L-98-031, Application for Amend to License NPF-16,revising Applicability of TS 3.4.7 Re RCS Chemistry,Consistent W/ Corresponding Specification for Unit 1

From kanterella
(Redirected from ML17229A648)
Jump to navigation Jump to search
Application for Amend to License NPF-16,revising Applicability of TS 3.4.7 Re RCS Chemistry,Consistent W/ Corresponding Specification for Unit 1
ML17229A648
Person / Time
Site: Saint Lucie 
Issue date: 03/03/1998
From: Stall J
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML17229A649 List:
References
L-98-031, L-98-31, NUDOCS 9803090325
Download: ML17229A648 (16)


Text

CATEGORY 1 REGULA' INFORMATION DISTRIBUTIO SYSTEM (RIDS)

ACCESSION NBR:9803090325 DOC.DATE: 98/03/03 NOTARIZED: YES FACXL:50-389 St. Lucie Plant, Unit 2, Florida Power

&. Light Co.

AUTH.NAME.

AUTHOR AFFILIATION STALL,Z.A.

Florida Power

& Light Co.

RECIP.NAME RECIPIENT AFFXLIATION Document Control Branch (Document Control Desk)

SUBJECT:

Application for amend. to license NPF-16,revising applicability of TS 3.4.7 re RCS chemistry, consistent w/"

corresponding specification for Unit 1.

DISTRIBUTION CODE: A001D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: OR Submittal:

General Distribution DOCKET ¹ 05000389 NOTES:

RECIPIENT ID CODE/NAME PD2-3 LA GLEAVES,W COPIES LTTR ENCL 1

1 1

1 RECIPIENT ID CODE/NAME PD2-3 PD COPIES LTTR ENCL 1

1 0

INTERNAL: ACRS NRR/DE/ECGB/A NRR/DRCH/HICB NRR/DSSA/SRZB OGC/HDS3-1 1

1 1

1 1

1 1

1 0

FILE CENTER B

NRR/DSSA/SPLB NUDOCS-ABSTRACT 1

1 1

1 1

1 1

1 Y,

EXTERNAL: NOAC NRC PDR 1

1 D

E NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD)

ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED:

LTTR

'14 ENCL 13

Florida Power &Light Company, 6351 S. Ocean Drive, Jensen Beach, FL30S57 March 3, 1998 L 031 10 CFR 50.90

  • I U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Re:

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls Pursuant to 10 CFR 50.90, Florida Power 8 Light Company (FPL) requests to amend Facility Operating License NPF-16 for St. Lucie Unit 2 by incorporating the attached Technical Specifications (TS) revisions.

The amendment will revise applicability of TS 3.4.7, Reactor Coolant System Chemistry, consistent with the corresponding specification for St. Lucie Unit 1, and thereby eliminate unnecessary personnel radiation exposure associated with sampling during a defueled plant condition.

In addition, administrative changes to TS 5.6.1.a.1, Design Features-Fuel Storage, Criticality, and Administrative Control 6.5.2.9.d, Technical Review Responsibilities are included.

It is requested that the proposed amendment, ifapproved, be issued by October 1, 1998, prior to the next scheduled refueling outage.

Attachment 1

is an evaluation of the proposed TS changes. is the "Determination of No Significant Hazards Consideration." contains a copy of the affected TS pages marked-up to show the proposed changes.

I 1

The proposed amendment has been reviewed by the St. Lucie Facility Review Group and the Florida Power 8 Light Company Nuclear Review Board.

In accordance with 10 CFR 50.9'I (b)(1), a copy of the proposed amendment is being forwarded to the State Designee j

for the State of Florida.

Please contact us ifthere are any questions about this submittal.

Very truly yours, 4

J. A. Stall

~ "'t 48,~

Vice President St. Lucie Plant 9803090325 980303 PDR ADQCK 05000389(

P PDR an FPL Group company llllllllllllllllllllllllllllllllJIIIIIII

~

I t'

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L-98-031 Page 2 JAS/RLD Attachments cc:

Regional Administrator, Region II, USNRC.

Senior Resident Inspector, USNRC, St. Lucie Plant.

Mr. W.A. Passetti, Florida Department of Health and Rehabilitative Services.

St. Lucie Unit 2 Docket'o. 50-389 Proposed License Amendment RCS Chemist

/Desi n features/Administrative Controls L-98-031 Page 3 STATE OF FLORIDA

)

)

ss.

