ML17180A372

From kanterella
Jump to navigation Jump to search
Emergency Response Data System Changes
ML17180A372
Person / Time
Site: Browns Ferry  
(DPR-033, DPR-052, DPR-068)
Issue date: 06/29/2017
From: Bono S
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML17180A372 (5)


Text

Tennessee Valley Authority, Post Office Box 2000, Decatur, Alabama 35609-2000 June 29, 2017 A TIN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2, and 3 10 CFR 50.4 10 CFR 50, Appendix E Renewed Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296

Subject:

Emergency Response Data System Changes The purpose of this letter is to provide changes to the Emergency Response Data System (EROS), as required by Title 10 of the Code of Federal Regulations (1 O CFR) 50, Appendix E, Section Vl.3, "Maintaining Emergency Response Data System" for Browns Ferry Nuclear Plant (BFN), Units 1, 2, and 3. This revision to the EROS changed the upper range limit on EROS data point SPDS0024. The changes to the EROS Data Point Library are summarized in the Enclosure.

This change is being provided in accordance with 10 CFR 50, Appendix E, Section Vl.3.a, which requires a notification within 30 days after the changes are made for any software or hardware changes to any transmitted data points identified in the Data Point Library. This change went into effect on June 2, 2017.

There are no new regulatory commitments in this letter. Please direct questions concerning this issue to Jamie L. Paul at (256) 729-2636.

R~~\\~

S. M. Bono Site Vice President

Enclosure:

Emergency Response Data System Data Point Library Change cc (w/Enclosure):

NRC Regional Administrator - Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant

ENCLOSURE Browns Ferry Nuclear Plant Units 1, 2, and 3 Emergency Response Data System Data Point Library Change (See Enclosed)

BFN Emergency Response Data System 1-Tl-411 Unit 1 EROS Point Number 38 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital.

Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Comp~nsation:

Level Reference Leg:

Unique System Desc.:

(EROS) Data Point Library Appendix A (Page 38 of 38)

EFF GAS RAD 12/20/2006 BF1 1

EFF GAS RAD SPDS0024 Rev.0005 Paae 43 of 43 RADIOACTIVITY OF SPDS0024 RELEASED GASES STACK RELEASE RATE-COMPOSED Radioactivity of Released Gasses A

Ci/SEC N/A 0.0 8.5E6 N/A N/A p

7 See Below Plant Stack All modes: HIHl=140 Hl=14 N/A N/A LOW y

N/A How Processed: Stack flow (cfm) X Stack Release Activity (uCi/cc) (MUL T). where Stack Activity = Monitor counts X Calibration constant X Temperature correction X Pressure correction X Dead Time correction.

BFN Emergency Response Data 2-Tl-411 Unit2 System (EROS) Data Point Library Rev.0005 Appendix A (Page 38 of 38)

Page 43 of 43 EROS Point Number:

38 EFF GAS RAD SPDS0024 Radioactivity of Released Gasses Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS Number of Sensors:

How Processed:

Sensor Locations:

Alarmffrip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc:

9/12/2005 BF2 1

EFF GAS RAD SPDS0024 STACK RELEASE RATE - COMPOSED Radioactivity of Released Gasses A

Ci/SEC N/A 0.0 8.5E6 N/A N/A p

7 See Below Plant Stack All modes: HIHl=140, Hl=14 N/A N/A LOW y

N/A How Processed:

Stack flow (cfm) X Stack Activity (uCi/cc) (MUL T) where Stack Activity = Monitor counts X Calibration constant X Temperature correction X Pressure correction X Dead Time correction

BFN Unit 3 Emergency Response Data System (EROS) Data Point Library Appendix A (Page 38 of 38) 3-Tl-411 Rev.0005 Page 43 of 43 EROS Point Number:

38 EFF GAS RAD SPDS0024 Radioactivity of Released Gasses Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS Number of Sensors:

How Processed:

Sensor Locations:

Alarmffrip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc:

9/12/2005 BF3 1

EFF GAS RAD SPDS0024 STACK RELEASE RATE-COMPOSED Radioactivity of Released Gasses A

Ci/SEC N/A 0.0 8.5E6 N/A N/A p

7 See Below Plant Stack All modes: HIHl=140 Hl=14 N/A N/A LOW y

N/A How Processed:

Stack flow (cfm) X Stack Actity (uCi/cc) (MUL T) where Stack Activity =

X Pressure correction X Dead Time correction Monitor counts X Calibration constant X Temperature correction