ML17261A810
| ML17261A810 | |
| Person / Time | |
|---|---|
| Site: | Ginna |
| Issue date: | 12/29/1988 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | |
| Shared Package | |
| ML17261A809 | List: |
| References | |
| 50-244-88-24, NUDOCS 8901120400 | |
| Download: ML17261A810 (4) | |
Text
APPENDIX A NOTICE OF VIOLATION Rochester Gas and Electric
- Company, R.
E. Ginna Nuclear Station Docket No.
50-244, License No.
DPR-18 As= a result of the inspection conducted on November 15-17,
- 1988, and in accordance with the "General Statement. Policy and Procedure, for NRC Enforcement Actions",
10CFR Part 2, Appendix C (Enforcement Policy 1988) the following violations were identified:
A.
10 CFR 50, Appendix R, Section III.G requires that fire protection features be provided to safe shutdown components so that one train of
.systems required to achieve hot shutdown is free of fire damage.
One method of ensuring that one of the redundant trains remains free of fige damage is the enclosure. of cables and equipment in a fire barrier having a one hour rating.
Contrary to the above, as a result of an inspection conducted on September 8-22, 1988, it was determined that the redundant train that provides steam generator pressure
.indication would not be free of damage by a fire in the Intermediate Building, elevation 253'-6"
~
Also, the redundant train that provides primary coolant make up would not be free of damage from a fire in the Auxiliary Building, Fire area ABBM.
These redundant safe shutdown trains would be damaged by fire because the one hour fire barrier provided for cable enclosure was improperly installed.
The improperly installed fire barrier was the one hour rated fire wrap which protects conduit R975 for steam generator pressure indication and the fire wrap of conduits L400 and L398 required for the operation of charging pump lA.
This is a Severity Level IV Violation (Supplement I).
B, License Condition C.(3) Fire Protection, requires that the licensee maintain in effect all fire protection features described in the NRC's Fire Protection Safety Evaluation (SE) dated February 14, 1979.
The SE in paragraph
- 3. 1.31 requires that quarterly fire drills be conducted for each shift brigade and in paragraph 6.2 it requires that the quarterly drills be preplanned.
esOa>
04 OKoOO244
()cj 8.='i22+
P [Ifi AGOG K pP C.
rq
Appendix A Contrary to the, above, on November 15-17, 1988, it 'was determined that the licensee did not perform preplanned fire drills quarterly for all shift brigades.
In the first quarter of 1988, four out of five shift brigades did not attend a preplanned fire drill, in the second quarter two out of five shift brigades did not participate in a preplanned fire drill and in the third quarter three out of six shift brigades did not participate in a preplanned fire drill.
This is a Severity Level V Violation (Supplement I)
Pursuant to 10 CFR 2.201, Rochester Gas and Electric Company is hereby required to submit to this office, within 30 days of the date of the letter transmitting this Notice, a written statement or explanation in reply, including:
( 1) The reasons for the violations; (2) the corrective steps which have been taken and the results achieved; (3) corrective steps which will be taken to avoid further violations; and (4) the date when full compliance will be achieved.
Where good cause is shown, consideration will be given to extending this response time.
48