In the Matter of UNITED STATES OF AflERICA NUCLEAR REGULATORY COflfiISSION BEFORE THE ATO".IIC SAFETY AND LICENSING BOARD

'g

)

Mp~

c~'*awe C iiU

$ tg~j

,ci) ct

a~Cgbl M'rt PENNSYLVANIA POl(ER AND LIGHT CO.

AND ALLEGHENY ELECTRIC COOPERATIVE, INC.

)

)

(Susquehanna Steam Electric Station, Units 1 and 2)

Docket Nos.

ggj-387 50-388 NRC STAFF

RESPONSE

SUPPORTING IN PART AND OPPOSING IN PART APPLICANTS'OTION FOR PARTIAL SUfiMARY DISPOSITION OF CONTENTION 17 I.

INTRODUCTION t

On December 8, 1980, "Applicants'otion for Partial Summary Disposi-tion of Contention 17" (Motion) was served on the NRC Staff.

In that Motion, Applicants move the Board for summary disposition in its favor on the remain-ing portion of Contention 17 which alleges that Applicants'ultrahigh voltage (UHV)" transmission lines will "produce noise pollution, cause electrical shock from flashover, create television and radio interference, create electrostatic and electromagnetic fields that adversely affect living organisms along the UHV transmission right-of-way and beyond."

Contention 17 further asserts that "the Applicants should be barred from transmitting electricity from the facility, if and when it becomes operational, over UHV lines and should be required to use lines in the range of 138,000 - 230,000 volts maximum.

Alternatively, the Applicants should be required to place

the UHV lines underground, using compressed gas as an insulator."

Appli-cants assert that this portion of Contention 17 presents no genuine issue of material fact and that thus Applicants are entitled to a decision in their favor on this portion as a

ma.ter of law.

The tlRC Staff supports in part and opposes in part Applicants'otion.

The Staff concludes that ApplicantsNotion and its supporting documentation clearly demonstrate the absence of any genuine issue of material fact with reg>>. " to noise pollution, electrical shock from flashovers, television and radio interference, and the human health effects of magnetic fields.

Thus, the Staff believes the Board should dismiss that part of Contention 17 which deals with these issues as a matter of law.

The Staff believes, however, that Applicants'otion and its supporting documentation do not clearly demonstrate the absence of any genuine issue of material fact regard-ing the human health effects of electric fields.

Thus, as the Staff concludes that Applicants have not met their burden of proof with regard to that portion of Contention l7 which raises this issue, the Staff does not support dismissal of this portion of Contention 17 as a matter of law.

Section II of this pleading will discuss generally the law applicable to motions for summary disposition.

Section III will set forth the Staff's reasons for concluding that that part of Contention 17 which deals with noise pollution, electrical shock from flashover, television and radio interference, and the human health effects of magnetic fields raises no II Paragrap s

t rough 27 of "Applicants'tatement of Naterial Facts as~

to Which There is no Genuine Issue to be Heard" set forth facts extran-eous to the issue of "electrical shock from flashover" in Contention 17.

~

~

tf 'l E

~

~

~

~,

s

~

~ )

3 genuine issue of material fact.

Section IV will set forth the basis for the Staff's conclusion that Applicants'otion and its supporting documentation do not demonstrate the absence of any genuine issue of material fact regard-ino the human health effects of electric fields.

lf i V

~ F

~ P II.

GENERAL POINTS OF LAB The Commission's Rules of Practice provide for summary disposition of certain issues on the pleadings where the filings in the proceeding show that there is no genuine issue as to any material fact and that movant is entitled to a decision as a matter of law.

10 CFR 5 2.749.

As the Commission's summary disposition rule is analogous to Rule 56 of the Federal Rules of Civil Procedure (summary judgment),

Federal court decisions interpreting Rule 56 may be relied on for an understanding of the operation of the summary dis-position rule; Thus, in Adickes v. Kress 8 Co.,

389 U.S.

144, 157 (1970),

the Supreme Court held that the party seeking summary judgment has "the burden of showing the absence of a genuine issue as to any material fact."

3/

To meet this burden, the movant must eliminate any real doubt as to the existence of any genuine issue of material fact.

To further thss goal, 4/

the summary disposition rule provides that all material facts, set out in the statement mandatorily accompanying summary disposition motions, will be 2/

Alabama Power Company (Joseph M. Farley, Units 1 and 2), ALAB-182, 7 AEC

210, 217 (1974).

3/

See also Cleveland Electric Illuminating Co. (Perry, Units 1 and 2), ALAB-

433, 6

NRC 741, 752 - 54 (1977).

4/

Poller,v.

Columbia Broadcasting Co., 368 U.S.

464, 468 (1962); Sartor v.

Arkansas Natural Gas Corp.,

321 U.S. 620, 627 (1944)..

deened to be admitted unless controverted by the opposing party.

