Cutsets for the sensitivity cases summarized in inspection report 2017-011 dated August 14, 2017 (4) Details on the approach to quantify the consequential failure of the SSST (5) Segregated bus common cause failure values used for base case and ESST fault case cc w/ encl: Electronic Distribution

ML17261B162 SUNSI Review: ADAMS: Non-Publicly Available Non-Sensitive Keyword:

By: CYoung/dll Yes No Publicly Available Sensitive NRC-002 OFFICE RIV/DRS RIV/DRP RIV/DRS RIV/DRP NAME RDeese CYoung HGepford JKozal SIGNATURE /RA/ /RA/ /RA/ /RA/

DATE 9/14/17 9/14/17 9/14/17 9/14/17 Cutsets for the base case SPAR internal events PRA The top 100 cutsets of the base internal events model are listed below. The base model contained the modifications described in NRC inspection report 05000298/2017011 and were run on the Cooper SPAR model, Version 8.50, on SAPHIRE 8.1.5.

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 3 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 4 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 5 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 6 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 7 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 8 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 9 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 10 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 11 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 12 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 13 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 14 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 15 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 16 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 17 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 18 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 19 IE-TRANS,DCP-BCH-CF-125 20 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 21 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 22 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 23 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 24 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 25 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 26 IE-TRANS,DCP-BDC-CF-125AB 27 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 28 IE-LOSWS,CTM-INJ-RP-COOP,EHV-XHE-XM-ALTRC,IE-SWS-STR-CF-PE-AB 29 IE-MLOCA,ADS-XHE-XM-MDEPR-M,HCI-TDP-FR-TRAIN 30 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 31 IE-XLOCA,RPVRM 32 IE-LOOPSC,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 33 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 34 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 35 IE-LOOPGR,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 36 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-TM-TRAIN,RCI-TDP-FR-TRAIN 37 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-TM-TRAIN 38 IE-LOOPSC,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 39 IE-LOACB-F,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRND,SPC-XHE-XL-NOREC 40 IE-LOACB-G,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRNA,SPC-XHE-XL-NOREC 41 IE-LODCB-A,ADS-TSW-FT-DC125,HCI-TDP-FR-TRAIN 42 IE-LOACB-F,ACP-BAC-LP-4KV1G,EPS-XHE-XM-PDG 43 IE-LOACB-G,ACP-BAC-LP-4KV1F,EPS-XHE-XM-PDG 44 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PG-AB,RCI-TDP-FR-TRAIN 45 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 46 IE-LOOPGR,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 47 IE-LOSWS,BWR-XHE-XE-LPINJ,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 48 IE-LOSWS,IE-SWS-MDP-CF-FE-ABCD,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 49 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-TM-TRAIN 50 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FS-TRAIN 51 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FS-TRAIN,RCI-TDP-FR-TRAIN 52 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,PCS-XHE-XO-MVPS,RCI-TDP-FR-TRAIN 53 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 54 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 55 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 56 IE-LODCB-A,ADS-TSW-FT-DC125,PPR-SRV-OO-1VLV Attachment 1
  1. CUT SET 57 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 58 IE-LOSWS,CTM-INJ-RP-COOP,EHV-XHE-XM-ALTRC,IE-SWS-STR-CF-PG-AB 59 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FS-TRAIN 60 IE-TRANS,ADS-XHE-XM-MDEPR,PCS-XHE-XO-MVPS,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 61 IE-LOCHS,ADS-SRV-CF-VALVS,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 62 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 63 IE-SLOCA,ADS-XHE-XM-MDEPR-S,HCI-TDP-FR-TRAIN 64 IE-LOOPWR,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 65 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 66 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 67 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-TM-TRAIN,RCI-TDP-FR-TRAIN 68 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-TM-TRAIN 69 IE-LOACB-F,CVS-XHE-XL-LOAC,RHR-HTX-TM-HTXB,SPC-XHE-XL-NOREC 70 IE-LOACB-G,CVS-XHE-XL-LOAC,RHR-HTX-TM-HTXA,SPC-XHE-XL-NOREC 71 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-RESTART,RCI-TDP-RS-RSTRT,RCI-XHE-XL-RSTRT 72 IE-LOOPSC,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 73 IE-LOCHS,ADS-SRV-CF-VALVS,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 74 IE-LOACB-F,CRD-MDP-AP-RUNA,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRND,SPC-XHE-XL-NOREC 75 IE-LOACB-F,CRD-MDP-AP-RUNB,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRND,SPC-XHE-XL-NOREC 76 IE-LOACB-G,CRD-MDP-AP-RUNA,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRNA,SPC-XHE-XL-NOREC 77 IE-LOACB-G,CRD-MDP-AP-RUNB,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRNA,SPC-XHE-XL-NOREC 78 IE-TRANS,PPR-SRV-OO-1VLV,RHR-XHE-XM-ALLDHR 79 IE-LOOPWR,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 80 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FS-TRAIN 81 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FS-TRAIN,RCI-TDP-FR-TRAIN 82 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-MDP-CF-FE-ABCD,SWS-XHE-XL-NOREC 83 IE-LODCB-A,DCP-BCH-LP-BC1B,EPS-XHE-XM-PDG 84 IE-LODCB-B,DCP-BCH-LP-BC1A,EPS-XHE-XM-PDG 85 IE-LOOPGR,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 86 IE-LODCB-A,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN 87 IE-LODCB-B,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 88 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-RESTART,RCI-TDP-RS-RSTRT,RCI-XHE-XL-RSTRT 89 IE-LOSWS,ACP-CRB-OO-1AS,CVS-XHE-XL-LOIAS,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 90 IE-LOSWS,ACP-CRB-CC-1AN,CVS-XHE-XL-LOIAS,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 91 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,OEP-VCF-LP-CLOPT,RCI-TDP-FR-TRAIN 92 IE-LOSWS,BWR-XHE-XE-LPINJ,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 93 IE-LOIAS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,IE-IAS-MDC-CF-FR-ABC,RCI-TDP-FR-TRAIN 94 IE-LOCHS,CVS-XHE-XM-VENT,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 95 IE-LOCHS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 96 IE-LOSWS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 97 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-MDP-CF-FE-ABCD,SWS-XHE-XL-NOREC 98 IE-LOMFW,ADS-SRV-CF-VALVS,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 99 IE-LODCB-A,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV 100 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-MDP-CF-FE-ABCD,PPR-SRV-OO-1VLV A1-2

