]pegulatory Docket file 0

5 0- 2 4 9

  • ~~-rH
  • .~

... oo..

USAEC HQS GTWN WU WSH.

TLXA 1 96 WAG201C1739JC1-039094Cl44>PD

  • ~.

ICS IPMV EIC MVN 03259.TOVE MORRI$ IL '124 05-24 201P COT PMS MR J F O'LEARY DIRECTOR DIRECTORATE OF LICENSING WU~

$.ATOMIC ENERGY COMMISSION WASHINGTON PC 20545 1974 MAY 24 PM 9, 20':

SUBJECT OPR-25 DRESDEN NUCLEAR POWER STATION UNIT THREE lHIS WILL CONFIRM A CONVERSATION WITH F MAURA OF YOUR OFFICE AT 1345 HOURS THIS DA.TE CONCERNING T-HE DISCOVERY DURING ROUTINE WARTERLY CALIBRATION CHECKS OF. A SET POINT DRIFT OF

~1.T.s. 3-263-72A BEYOND THE PREMISSABLE VALVE GIVEN I

'TABLE 3.2.2. OF.THE TECHNICAL SPEC~FICATION.

THIS SWITCH WHICH JS THE SO CALLED 2/3 CORE COVERAGE INTERLOCKS FOR CONTAINME~T COO.LING WAS FOUND TO OPERATE: AT 259 INCHES OF WATER DECREASING

~ICH IS ABOVE THE PREMISSABLE SET POINT OF 257 INCHES OF WATER I

DECREASI.N~*

THE SWI T~ WAS RESET T.O OPERATE 254* 5 INCHES OF WAT~R*

ADDITIONAL DETAILS WILL BE FORTHCOMMING IN THE

. FQR~,QF A JEN.DAY LETTER IN ACCORDANCE WITH SECTIONS 6.6.}J.t.A CF THE TECHNICAL SPECIF.IGATIONS I

BB SJEPH~NSQN, SUPERINTENDENT PRESD~~ NUCLEAR POW~R.STATION COf1MQNWE~L.TH EDISON COMPA!\\IY

.. R. R I _MORRJ_S.IL ~04~~

822P EDT USA.EC HQS GTWN

\\

I

\\,,.

    • -.. *~,,,. '......

0