Recommends That Licensee Proposal on Fire Protection Review Item 3.2.6 Re Backflow Protection Be Accepted Subj to Review of Four Listed Documents.Also Recommends That Fire Brigade Size Be Increased to Five Men
ML17249A883
Person / Time
Site: Ginna Constellation icon.png
Issue date: 01/23/1980
From: Randy Hall
BROOKHAVEN NATIONAL LABORATORY
To: Ferguson R
Office of Nuclear Reactor Regulation
Shared Package
ML17249A882 List:
References
NUDOCS 8005070012
Download: ML17249A883 (2)


Text

3 IIT'II Departrrent of Nuclear Energy ENCLOSURE 3 e

BROOKHAVEN NATIONALLABORATORY ASSOCIATED UNIVERSITIES, INC.

Upton, New York 11973 (516) 345-2I44 January 23, 1980 Mr. Robert L. Ferguson Plant Systems Branch U.S. Huclear Regulatory Commission Washington, D.C.

20555 RE:

Ginna Huclear Power Plant Fire Protection Review Items 3.2.6 and 3.2.9

Dear Bob:

Item 3.2.6 Backflow Protection The Safety Evaluation Report (SER) stated that the licensee will review the p1ant's drain systems and provide backflow protection, to prevent the spread of a possible liquid fire via the drain systems, where drains'frcm safety-related areas tie into drains from other areas which contain a large quantity of flammable liquid and which could affect the safety-related area.

A report of this review was given by the licensee in a letter dated September 28, 1979.

They confirmed that they found potential drain problems in the contaireent, the aux'iliary building basement, intermediate building basement and the B diesel generator room.

The licensee further stated that these drains will be modified to ensure that ccmbustible or flammable liquids will not be allowed to flow via the drain system to a separate safety related area.

In order to fully evaluate the licensee's proposal we request that the licensee's submit:

prints of the drain system, location of the problem

drains, method of analysis and method of solution.

We reccmmend that the licensee's proposal on this item be accepted subject to review of the documents listed above.

Item 3.2.9 Fire Bri ade Size The SER states that the licensee has proposed a three'man fire brigade and further states that the staff is not convinced that three men provide suffi-cient margin for adverse conditions that may occur in the event of a signifi-cant fire.

This item is, therefore, unresolved at this time.

To.

R.

L Ferguson 8

January 18, 1980 On the plant site visit, June 27-30, 1978 the licensee had stated that their three man fire brigade was sufficient.

Ne took a position stated in our consultant's report of July 10, 1978 that the brigade size was inadequate and that it should be increased to five men.

The licensee, in their letter of May 25, 1979 agreed to having a five-man fire brigade.

We reccmmend that this position be accepted.

Respectfully yours,

+.pP~ p,~~

Robert E. Hall, Group Leader Reactor Engineer i ng Anal ys is REH:EAN:sd

'cc.:

R.

Cerbone W. Kato

4. Lee E. MacDougall V.= Panci era