Cutsets for the case that represents the performance deficiency The performance deficiency is represented by a mixture of 2 conditions. The first condition is with failure of the ESST bus duct set to TRUE. The second condition is with the failure of the ESST and SSST-X bus ducts set to TRUE. The 2 conditions are weighted and combined such that 75 percent of condition 1 and 25 percent of condition 2 comprise the final estimate. The top 100 cutsets are provided for each of these conditions below.

Condition 1 (ESST bus duct failure set to TRUE):

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 3 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 4 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 5 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 6 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 7 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 8 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 9 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 10 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 11 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 12 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 13 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 15 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 16 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 17 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 18 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 19 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 20 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 21 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 22 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 23 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 24 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 25 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 26 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 27 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 28 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 29 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 30 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 31 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 32 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 33 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 34 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 35 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 36 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 37 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 38 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 39 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 40 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 41 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 42 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 43 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 44 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 45 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 46 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 47 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 49 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 50 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN Attachment 2
  1. CUT SET 51 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 52 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 53 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 54 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 55 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 56 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 57 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 58 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 59 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 60 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 61 IE-TRANS,DCP-BCH-CF-125 62 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 63 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 64 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 65 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 66 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 67 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 68 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 69 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 70 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 71 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 72 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 73 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 74 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR 75 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 76 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 77 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 78 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 79 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 80 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 81 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 82 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 83 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 84 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 85 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 86 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 87 IE-LOMFW,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 88 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 89 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 90 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 91 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 92 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 93 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 94 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 95 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 96 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 97 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 98 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 99 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 100 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV A2-2

