Amend 98 to License NPF-16,revising Table 2.2-1 Notations in TS Section 2.2.1 & Table 3.3-1 Notations in TS Section 3/4.3.1,by Replacing Term Thermal Power with Explicit Parameters Based on Output of Excore Neutron Flux Monitors
ML17229A919
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 11/24/1998
From: Hebdon F
NRC (Affiliation Not Assigned)
To:
Shared Package
ML17229A920 List:
References
NUDOCS 9811300238
Download: ML17229A919 (8)


Text

gPR RE00

~4

~o Cy A,

ClO IIh O~

Cy qO

++*++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON> D.C. 205554001 FLORIDA 0 ER 8 LIG CO PA ORLANDO UTILITIESCOMMISSION OF T

Cl OFO LAND L

D

~ND FLORIDA M I

I WE A

E D CE

-89 S

LUC E PLANT UNIT N MENDME TTO FACILITYOPERATING LI EN Amendment No.%

License No. NPF-16

1. The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Florida Power & Light Company, et al. (the licensee),

dated October 29, 1998, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facilitywilloperate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

98ii300238 98ii24 PDR ADQCK 05000389 P

PDR 1

~

~

0 2.

Accordingly, Facility Operating License No. NPF-16 is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and by amending paragraph 2.C.2 to read as follows:

2.

Tech ic IS ecifi a io s The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 98, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance and shall be implemented immediately upon receipt.

FOR THE NUCLEAR REGULATORYCOMMISSION Frederick J. Hebdon, Director Project Directorate II-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

bbverber 24, 1998

r

~

, ~

ATTACHM NTTO I

EN EA ENDME TNO +

TO FACILI OPERATI LICENSE NO NPF-16 D GET 9

Replace the following pages of the Appendix "A"Technical Specifications with the enclosed pages.

The revised pages are identified by amendment number and contain vertical lines indicating the area of change.

ovePa e

nsertPa e

2-6 3/4 3-3 2-6 3/4 3-3

TABLE2.2-1 (Continued)

REACTOR PROTECTIVE INSTRUMENTATIONTRIP SETPOINT LIMITS TABLE NOTATION (1)

Trip may be manually bypassed below 0.5% of RATED THERMALPOWER during testing pursuant to Special Test Exception 3.10.3; bypass shall be automatically removed when the Wide Range Logarithmic Neutron Flux power is greater than or equal to 0.5% of RATED THERMALPOWER.

(2)

Trip may be manually bypassed below 705 psig; bypass shall be automatically removed at or above 705 psig.

(3)

% of the narrow range steam generator level indication.

(4)

Trip may be bypassed below 10 % and above 15% of RATEDTHERMALPOWER; bypass shall be automatically removed when Wide Range Logarithmic Neutron Flux power is > 10 % and Power Range Neutron Flux power < 15% of RATED THERMALPOWER.

(5)

Trip may be bypassed below 15% of RATED THERMALPOWER; bypass shall be automatically removed when Power Range Neutron Flux power is greater than or equal to 15% of RATED THERMALPOWER.

ST. LUCIE-UNIT2 2-6 Amendment No. 98

~ ~

TABLE3.3-1 (Continued)

TABLENOTATION

  • With fhe protective system trip breakers in the closed position, the CEA drive system capable of CEA withdrawal, and fuel in the reactor vessel.

The provisions of Specification 3.0.4 are not applicable.

(a)

Trip may be manually bypassed below 0.5/o of RATED THERMALPOWER in conjunction with (d) below; bypass shall be automatically removed when Wide Range Logarithmic Neutron Flux power is greater than or equal to 0.5/0 of RATED THERMALPOWER.

(b)

Trip may be manually bypassed below 705 psig; bypass shall be automatically removed at or above 705 psig.

(c)

Trip may be bypassed below 15/o of RATED THERMALPOWER; bypass shall be automatically removed when Power Range Neutron Flux power is greater than or equal to 15/o of RATED THERMALPOWER.

(d) Trip may be bypassed during testing pursuant to Special Test Exception 3.10.3 (e)

Trip may be bypassed below 10

/0 and above 15/o of RATED THERMALPOWER; bypass shall be automatically removed when Wide Range Logarithmic Neutron Flux power is > 10

/o and Power Range Neutron Flux power < 15/o of RATED THERMALPOWER.

k (f)

Each channel shall be comprised of two trip breakers; actual trip logic shall be one-out-of-two taken twice.

(g) There shall be at least two decades of overlap between the Wide Range Logarithmic Neutron Flux Monitoring Channels and the Power Range Neutron Flux Monitoring Channels.

ACTION STATEMENTS ACTION 1 With the number of channels OPERABLE one less than required by the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT STANDBYwithin the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and/or open the protective system trip breakers.

ST. LUCIE-UNIT2 3/4 3-3 Amendment No.

98