Consolidated Edison Company of New York, Inc.

4 Irving Place, New York, NY 10003 Mr. James P. O'Reilly, Director Regulatory Operations, Region 1 U.S. Atomic Energy Commission 631 Park Avenue

'King of Prussia, Pennsylvania 19406

Dear Mr. O'Reilly:

August 23, 1973 Indian Point Station Re:

Facility Operating License DPR-26 In accordance with the Technical Specifications of Facility Operating License No. DPR-26, we wish*to inform you of an Abnormal Occurrence (A.O. 3-2-11) which was identified on August 22, 19.7 3.

Periodic Surveillance Test PT-Mll, '**steam Line Pressure An-alog Chanrlel Functional Test" was performed during power op-eration at approximately 49% power. *The instrument setting for one channel of the low steam line pressure controllers in the high steam flow safety circuit was found to be below that required by Table 3-1, No. 5 (577 versus 600 psig).

The remaining three channels were found to be operating cor-rectly.

The channel was recalibrated and retested satisfac-torily.

Saf e~y implications of this occurrence are considered to be slight since the remaining three channels of the 2 out of 4 actuation logic' were set correctly and would have functioned if required.

Mr. Fasano of your offi~e was notified of this occurrence by telephone on August 22, 1973.