Condition 2 (ESST and SSST-X bus duct failure set to TRUE):

1 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 2 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 3 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 4 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 5 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 6 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 7 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 8 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 9 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 11 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 12 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 13 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 15 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 16 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 17 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 18 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 19 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 20 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 21 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 22 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 23 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 24 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 25 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 26 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 27 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 28 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 29 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 30 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 31 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 32 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 33 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 34 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 35 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 36 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 38 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 39 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 40 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 41 IE-TRANS,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 42 IE-TRANS,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 43 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 44 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 45 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 46 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 47 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 49 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 50 IE-TRANS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 51 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 52 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 53 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 54 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 55 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 56 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 58 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 59 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 60 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 61 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H A2-3

62 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 63 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 64 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 65 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 66 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 67 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 68 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 69 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG 70 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG,RCI-XHE-XO-ERRLT 71 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 72 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 73 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 74 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 75 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 76 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 77 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 78 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 79 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 80 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 81 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 82 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 83 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 84 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 85 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 86 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 87 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 88 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 89 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 90 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 91 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 92 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 93 IE-TRANS,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 94 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 95 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 96 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 97 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 98 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 99 IE-TRANS,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1B,RRS-MDP-LK-SEALS A2-4

Cutsets for the sensitivity cases summarized in inspection report 2017-011 dated August 14, 2017 Five sensitivities were included in the inspection report. They were:

a. No common cause effect
b. Larger common cause group
c. Different common cause factor
d. Loading the transformer
e. No recirculation pump seal failure Each of these sensitivities were estimated in the same manner as the case representing the performance deficiency by combining Conditions 1 and 2.

No common cause effect Condition 1 - ESST only

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 3 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 4 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 5 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 6 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 7 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 8 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 9 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 10 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 11 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 12 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 13 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 15 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 16 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 17 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 18 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 19 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 20 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 21 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 22 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 23 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 24 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 25 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 26 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 27 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 28 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 29 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 30 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 31 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 32 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 33 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 34 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 35 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 36 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 37 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 38 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 39 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV Attachment 3
  1. CUT SET 40 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 41 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 42 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 43 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 44 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 45 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 46 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 47 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 49 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 50 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 51 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 52 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 53 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 54 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 55 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 56 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 57 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 58 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 59 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 60 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 61 IE-TRANS,DCP-BCH-CF-125 62 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 63 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 64 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 65 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 66 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 67 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 68 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 69 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 70 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 71 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 72 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 73 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 74 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR 75 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 76 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 77 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 78 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 79 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 80 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 81 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 82 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 83 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 84 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 85 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 86 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 87 IE-LOMFW,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 88 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 89 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 90 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 91 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 92 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 93 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 94 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 95 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 96 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 97 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 98 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 99 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV A3-2

Condition 2 - Both ESST and SSST

  1. CUT SET 1 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 2 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 3 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 4 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 5 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 6 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 7 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 8 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 9 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 11 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 12 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 13 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 15 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 16 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 17 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 18 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 19 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 20 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 21 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 22 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 23 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 24 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 25 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 26 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 27 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 28 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 29 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 30 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 31 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 32 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 33 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 34 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 35 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 36 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 38 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 39 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 40 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 41 IE-TRANS,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 42 IE-TRANS,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 43 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 44 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 45 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 46 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 47 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 49 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 50 IE-TRANS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 51 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 52 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 53 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 54 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 55 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 56 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 58 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 59 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 60 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN A3-3
  1. CUT SET 61 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 62 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 63 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 64 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 65 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 66 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 67 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 68 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 69 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG 70 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG,RCI-XHE-XO-ERRLT 71 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 72 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 73 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 74 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 75 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 76 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 77 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 78 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 79 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 80 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 81 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 82 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 83 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 84 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 85 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 86 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 87 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 88 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 89 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 90 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 91 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 92 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 93 IE-TRANS,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 94 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 95 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 96 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 97 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 98 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 99 IE-TRANS,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1B,RRS-MDP-LK-SEALS A3-4

