USAEC HQS GTWN f97J NOV.13* PM 7 ~l rwu
~tSH
. TLXA239 WAD3 57 c I 720 > < l-027866C 31 7002 >PD I 1'11 ~A5J AfLTalQ ENERGY COMM
. T W X UNIT ICS IPMVEI G MVN 07171 TOVE MORRIS IL 114 11-13 310P CST 50-249 PMS MR A GIAM~USSO
~PUTY* DIRECTO~ FOR REACTOR PROJECTS DIRECTORIATE OF LICENSING UX U S ATOMIC ENERGY COMMISSION WASH DC 20 545 Regulatory_
File Cy.
SUBJECT:
DPR-25 DRESDEN NUCLEAR POWER STATION UNIT #3 lHIS WILL CONFIRM A CONVERSATION WITH MR H DANCE OF YOUR OFFICE AT
~ 42 SH OURS TH IS. DATE CONCERN I NG HPC I HIGH STEAM FLOW ISOLATION CENSORS OUT OF CALIBRATION.
~ 11-12-73 THE INSTRUMENT DEPARTMENT MADE A QUARTERLY CALIBRATION
~ HPCI HIGH STEAM FLOW ISOLATION CENSORS. TABLE 3.2.1 OF THE KCHNICAL SPECIFICATION STATES THE TRIP LEVEL SETTING WILL BE LESS THAN OR EQUAL TO 150 INCHES OF WATER. OPIS 3-2352 TRIP SETTING
. AS FOUND. 152 INCHES OF WATER* DPIS 3-2353 TRIP SETTING WAS FOUND 16Q INCHES OF WATER~ THE TRIP SET POINT WERE IMMEDIATELY RESEt ro 146 PLUS OR LESs-2 INCHES OF WATER.
WP WORDEN SUPERINTENDENT DRESDEN NUCLEAR POWER.STATION
.RT 1. MORRIS ILLINOIS l\\NNN 731P EDT NOV 13 1973 USAEC HQS GTWN WU WSH WESTERN UNl:OM U~CO.MUID.
~
- ~
.