  • E~TtRN UNION U~GUMING **

+

  • \\912 MAY 8 PM 3 47*,*...

USAEC HQS GTWN WU WSH.t TLXA117 PA160 Q NNH096 <CH 1,29*;,530096>PD WU JOL

  • 0J 30P ZCZC 2 NL\\PDF MORRIS ILL 4 415P CDT DR PETER A MORRIS,.DIRECTOR DIVN OF 'REACTOR LICENSING

___:_~----:"""~------*

  • -,..---~~~'

US ATOMIC E~ERGY COMMISS~ WASHDC 20545 BT DP R 25 DRESDEN:NUCLEAR POWER STATION UNIT 3:

THIS WILL CON~l~M CO~VERSATIO~ AT 15:00 HRS THIS DATE WITH H

\\.

I REGARDING FAILURE OF THE ISOLATIO~ CONDENSQR VALVE 3~1301-3 io OPEN ELECTRIC~LLY FOLLOWING ~ ~EACTOR StRAM*. IMMEDfATELY FOLLO~IN~

THE SCRAM WHICH OCCURRED AT 090*1 HRS A GROUP 1 ISOLATION OCCURED BECAUSE OF A HIGH _WATER LEVEL CONDITION.

AN ATTEMPT WAS MADE TO PLACE THE ISOLATION CONDENSOR 1N SERVICE BUT VALVE 3-1301-3 WOULD NOT OPEN. AN OPERATOR AD TO GO TO THE VALVE I

-~~1*

AND MANUALL~ CRAKE THE VALVE OFF ITS SEAT. ONCE THE VALVE WAS 2~16*

~a5fi I

\\

  • OPENED ITS BREAKER RE-SET AND Ir FUNCTIONED PROPERLY*

~---..

l*

I WHILE THE OPERATOR ~AS WORKING ON PLACING THE

~SOLA~ION CONDENSOR IN SERVICE REACTOR PRESSURE INCREASED TO APPROXIMATELY I

1100 PSIG AT THIS PRESSURE 3A ELECTROMATIC VALVE OPENS AUT0M~1lCALLY.

'WHE,N THE ELECTROMAT IC VALVE OPENED THE DRY WELL PRE*SSURE I MME DI ATE LY INCREASED TO 2.s PSI~* AFTER,IEAKING AJ 2.sc PSIG THE FRYWELL PRESSURE RETURNEF TO NORMAL.

I A COMPLETE DRYWELL IN PECTION WILL SE MADE WHEN ENTRY IS POSSIBLE TO DETERMINE THE CAUSE.OF THE PR~SSUR1~ATf ON AND' TO DElERMINE IF ANY EQUIPMENT HAS BEEN DAMAGED AS A RESULf OF THIS PRESSURIZ~tION IN ADDITION A COMPLETE CHECK-OUT WILL EBE MADE ON

~ALVE 3-1301*3 OF THE ISO~ATibN'CONDENSOR TO DETERMINE WHY IT FAILED TO OPEN W P WORDEN PLANT SUPERINTENDENT DRESDEN NUCLEAR PbWER STATION

~*