Larger common cause group Condition 1 - ESST only

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 3 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 4 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 5 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 6 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 7 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 8 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 9 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 11 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 12 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 13 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 14 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 15 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 16 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 17 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 18 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 19 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 20 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 21 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 22 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 23 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 24 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 25 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 26 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 27 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 28 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 29 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 30 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 31 IE-TRANS,DCP-BCH-CF-125 32 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 33 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 34 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 35 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 36 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR 37 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 38 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 39 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 40 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 41 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 42 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 43 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 44 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 45 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 46 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 47 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 48 IE-TRANS,DCP-BDC-CF-125AB 49 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 50 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 51 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 52 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 53 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 54 IE-LOSWS,CTM-INJ-RP-COOP,EHV-XHE-XM-ALTRC,IE-SWS-STR-CF-PE-AB 55 IE-MLOCA,ADS-XHE-XM-MDEPR-M,HCI-TDP-FR-TRAIN 56 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-LOOPSC,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV A3-5
  1. CUT SET 58 IE-TRANS,AACP-TFM-TM-SSST,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 59 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 60 IE-XLOCA,RPVRM 61 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 62 IE-LOOPSC,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 63 IE-LOOPSC,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 64 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 65 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 66 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 67 IE-TRANS,AACP-TFM-TM-SSST,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 68 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 69 IE-LOOPSC,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 70 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MWR,RCI-TDP-FR-TRAIN 71 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 72 IE-LOOPGR,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 73 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 74 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 75 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 76 IE-LOOPSC,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 77 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-TM-TRAIN,RCI-TDP-FR-TRAIN 78 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-TM-TRAIN 79 IE-LOOPSC,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 80 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 81 IE-LOACB-F,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRND,SPC-XHE-XL-NOREC 82 IE-LOACB-G,CVS-XHE-XL-LOAC,RHR-MDP-TM-TRNA,SPC-XHE-XL-NOREC 83 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 84 IE-LOOPSC,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 85 IE-LOOPGR,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 86 IE-LODCB-A,ADS-TSW-FT-DC125,HCI-TDP-FR-TRAIN 87 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 88 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 89 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 90 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 91 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR 92 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PG-AB,RCI-TDP-FR-TRAIN 93 IE-LOOPSC,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 94 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 95 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 96 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 97 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 98 IE-LOOPGR,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 99 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN A3-6

Condition 2 - Both ESST and SSST

  1. CUT SET 1 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 2 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 3 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 4 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 5 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 6 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 7 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 8 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 9 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 11 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 12 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 13 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 14 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 15 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 16 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 17 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 18 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 19 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 20 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 21 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 22 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 23 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 24 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 25 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 26 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 27 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 28 IE-TRANS,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 29 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 30 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 31 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 32 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 33 IE-TRANS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 34 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 35 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 36 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 38 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 39 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 40 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 41 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 42 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 43 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 44 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 45 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 46 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 47 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 48 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 49 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 50 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 51 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 52 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 53 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 54 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 55 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 56 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 58 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 59 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 60 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV A3-7
  1. CUT SET 61 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 62 IE-TRANS,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 63 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 64 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 65 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 66 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 67 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 68 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 69 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 70 IE-TRANS,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1A,PPR-SRV-OO-1VLV 71 IE-TRANS,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1B,PPR-SRV-OO-1VLV 72 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 73 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-2VLVS 74 IE-LOCHS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 75 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 76 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 77 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 78 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 79 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,EPS-XHE-XR-DG1A 80 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR12H,EPS-XHE-XR-DG1B 81 IE-TRANS,ADS-XHE-XM-MDEPR,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN 82 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 83 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 84 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 85 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 86 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 87 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 88 IE-TRANS,EPS-DGN-CF-FS,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 89 IE-TRANS,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 90 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 91 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 92 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 93 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 94 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR08H 95 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR08H 96 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 97 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 98 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 99 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN A3-8