10 CFR

> 2.749(a).

Any other party may serve an answer supporting or opposing the motion for summary disposition.

10

CFP, 5 2.749(a).

Attached to a motion opposing summary disposition must be a separate,

short, and concise statement of the material facts as to which it is contended that there exists a genuine issue to be heard.

10 CFR 5 2.749(a).

The opposing party need not show that it waul d pi e'va 'll vn the issues but only that there af'e g&liviiie i ssues to be tried.

Furthermore, the record and affidavits supporting and opposing the 5/

motion must be viewed in the light most favorable to the party opposing the motion. Finally, the proponent of a motion for summary disposition must 6/

meet its burden of establishing that it is entitled to judgment as a

matter of law even if the opponent of such a motion fails to submit evidence controverting the conclusions reached in documents submitted in support of the motion.

III.

STAFF ARGUMENT IN SUPPORT OF PART OF APPLICANTS'OTION The lines proposed for use by Applicants are designed for alternating current (AC) transmission and are further classified by their maximum design

voltage, 550 kV, as "extra high voltage" (EHY) lines.

The alternating Q5 American tQnufacturers faut. Ins.

Co. v. American Broadcasting - Para-mount Theaters, Inc., 388 F.2d 272, 280 (2d Cir. 1976).

6/

See Public Service Co. of New Hampshire (Seabrook Station, Units 1 and

~2, LBP-74-36, 7 AEC 877 (1974).

Q7 Cleveland Electric Illuminating Co., (Perry, Units 1 and 2), ALAB-443, 6

NRC 741, 753 - 54 (1977).

current transsission lines associated with the Susquehanna plant dissipa.=.

energy fro;.~ the surfaces of the conductors via a

m "hanism known as corona

loss, This loss occurs by ionization of air in the inmedia+e vicinity o the conduc-~:

sur ace when it ls energized, when a

I=rge po=ential diffe,'-

ence exists between the conductor and the air.

The design of modern EH" transmission lines is such that this loss is negligible under fair weather conditions.

However, when the conductor surface becomes
wet, as during fog, ra'i(iq ice, or snow

> the I it.6 ui col ona d i scil ge i

'Ilcrea ~

I

~

'E'

~ 10 discharges result in audible noise.

(Affidavit of John C.

Lehr at 2}.

Additionally, corona discharges result in the production of ozone and radio and television interference.

(Affidavit of Gerald Gears at 4).

A.

Noise Pollution The alternating current (AC) transmission lines associated with the Susquehanna Steam Electric Station will produce audible noise as a result of corona discharge only during wet weather conditions.

(Lehr at 2).

This noise will be a buzzing, hissing, and/or crackling sound calculated by Applicants to be 52.5 dBA over all transmission line segments.

(Lehr at 3-4).

Applicants'redicted average value is within the range predicted by studies conducted on this matter.

(Lehr at 3-4).

Of these, one study, based on actual experience with transmission line operation, found a low proba-bility of complaints being registered for an audible noise level of 52.5 dBA or less, measured 100 feet from the centerline of the transmission line.

(Lehr at 5).

Further, an annual average day-night equivalent sound level (LD ) of 52.9 dBA may be computed for the Susquehanna lines using inclement

weather data and the maximum noise level predicted by Applicants for the edge of the right-of-way (57.1 dBA). (Lehr at 5).

This level is below the L>value of 55 dBA published by EPA for "residential areas with outside space and farm residences."

(Lehr at 5).

EPA established this value pursuant to the Noise Control Act which requires EPA to publish information on levels of environmental

noise, the attainment and maintenance of which are requisite to protect the public health and welfare with an adequate margin of safety.

42 U.S.C.

5 4904(a)(2).

Finally, even these acce;,able le',els of noise

~"i11 be reduced by transmission loss due to passage of sound through the walls and windows of a home/building and through space.

Tests on 500 kY lines have shown an attenuation of 3 to 4 dBA for each doubling of distance from the 50 foot mark on either side of the centerline of the transmission line.

(Lehr at 6-7).

Based on the above, the Staff concludes that the audible noise which will be produced by the Susquehanna transmission lines under wet weather conditions will not cause significant indoor activity interference or annoyance.

B.

Electrical Shock from Flashover Flashovers are electrical discharges occurring around the edge or over the surface of a transmission system's insulators.

As these disruptive electrical discharges may cause permanent damage to the insulator, trans-missions systems are designed to reduce the probability that a flashover might occur.

For example, lines undergoing flashovers are de-energized instantaneously by circuit breakers.

The presence of circuit breakers makes it highly improbable that a person would experience a serious shock or other

'f

~

~

I

~

adverse health effect from a flashover; thus, the Staff concludes that the possibility of electrical shock fro~ flashover does not pose a significant threat to persons in the vicinity of the transmission lines.