COUNTY OF ST. LUCIE

)

J. A. Stall being first duly sworn, deposes and says:

That he is Vice President, St. Lucie Plant, for the Nuclear Division of Florida Power & Light Company, the Licensee herein; That he has executed the foregoing document; that the statements made in this document are true and correct to the best of his knowledge, information and belief, and that he is authorized to execute the document on behalf of said Licensee.

J.A. Stall STATE OF FLORIDA COUNTYOF Sworn to and subscribed before me this 8~6 day of lYA~,19 by J. A. Stall, who is personally known to me.

Signature of Notary Public-State of Florida Losiio J. Whltweil

,=a..v, MYCOMMISSIOIIICC646183 EXPIRES May 12, 2001

"~jv"~C'0NDEO1lSU TROYMt1 NSURANCE, IlC.

Name of Notary Public (Print, Type, or Stamp)

1

%$1 I

I>>

b f'6 '. lf E

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls ATTACHMENT1 EVALUATIONOF PROPOSED TS CHANGES

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L 031 Page1 of 4 EVALUATIONOF PROPOSED TS CHANGES Introduction The proposed amendment to Facility Operating License NPF-16 for St. Lucie Unit 2 (PSL2) willrevise the required plant conditions specified for applicability of Technical Specification (TS) 3.4.7, Reactor Coolant System (RCS) Chemistry, consistent with the corresponding TS for St. Lucie Unit 1.

This change will obviate the burden and personnel radiation exposure associated with sampling the RCS for chloride and fluoride concentrations during low temperature, defueled conditions at PSL2, and which are the result of the existing requirement to comply with the subject TS "At all times." FPL has determined that routine sampling for these halides during plant conditions other than the operational MODES defined in the TS is not necessary.

In addition, administrative changes are proposed for: (a) TS 5.6.1.a.1, Design Features-Fuel Storage, Criticality, to more accurately reflect the total uncertainties previously approved for criticality analyses performed for the spent fuel storage pool, and (b) TS 6.5.2.9.d, Technical Review Responsibilities, to more accurately describe the recipients of detailed recommendations resulting from technical reviews performed under cognizance of the Company Nuclear Review Board (CNRB).

Pro osed Chan es:

Descri tion and Bases/Justification (1)

TS 3.4.7: The reactor coolant system (RCS) chemistry Limiting Condition for Operation (LCO) is revised as follows:

(a) APPLICABILITY:Change "At all times" to read, "AllMODES" (b) ACTION: Change "AtAll Other Times" to read, "MODES 5 and 6" Basis/Justification for Pro osed Chan e

TS 3.4.7 provides RCS Chemistry limits to ensure that corrosion of the RCS is minimized over the life of the plant and thereby ensure structural integrity and a reduction in the potential for RCS leakage.

Specifically,-steady state and transient limits are established for oxygen, chloride, and fluoride concentrations in the reactor coolant to minimize corrosion of the zircaloy fuel cladding, austenitic stainless steel pipingand piping and components that are clad with stainless steel.

The corrosive effects are time and

~ X St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L 031 Attachment 1

Page 2 of 4 temperature dependent, and include pitting and stress corrosion cracking (SCC).

The existing Specification is applicable "At all-times" and requires sampling the RCS for dissolved oxygen, chloride, and fluoride concentrations at least 3 times per 7 days, except that the limits and sampling requirements for dissolved oxygen are waived when temperature is ~ 250 'F. The surveillance requirements are established to assure that concentrations in excess of the limits willbe detected in sufficient time to take corrective actions.

Chloride and fluoride are more aggressive corrosion agents than oxygen and excessive concentrations of these halides can cause damage to reactor components even at temperatures below 250 'F. Therefore, monitoring requirements as well as actions for concentrations above the specified limits are appropriate for plant operation in MODES 5 and 6.

However, compliance with the literal meaning of the existing TS applicability statement requires continuation of RCS chemistry surveillance activities during certain refueling operations even when there is no fuel in the reactor vessel following full core off-load.

Typically, coolant temperature in this defueled condition is less than 100 'F, the RCS is depressurized, systems that are necessary for circulation of reactor coolant to obtain a representative chemistry sample are not required to be OPERABLE, and ifthe RCS inventory has been drained to below the elevation of the reactor vessel flange and the Shutdown Cooling System is removed from service, sampling the coolant in the vessel is only possible by entering the reactor vessel area and manually dipping a sample container into the available inventory from the upper refueling cavity. This latter sampling method results in personnel radiation exposure that, otherwise, would not be incurred.