Different common cause factor Condition 1 - ESST only

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 3 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 4 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 5 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 6 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 7 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 8 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 9 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 10 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 11 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 12 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 13 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 14 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 15 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 16 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 17 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 18 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 19 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 20 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 21 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 22 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 23 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 24 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 25 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 26 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 27 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 28 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 29 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 30 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 31 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 32 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 33 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 34 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 35 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 36 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 38 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 39 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 40 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 41 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 42 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 43 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 44 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 45 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 46 IE-TRANS,DCP-BCH-CF-125 47 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 48 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 49 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 50 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 51 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 52 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 53 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR 54 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 55 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 56 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 57 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN A3-9
  1. CUT SET 58 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 59 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 60 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 61 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 62 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 63 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 64 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 65 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 66 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 67 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 68 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 69 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 70 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 71 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 72 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 73 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 74 IE-TRANS,DCP-BDC-CF-125AB 75 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 76 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 77 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 78 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 79 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 80 IE-LOSWS,CTM-INJ-RP-COOP,EHV-XHE-XM-ALTRC,IE-SWS-STR-CF-PE-AB 81 IE-LOOPSC,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 82 IE-TRANS,AACP-TFM-TM-SSST,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 83 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 84 IE-MLOCA,ADS-XHE-XM-MDEPR-M,HCI-TDP-FR-TRAIN 85 IE-LOOPSC,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 86 IE-TRANS,AACP-TFM-TM-SSST,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 87 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 88 IE-LOOPSC,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 89 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 90 IE-XLOCA,RPVRM 91 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 92 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 93 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 94 IE-LOOPSC,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 95 IE-LOOPSC,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 96 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 97 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 98 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 99 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN A3-10

Condition 2 - Both ESST and SSST

  1. CUT SET 1 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 2 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 3 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 4 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 5 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 6 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 7 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 8 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 9 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 11 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 12 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 13 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 15 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 16 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 17 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 18 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 19 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 20 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 21 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 22 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 23 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 24 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 25 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 26 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 27 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 28 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 29 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 30 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 31 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 32 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 33 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 34 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 35 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 36 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 38 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 39 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 40 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 41 IE-TRANS,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 42 IE-TRANS,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 43 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 44 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 45 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 46 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 47 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 49 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 50 IE-TRANS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 51 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 52 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 53 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 54 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 55 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 56 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 58 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 59 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 60 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN A3-11
  1. CUT SET 61 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 62 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 63 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 64 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 65 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 66 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 67 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 68 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 69 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG 70 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG,RCI-XHE-XO-ERRLT 71 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 72 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 73 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 74 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 75 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 76 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 77 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 78 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 79 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 80 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 81 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 82 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 83 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 84 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 85 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 86 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 87 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 88 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 89 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 90 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 91 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 92 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 93 IE-TRANS,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 94 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 95 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 96 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 97 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 98 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 99 IE-TRANS,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1B,RRS-MDP-LK-SEALS A3-12

Loading the transformer Condition 1 - ESST only

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 3 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 4 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 5 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 6 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 7 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 8 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 9 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 10 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 11 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 12 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 13 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 15 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 16 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 17 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 18 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 19 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 20 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 21 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 22 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 23 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 24 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 25 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 26 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 27 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 28 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 29 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 30 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 31 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 32 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 33 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 34 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 35 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 36 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 37 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 38 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 39 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 40 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 41 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 42 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,RRS-MDP-LK-SEALS 43 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 44 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 45 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 46 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 47 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 49 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 50 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 51 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 52 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 53 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 54 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 55 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 56 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 57 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN A3-13
  1. CUT SET 58 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 59 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 60 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 61 IE-TRANS,DCP-BCH-CF-125 62 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 63 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 64 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 65 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 66 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 67 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 68 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 69 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 70 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 71 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 72 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 73 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 74 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR 75 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 76 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 77 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 78 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 79 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 80 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 81 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 82 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 83 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 84 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 85 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 86 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 87 IE-LOMFW,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 88 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 89 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 90 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 91 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 92 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 93 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,RRS-MDP-LK-SEALS 94 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 95 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 96 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 97 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 98 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,RRS-MDP-LK-SEALS 99 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV A3-14

