ae

~~~~ p44$

lggWZFIj'<fllllk/ZZ ROCHESTER GAS AND ELECTRIC.CORPORATION o

89 EAST AVENUE, ROCHESTER, N.Y. 14649 LEON D. WHITE. JR.

VICE PRE5IOENT TEI.EPHONE AREA CODE Tld 546-2700 April 25, 1980 Mr. Boyce H. Grier, Director U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King 'of Prussia, Pennsylvania 19406

Subject:

IE Bulletin 79-17 Revision 1 Response - results of additional welds inspected R. E. Ginna Nuclear Power Plant, Unit 41 Docket No. 50-244

Dear Mr. Grier:

On November 26, 1979 Rochester Gas and Electric Corporation pro-vided an initial response to Revision 1 of the subject I&KBulletin 79-17, which indicated that an additional seven (7) welds would require examina-tion.

These welds are located on our Charging and Safety Injection systems, and we indicated they would be examined during our 1980 Refueling Outage.

This letter is to confirm that these seven welds have been examined in accordance with the requirements of Item 2B of I&E Bulletin 79-17, Revi-sion 1.

The following is a listing of the welds examined and the examina-tion results:

Charging System (4" Suction from RWST) 4-CH-2001-7 No Indications 4-CH-2001-17 No Indications 4-CH-2 00 1-20 No Indications Safety Injection (4" Suction from RHR Discharge) 4-RH-2014-22 No Indications Safety Injection (4" Suction from BAST's) 4-SI-2003-29 1/32" Deep undercut at edge of weld crown 4-SI-2004-25 No Indications 4-SI-2008-14 No Indications 8 Q Q 5 2 V vA'~

~

P MROCHESTER GAS AND ELECTRI RP.

DATE April 25, l980 To Mr. Boyce H. Grier, Director SHEET NO. 2 The indication identified on weld 4-SI-2003-29 was repaired in accordance with our Emergency Maintenance procedures and reexamined with no indications.

This particular indication does not indicate the sub-ject weld or adjacent base metal has undergone any stress corrosion cracking attack.

Very truly yours, L. D. White, Jr.

xc:. Director Division of Operating Reactors U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Washington, D. C.

20555

yC