FPL has reviewed parameters associated with pitting and SCC of stainless steel and, for the limited periods of time and low temperatures associated with a full core off-load condition, has concluded the following: (1) at temperatures near ambient, pitting is unlikely to result from exposure to an aqueous solution containing a halide concentration of several orders of magnitude above the TS limits; and (2) SCC of 304/316 and associated L grades of stainless steel is not expected at temperatures near ambient with halide concentrations below1 ppm, and an increase in concentration of several orders of magnitude above the limits at these temperatures would not significantly impact SCC susceptibility.

Moreover, due to the large volume of contaminated coolant addition that would be required, it is unlikely that the chloride or fluoride concentrations could be significantly increased beyond the concentrations that existed during MODE 6 prior to the full core off-load. Based on the preceding discussion, FPL believes that routine sampling for chloride and fluoride concentrations is not necessary at St. Lucie Unit 2 during a defueled, low temperature plant condition.

The proposed LCO will remove the burden of monitoring RCS chloride and fluoride concentrations during a condition other than the operational MODES defined in the

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L 031 Attachment 1

Page 3 of 4 Technical Specifications.

In addition, the proposed changes willmake the specification consistent with the corresponding TS for St. Lucie Unit 1.

(2)

TS 5.6.1.a.1:

This Specification describes the overall uncertainties included in the criticality analysis (for unborated water) supporting the approved design of the spent fuel pool storage racks, and is revised as follows:

Change the phrase, "... which includes a conservative allowance of.024 bk, for Total Uncertainty" to read, "... which includes a conservative allowance of.024 Ilk <<(Region I) and.01 7 bk,<<(Region II)for Total Uncertainty" Basis/Justificationfor Pro osed Chan e

TS 5.6.1.a provides certain requirements for Regions I and II of the spent fuel storage pool based on the design parameters that have been reviewed and approved for the spent fuel storage racks.

Item 1 of the specification addresses the acceptance criteria and the total uncertainty associated with the calculated effective neutron multiplication factor (k,) for a hypothetical case considering the spent fuel storage racks flooded with unborated water.

The existing Specification was issued with Facility Operating License Amendment No.7 (October 16, 1984) which authorized an increase in the storage capacity of the spent fuel pool to 1076 fuel assemblies.

In the criticality analysis performed for the case considering the fuel racks flooded with unborated water, an overall uncertainty of.024 and.017 was obtained for Regions I and II, respectively.

These values, including their constituents and method of derivation, are documented in Attachment 1 to FPL letter L-84-219, FPL response to NRC Item No.5 (J.W.

Williams (FPL) to J.R. Miller(NRC), Docket 50-389: Request for Additional Information, Spent Fuel Rack Submittal: August 29,1984).

The same uncertainty values are also documented in section 2.1.1, Analysis Methods, of the safety evaluation by the Office of Nuclear Reactor Regulation supporting Amendment No. 7 to Facility Operating License No. NPF-16, Docket 50-389.

The proposed revision to TS 5.6.1.a.1 is administrative in nature, and willensure that the literal description of the total uncertainty associated with the criticality analysis (unborated) for the St. Lucie Unit 2 spent fuel storage racks is consistent with the previously approved values.

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L 031 Page 4 of 4 (3)

TS 6.5.2.9.d: The specification states that the technical review responsibilities under the cognizance of the CNRB shall encompass, "Making detailed recommendations through the Chairman-CNRB for revising

... " Revise this statement to read:

"Making detailed recommendations to the Chairman-CNRB and plant management for revising... "

Basis/Justification for Pro osed Chan e

TS 6.5.2.9 was established as part of Facility Operating License Amendment No. 69 (December 22, 1994) which authorized transfer of activities previously performed by an Independent Safety Engineering Group (ISEG) to the Quality Assurance Department.

Recommendations resulting from the technical review activities performed pursuant to this specification are reported to the Chairman-CNRB and St. Lucie plant management to ensure that such recommendations are properly dispositioned.

The proposed revision is editorial/administrative in nature, and ensures that the literal description of making detailed recommendations is consistent with the previously approved quality assurance process.