Condition 2 - Both ESST and SSST

  1. CUT SET 1 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 2 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 3 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 4 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 5 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 6 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 7 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 8 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 9 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 11 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 12 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 13 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 14 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 15 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 16 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 17 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 18 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 19 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 20 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 21 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 22 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 23 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 24 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 25 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 26 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 27 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 28 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 29 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 30 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 31 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 32 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 33 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 34 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 35 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 36 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 38 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 39 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 40 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 41 IE-TRANS,EPS-DGN-CF-FR,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 42 IE-TRANS,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 43 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 44 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 45 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 46 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 47 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 48 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 49 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 50 IE-TRANS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 51 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 52 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 53 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 54 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 55 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 56 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 58 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 59 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 60 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN A3-15
  1. CUT SET 61 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 62 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 63 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 64 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 65 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 66 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 67 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 68 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 69 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG 70 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG,RCI-XHE-XO-ERRLT 71 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 72 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 73 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 74 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 75 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 76 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 77 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 78 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 79 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 80 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 81 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 82 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 83 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 84 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 85 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 86 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 87 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 88 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 89 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RRS-MDP-LK-SEALS 90 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 91 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 92 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 93 IE-TRANS,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 94 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,RCI-TDP-FR-TRAIN,RRS-MDP-LK-SEALS 95 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 96 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 97 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 98 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 99 IE-TRANS,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1B,RRS-MDP-LK-SEALS A3-16

No recirculation pump seal failure Condition 1 - ESST only

  1. CUT SET 1 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 2 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 3 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 4 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 5 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-2VLVS,SWS-XHE-XL-NOREC 6 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 7 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV 8 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 9 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PE-AB,SWS-XHE-XL-NOREC 10 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 11 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 12 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 13 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 14 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 15 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 16 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 17 IE-LOCHS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 18 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 19 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 20 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-1VLV 21 IE-LOSWS,CVS-AOV-CC-PC237,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 22 IE-LOSWS,CVS-AOV-CC-PC032,IE-SWS-STR-CF-PG-AB,SWS-XHE-XL-NOREC 23 IE-LOMFW,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 24 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 25 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 26 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 27 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 28 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 29 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 30 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 31 IE-LOSWS,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 32 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 33 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 34 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 35 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 36 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 38 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 39 IE-TRANS,RHR-XHE-XM-ALLDHR,SPC-XHE-XL-NOREC 40 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 41 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 42 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 43 IE-LOACB-G,ADS-XHE-XM-MDEPR,RCI-TDP-FR-TRAIN 44 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 45 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 46 IE-TRANS,DCP-BCH-CF-125 47 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 48 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 49 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MGR,RCI-TDP-FR-TRAIN 50 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 51 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 52 IE-LOSWS,CTM-INJ-RP-COOP,HCI-TDP-FR-TRAIN,IE-SWS-STR-CF-PE-AB,RCI-TDP-FR-TRAIN 53 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,OEP-XHE-XL-NR30MSC,RCI-TDP-FR-TRAIN 54 IE-LOMFW,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 55 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 56 IE-LOOPWR,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,OEP-XHE-XL-NR12HWR A3-17
  1. CUT SET 57 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 58 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 59 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 60 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 61 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 62 IE-TRANS,AACP-BUS-CF-FAIL,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 63 IE-LOOPGR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 64 IE-LOMFW,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 65 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 66 IE-LOSWS,CDS-XHE-XM-CSTRFL,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 67 IE-LOSWS,BWR-XHE-XM-NRCST,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 68 IE-LOSWS,CVS-XHE-XM-VENT,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 69 IE-LOOPWR,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 70 IE-LOOPGR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 71 IE-LOOPGR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HGR,PPR-SRV-OO-1VLV 72 IE-LOSWS,CTM-INJ-RP-COOP,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 73 IE-LOCHS,ADS-XHE-XM-MDEPR,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 74 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 75 IE-LOCHS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 76 IE-TRANS,DCP-BDC-CF-125AB 77 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 78 IE-LOOPWR,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 79 IE-LOOPWR,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HWR,PPR-SRV-OO-1VLV 80 IE-LOSWS,IE-SWS-STR-CF-PG-AB,PPR-SRV-OO-3VLVS,SWS-XHE-XL-NOREC 81 IE-LOSWS,CTM-INJ-RP-COOP,EHV-XHE-XM-ALTRC,IE-SWS-STR-CF-PE-AB 82 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 83 IE-MLOCA,ADS-XHE-XM-MDEPR-M,HCI-TDP-FR-TRAIN 84 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 85 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 86 IE-LOOPSC,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 87 IE-TRANS,AACP-TFM-TM-SSST,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 88 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 89 IE-LOCHS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 90 IE-LOSWS,CVS-MOV-CC-PC233,IE-SWS-STR-CF-PE-AB,PPR-SRV-OO-1VLV,SWS-XHE-XL-NOREC 91 IE-XLOCA,RPVRM 92 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 93 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 94 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 95 IE-TRANS,AACP-BUS-CF-FAIL,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 96 IE-LOOPSC,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 97 IE-LOOPSC,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,OEP-XHE-XL-NR04HSC,PPR-SRV-OO-1VLV 98 IE-LOOPSC,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 99 IE-TRANS,AACP-BUS-CF-FAIL,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT A3-18

