ML17254A649

From kanterella
Jump to navigation Jump to search
Documents Understanding Reached W/Nrc Re full-term OL Fire Protection Condition.New Plant Process Computer Sys Will Be Installed in Spring 1986.Existing Computer Room Floor Will Be Removed & Wires Relocated
ML17254A649
Person / Time
Site: Ginna 
Issue date: 11/27/1985
From: Kober R
ROCHESTER GAS & ELECTRIC CORP.
To: Lear G
Office of Nuclear Reactor Regulation
References
RTR-NUREG-0737, RTR-NUREG-737 NUDOCS 8512030290
Download: ML17254A649 (6)


Text

REGUL'ATORY I ORMATION DISTRIBUTION SYST It (RIOS)'CCESSION

@BR;85120>0290 DOC.DATE: S5/11/27 NOTARIZED'O DOCKET FACIL~'50 244 Robert Emmet Ginna Nuclear Planti Unit ii Rochester G

05000244 AUTH'AME AUTHOR AFFILIATION KOBERpR ~ HE Rochester Gas 8 Electric Corp, RECIP ~ NAME RECIPIENT AFFILIATION LEARgG ~ ED PHR Project Directorate

SUBJECT:

Documents understanding reach w/NRC re full term OL fire protection condition. New plant process computer sys will be installed in Spring 1966,Existing computer room floor will be removed 8 wires relocated, DISTRISUTIOil CDOE:

00000 COPIES RECEIVED:LTR $

ENCL SIZE:

TITLE:

OR Submittal: Fire Protection NOTES:NRR/DL/SEP 1cy ~

OL: 09/19/69 05000244'ECIPIENT IO CODE/NAMEl PHR A

PD1 PO 01 INTERNALI0 ACRS 1.1 ELD/HOS4 NRR BAR DIR NRR P tiR~B DIR NRR HERMEILrJ06 NRR/OSRO DIR RGN1 "EXTEfAALi: 24X NRC POR 02 NOTES:

COPIES L'T l'R ENCL 1

1 1

1 1

~

1 1

1 1

1 RECIP IEIVT<

IO CODE/IVAME LPDR NSIC 0$

05 ADM/LFMB IE NHITNEYgL'RR PAR A DIR NRR STANGgJ.

07 DIR G FIL 04 COPIES LTTR ENCL t

~ t TOTAL NUMBER OF COPIES REQUIRED:

LTTR 24 ENCL

r~

ll X

~

ri l

t

/III g 1

Ji

ROCHESTER GAS AND ELECTRIC CORPORATION o 89 EAST AVENUE, ROCHESTER, N.K 14649.0001 ROGER W. KOBER VICE PIIESIDENT ELECTRIC &STEAM PRODUCTION TELEPHONE

  • PC*CODE TIS 546-2700 November 27I 1985 Director of Nuclear Reactor Regulation Attention:

Mr. George E. Leari Chief PWR Project Directorate No.

1 U.S. Nuclear Regulatory Commission Washingtoni D.C.

20555

Subject:

Modification to Computer Room Fire Detection Zone Specified in Technical Specifications R.

E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Lear:

The purpose of this letter is to document an understanding reached with members of the NRC Staff concerning the Ginna Full Term Operating License fire protection condition.

Rochester Gas and Electric Corporation (RGSE) will install a new plant process computer system (PPCS) at Ginna in the Spring of 1986.

The PPCS is necessary to support the new Safety Assessment System required by NUREG-0737.

As a result of the PPCS installation>

the existing computer room floor will be modified.

The raised floor will be

'removed and wires for the computer will be relocated to a wire way

'nder 'the new PPCS.

A condition of the Ginna License requires that no modifica-tion be made to fire protection features that would decrease the current level of fire protectionl or otherwise would require a

Technical Specification change>

without NRC Staff review and approval.

The planned modification will not decrease the level of fire protection because detection and automatic actuation of Halon suppression will be retained.

However>

the current Technical Specifications specify two fire detection zones in the computer room<

Zone S07 under the raised floor and zone Z17 at the ceiling.

Currently Z17I the ceiling zonei is only used to actuate an alarm.

The under-floor zoner S07I is used to actuate the Halon system.

Modifications to the room to accommodate the PPCS will result in the Halon system being actuated by the ceiling zone.

The S07 detection zone will be removed along with the raised floor.

Neither the amount of Halon injected nor the concentration will be affected by this modification.

85>20302+0 8~

0~44 PDR ADOCK 0500PDR F

e S

I

~ ~

i II t

ROCHESTER GAS AND ELECTRIC RP.

DATE November 27 I 1985 Mr. George E. Lear SHEET NO.

The proposed modification to the fire zones has been discussed with members of your Staf f and the following conclusions were reached:

When detection zone S07 is made inoperablei a fire watch patroli as required by Technical Specification 3.14.l.lai will be established.

The fire watch patrol will continue until automatic actuation capability of the Halon system is reinstated using detection zone Z17.

A license amendment application will be submitted to delete zone S07 from the Technical Specifications.

The modification can be made prior to issuance of the Technical Specification amendment.

These conclusions meet the requirements of the Ginna Full Term Operating License fire protection paragraph.

The level of fire protection previously approved by the NRC Staff will be maintained during and after completion of the modification.

No NRC approval< other than for the license amendment to delete Zone S07 from the Technical Specifications>

is required to proceed with the modification.

V truly yoursi