ACCELERATED DISTRIBUTION DEMONSTPWTION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:9204200015 DOC.DATE: 92/04/13 NOTARIZED:
NO FACIL:50-335 St. Lucie Plant, Unit 1, Florida Power
& Light Co.
AUTH.NAME AUTHOR AFFILIATION GOLDBERG,J.H..
Florida Power
& Light Co.
RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT:
Responds to violations noted in Insp Rept 50-335/92-04.
Corrective actions: fire protection dept held training class on handling
& storage of flammable or combustible liquids 920128 event discussed at in-house events training class.
DISTRIBUTION CODE:
IE01D COPIES RECEIVED:LTR 5 ENCL SIZE:
TITLE: General (50 Dkt)-Insp Rept/Notice of Viooation esponse NOTES DOCKET ;.
05000335 R
D S-RECIPIENT ID CODE/NAME PD2-2 PD INTERNAL: ACRS AEOD/DEIIB DEDRO NRR/DLPQ/LHFBPT NRR/DOEA/OEAB NRR/DST/DIR 8E2 NUDOCS-ABSTRACT OGC/HDS3 RGN2 FILE 01 EXTERNAL: EG&G/BRYCE,J.H.
NSIC COPIES LTTR ENCL 1
1 2
2 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 RECIPIENT ID CODE/NAME NORRIS,J AEOD AEOD/DSP/TPAB NRR MORISS EAUi D NRR/DLPQ/LPEB10 NRR/DREP/PEPB9H NRR/PMAS/ILRB12 OE DXg~~y~
RC PDR COPIES LTTR ENCL 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
'1 1
1 D
D R
D NOTE TO ALL"RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE iVASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOih'I Pl 37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON T NEED!
OTAL NUMBER OF COP1ES REQUIRED:
LTTR 23 ENCL 23
P.O. Box 14000, Juno Beach, FL 33408-0420 APR 1
3 lggz L-92-99 10 CFR 2. 201 U.
S ~ Nuclear Regulatory Commission Attn:
Document Control Desk Washington, D.
C.
20555 Re:
St. Lucie Unit 1 Docket No. 50-3 3 5 Reply to Notice of Violation Ins ection Re ort 92-04 Florida Power and Light Company has reviewed the subject inspection report and pursuant to 1 0 CFR 2. 20 1 the response to the notice of violation is attached.
I Very truly yours, J.
H ~ Goldberg President Nuclear Division JHG/ JWH/kw Attachment cc: Stewart D. Ebneter, Regional Administrator, USNRC Region II Senior Resident Inspector, USNRC, St. Lucie Plant JHG/PSL f666-92 reer
~ C.,
92042000 1 5 crr204 1 3 P DR ADOCK 05000335 8
PDR Bn FVL Group conrprn; z/g I,
/~~5
0-
Re:
St. Lucie Unit 1 Docket No. 50-335 Reply to Notice of Violation Xns ection Re ort 92-04 VIOLATION:
Unit 1 Technical Specifications (TS) 6.8.1.f requires that written procedures shall be established, implemented, and maintained covering fire protection program implementation.
This requirement is, implemented in part by administrative procedure AP 0010434, Rev 23, Plant Fire Protection Guidelines.
AP 0010434 paragraph 8.2.3 listed the safety-related areaS where combustibles may be stored.
Storage of combustibles in the cable spreading rooms was not included.
lc hol t
RESPONSE
Contrary to the above, on January 28,
- 1992, two plastic pint spray bottles of 91 percent isopropyl a'lcohol were observed stored unattended in an open crew box in the Unit 1 cable spreading room.
These spray bottles had attached material safety data sheets numbered "1552.500, 1549" stating that the material was flammable and must be transferred to a safety can and stored in a flame-proof cabinet.
When notified, the licensee immediately removed the a
o o a non-safety-related area.
1.
The reason for the violation was personnel error.
2.
Steps taken to correct the non-compliance:
a)
The flammable material was immediately removed from the cable spreading room, transferred to a safety
- can, and stored in a flame-proof cabinet.
b)
All other crew boxes and work areas were inspected to ensure flammable materials were properly stored.
This inspection revealed several
~ additional instances of improperly stored flammabl'e material.
These materials were removed from the boxes and stored as required.
3.
Steps taken to avoid a further violation:
a)
The Plant Fire Protection Department held a training class at the electrical maintenance foreman/supervisor meeting in February 1992.
The training session focussed on the handling and storage of flammable or combustible liquids and the plant chemical control program.
b)
This event will be discussed at the next electrical maintenance in-.house-events training class.
This training is scheduled for the second quarter of 1992.
Re:
St. Lucie Unit 1 Docket No. 50-335 Reply to Notice of Violation Ins ection Re ort 92-04 c)
Area inspection work descriptions now include a check to ensure that flammable liquids are stored in safety cans and flame-proof cabinets.
d)
Plant. wide emphasis will be placed on chemical control through regularly scheduled safety meetings.
4 ~
Full compliance was achieved on January 28, 1992.