Condition 2 - Both ESST and SSST

  1. CUT SET 1 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 2 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 3 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 4 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 5 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 6 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 7 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 8 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 9 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 10 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 11 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 12 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 13 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 14 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 15 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 16 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 17 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 18 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 19 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 20 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-LR-DG1B,EPS-XHE-XL-NR12H 21 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-LR-DG1A,EPS-XHE-XL-NR12H 22 IE-TRANS,ADS-XHE-XM-MDEPR,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 23 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 24 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 25 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 26 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 27 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 28 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 29 IE-TRANS,EPS-DGN-CF-FR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 30 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-FS-DG1A,EPS-XHE-XL-NR12H 31 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FS-DG1B,EPS-XHE-XL-NR12H 32 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 33 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 34 IE-TRANS,ADS-XHE-XM-MDEPR,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 35 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 36 IE-LOCHS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 37 IE-LOCHS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 38 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 39 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 40 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 41 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 42 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 43 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 44 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 45 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 46 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 47 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 48 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 49 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 50 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H 51 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG 52 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG,RCI-XHE-XO-ERRLT 53 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 54 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 55 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 56 IE-TRANS,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 57 IE-TRANS,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 58 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 59 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-TDP-FR-TRAIN 60 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H A3-19
  1. CUT SET 61 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-LR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 62 IE-LOMFW,EPS-DGN-CF-FR,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 63 IE-TRANS,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 64 IE-TRANS,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 65 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 66 IE-LOMFW,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 67 IE-LOMFW,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 68 IE-TRANS,CVS-XHE-XL-LOIAS,RHR-XHE-XM-SPC,SPC-XHE-XL-NOREC 69 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 70 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 71 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FS-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 72 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 73 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H 74 IE-LOMFW,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 75 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 76 IE-TRANS,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1A,PPR-SRV-OO-1VLV 77 IE-TRANS,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR04H,EPS-XHE-XR-DG1B,PPR-SRV-OO-1VLV 78 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-MOV-CC-IVFRO,HCI-MULTIPLE-INJECT,HCI-XHE-XL-INJECT,RCI-TDP-FR-TRAIN 79 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-2VLVS 80 IE-LOCHS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 81 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR30M,HCI-TDP-FR-TRAIN,RCI-TDP-FR-TRAIN 82 IE-TRANS,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 83 IE-TRANS,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR30M,HCI-XHE-XO-ERRSBO,RCI-TDP-FR-TRAIN 84 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-XHE-XL-NR12H,EPS-XHE-XR-DG1A 85 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-XHE-XL-NR12H,EPS-XHE-XR-DG1B 86 IE-TRANS,ADS-XHE-XM-MDEPR,EPS-DGN-FR-DG1B,RCI-TDP-FR-TRAIN 87 IE-LOCHS,CVS-XHE-XM-VENTLT,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H 88 IE-LOCHS,EPS-DGN-FR-DG1A,EPS-DGN-FR-DG1B,PPR-SRV-OO-1VLV,RCI-TDP-FR-TRAIN 89 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 90 IE-TRANS,CDS-XHE-XM-RFLCSTLT,CVS-XHE-XM-VENTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR12H 91 IE-TRANS,EPS-DGN-CF-FR,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG,RCI-XHE-XO-ERRLT 92 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-CF-FR,EPS-XHE-XL-NR08H,EPS-XHE-XM-PDG 93 IE-TRANS,CDS-XHE-XM-RFLCSTLT,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H 94 IE-TRANS,EPS-DGN-CF-FR,EPS-DGN-FR-PDG,EPS-XHE-XL-NR08H,RCI-XHE-XO-ERRLT 95 IE-TRANS,EPS-DGN-CF-FS,EPS-XHE-XL-NR04H,PPR-SRV-OO-1VLV 96 IE-TRANS,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,EPS-XHE-XM-PDG,RCI-TDP-FR-TRAIN 97 IE-TRANS,EPS-DGN-FR-PDG,EPS-DGN-TM-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR04H,RCI-TDP-FR-TRAIN 98 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1B,EPS-DGN-TM-DG1A,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT 99 IE-TRANS,CVS-XHE-XM-VENTLT,EPS-DGN-FR-DG1A,EPS-DGN-TM-DG1B,EPS-XHE-XL-NR12H,RCI-XHE-XO-ERRLT A3-20