Conclusion The proposed revision to TS 3.4.7 will eliminate the burden and personnel radiation exposure associated with monitoring RCS chloride and fluoride concentrations when the reactor is in a low temperature, defueled condition; and will remain consistent with the basis for this specification as well as the corresponding TS at St. Lucie Unit 1.

The revisions proposed for TS 5.6.1.a.1 and TS 6.5.2.9.d are administrative changes that ensure the literal descriptions contained therein are consistent with the bases for previously approved license amendments.

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls ATTACHMENT2 DETERMINATIONOF NO SIGNIFICANTHAZARDS CONSIDERATION

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L-98-031 Page1 of 2 DETERMINATIONOF NO SIGNIFICANTHAZARDS CONSIDERATION Description of'mendment request:

The proposed amendment will revise the conditions specified for applicability of the reactor coolant system (RCS) chemistry requirements, Technical Specification (TS) 3.4.7, to eliminate the burden and personnel radiation exposures associated with monitoring RCS chloride and fluoride concentrations during low temperature, defueled plant conditions; and will implement administrative changes to TS 5.6.1.a.1, Design Features-Fuel Storage, Criticality, and Administrative Control 6.5.2.9.d, Technical Review Responsibilities, to ensure that literal descriptions contained therein are consistent with the bases for previously approved license amendments.

Pursuant to 10CFR50.92, a determination may be made that a proposed license amendment involves no significant hazards consideration if operation of the facility in accordance with the proposed amendment would not: (1) involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a new or different kind of accident from any accident previously evaluated; or (3) involve a significant reduction in a margin of safety.

Each standard is discussed as follows:

(1) Operation of the facilityin accordance with the proposed amendment would not involve a significant increase in the probability or consequences of an accident previously evaluated.

The proposed change to TS 3.4.7 willreplace the existing applicability statement of "At all times" with "AllMODES." This revision will obviate the burden and personnel radiation exposures associated with sampling the RCS for chloride and fluoride concentrations during low temperature, defueled conditions.

The existing limits, colrective actions for above limit conditions, and sampling requirements will be applicable for all operational MODES defined in the TS. The proposed applicability, willcontinue to assure consistency with the bases for the RCS chemistry specification, and the potential for occurrence, initial conditions, or consequences of events considered in the safety analyses are not changed.

The revisions proposed for TS 5.6.1.a.1 and 6.5.2.9.d are administrative in nature, and assure consistency with the bases for previously approved license amendments.

Therefore, operation of the facility in accordance with the proposed amendment will not involve a significant increase in the probability or consequences of an accident previously evaluated.

St. Lucie Unit 2 Docket No. 50-389 Proposed License Amendment RCS Chemist

/Desi n Features/Administrative Controls L-98-031 Page 2 of 2 (2) Operation of the facilityin accordance with the proposed amendment would not create the possibility of a new or different kind of accident from any accident previously evaluated.

E The proposed amendment will not change the physical plant or the operational MODES defined in the facilitylicense.

The changes do not involve the addition of new equipment or the modification of existing equipment, nor do they alter the design of St. Lucie plant systems.

Therefore, operation of the facility in accordance with the proposed amendment would not create the possibility of a new or different kind of accident from any accident previously evaluated.

(3) Operation ofthe facilityin accordance with the proposed amendment would not involve a significant reduction in a margin of safety.

The proposed revision to TS 3.4.7 will not change the existing RCS chemistry requirements that are applicable to the operational MODES defined in the technical specifications.

However, the change will allow the chloride and fluoride concentrations to go unmonitored during certain refueling operations when there is no fuel in the reactor vessel.

For the limited time intervals associated with this defueled condition, the RCS is depressurized, coolant temperature is near ambient, it is unlikely that the chloride and fluoride concentrations could be significantly increased above the concentrations that existed during MODE 6 prior to the core off-load, and susceptibility to corrosive attack from these halides is, therefore, significantly reduced.

The existing bases for the RCS chemistry limiting conditions for operation are not changed, and both the bases and the proposed specification are consistent with the corresponding TS at St. Lucie Unit 1. The proposed revisions to TS 5.6.1.a.1 and TS 6.5.2.9.d are administrative in nature and ensure that descriptions contained therein are consistent with the bases for previously approved license amendments.

Therefore, operation of the facility in accordance with the proposed amendment would not involve a significant reduction in a margin of safety.

Based on the discussion presented above and on the supporting Evaluation of Proposed TS Changes, FPL has concluded that this proposed license amendment involves no significant hazards consideration.