Details on the approach to quantify the consequential failure of the SSST The analyst examined photographs of the interior and exterior of the bus ducts between the emergency station service transformer (ESST) / startup station service transformer (SSST) and the turbine building. From these photographs, the ESST duct bottom external supports were assumed to be spaced either 6 feet or 8 feet apart. Also from photographs, the ESST duct internal supports were assumed to be spaced either 2, 2.5, 3, 3.5, 4, 4.5, 5, or 6 feet apart.

Combining the various combinations of internal and external support spacing yielded a range of values for the percentage of internal supports which would not be at the same location as external supports. This exercise produced a range of values between 17 and 83 percent of internal supports which would not be located at an external support. From this range, the analyst chose a 6-foot external support spacing and 3-foot internal support spacing as the point estimate based on the most frequently observed conditions in the photographs. This choice of spacing representative of the entire duct run predicted the 50 percent of the internal supports would not be located near an external support. This assumption contained uncertainties that would drive the estimate higher and lower.

The analyst then assumed half any postulated arc fault events would dissipate their energy downward based on the orientation of internal supports in the duct and any such downwardly directed fault over an area which was not externally supported would lead to breaching the SSST duct.

Attachment 4

Segregated bus common cause failure values used for base case and ESST fault case Base case: 7.01E-7 ESST fault case: 3.06E-2 Attachment 5

E-mail Correspondence -

From Mr. O. Olson, NPPD To Mr. R. Deese, NRC Dated August 21, 2017 From: Olson, Ole H.

To: Deese, Rick

Subject:

[External_Sender] ESST Bus Failure Call - Wayne Schmidt Date: Monday, August 21, 2017 7:20:43 AM Rick:

This email requests the following in support of follow up activities at Cooper Nuclear Station as we continue to support the significance determination process for the ESST bus fault.

1. Cutsets for the base case SPAR internal events PRA
2. Cutsets for the case that represents the performance deficiency
3. Cutsets for the sensitivity cases summarized in inspection report 2017-011 dated August 14, 2017
4. Details on the approach to quantify the consequential failure of the SSST
5. Segregated bus common cause failure values used for base case and ESST fault case Thank you, Ole Olson Ole Olson Cooper Nuclear Station Risk and Fire Programs Engineering Programs and Components Department Phone: (402) 825-5092 Email: oholson@nppd.com Attachment 6