(Gears at 5).

C.

Television and Radio Interference In addition to the production of audible noise and ozone, corona dis-charges cause radio and television interference which can disrupt Nl radio and television recep ion.

llhile degradation o

"" ra"o an" television reception may occur, the Staff concludes that the overall impact on radio and television reception resulting from operation of the Susquehanna 500 kV transmission lines will be negligible because Susquehanna's 500 kV lines traverse primarily rural areas with sparse populations.

(Gears at 4).

D.

Human Health Effects of Na netic Fields Current flow in a conductor gives rise to a surrounding magnetic force field.+

Hagnetic field strength is described in terms of flux density, usually expressed in units of gauss (6).

Transmission line magnetic fields are low.

Extra high voltage (EHV) systems similar to the Susquehanna 500 kV lines produce a magnetic field at ground level of 0.3 G or less.

Recommended 8/

Transmission lines produce both electric and magnetic fields.

The Staff's use of the term, "electric field," corresponds to the use of the term "electrostatic field" in Contention 17.

Similarly, the Staff's use of the term, "magnetic field," corresponds to the use of the term, "electro-magnetic field," in Contention 17.

exposure standards are two to three orders of magnitude (100 to 1000 times) greater.

Based upon the extremely low maonetic fields generated by operating EHV systems in comparison with recommended exposure stnadards, the Staff concludes that the magnetic fields produced by the Susquehanna 500 kY lines will not cause adverse biological effects.

(Gears at 5-6).

IV.

STAFF ARGUMENT IN OPPOSITION TO PART OF APPLICANTS'OTION Electric fields from EHY transmission lines cause currents to flow and voltages to be developed within persons, animals and plants.

The possible biological effects of these induced currents and voltages are very controversial.

The experimental procedures necessary to adequ'ately establish the influence of such fields on life forms are highly complex.

Various experiments have provided evidence that some biological subjects may sense, or respond to low electric field levels, similar to transmission line frequency.

These pre-liminary indications of response in test, animals are indicative of interaction of the fields with central nervous system functions or manifestations of chronic stimulation.

There is strong disagreement among researchers in this area as to the significane of these responses.

(Gears at 3).

Thus, the Staff cannot conclude that, with respect to this aspect of Contention 17, there is no genuine issue of material fact.

V.

CONC LUS ION Based on the foregoing, the NRC Staff believes it is clearly demon-strated that there is no genuine issue as to any material fact regarding that portion of Contention 17 which relates to noise pollution; electrical shock from flashovers, television and radio interference, and the human

health effects of magnetic fields.

Thus, the Staff believes that summary disposition in favor of the Applicants should be granted as a matter of law in accordance with 10 CFR 5 2.749 on this portion of Contention 17.

The Staff does not, however, believe that Applicants'otion and its supporting documentation clearly demonstrate the absence of any genuine issue of material fact regarding the human health effects of electric fields.

Accordingly, the Staff does not believe that summary disposition in favor of the Appli-cants should be granted on that portion of Contention 17 dealing with this issue.

Respectfully submitted,

$ Lent essica H. Laverty Counsel for NRC Staff Oated at Bethesda, Naryland this 9th day of January, 1981.

EP4lA.

wl "GATI,

L)

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION BEFORE THE ATOMIC SAFETY AND LICENSING BOARD In the Matter of

)

)

PENNSYLVANIA PO't!ER AND LIGHT CO.

)

AND

)

ALLEGHANY ELECTRIC COOPERATIVE, INC.

)

)

(Susquehanna Steam Electric Station,

)

Uni ts 1

and 2)

Docket Nos.

50-387 50-388 SUPPLEMENT TO APPLICANTS'TATEMENT OF MATERIAL FACTS 1.

Based on industry experience, noise levels are potentially of concern beyond the edge of the right-of-way only when voltage is 500 kV or above.

2.

The noise levels predicted to be produced by the Susquehanna transmission lines at the'dge of the right-of-way have 'a maximum calculated average annual day night sound level that is below the EPA identified level associated with adverse effects on public health and welfare.

Outdoor speech and activity interference and annoyance are,not expected to be significant in areas adjacent to the rights-of-way.

3.

Transmission line audible noise will attenuate beyond the edge of the right-of-way, reducing levels at residential structures on lands adjacent to the right-of-way.

Field measurements have shown this attenuation to be 3-4 dBA per doubling of distance beyond 50 ft from the outside phase of the transmission line.

4.

Interior noise levels in residences along the riohts-of-way due to'ransmission line operation in wet wea.her will be reduced below the exterior levels due to transmission loss throu h walls and window.'.

Using conservative loss factors, the likely interio.

noise levels due to the transmission lines are predicted to be below the EPP. indentified level associated vith adverse effects on pub>ic health and

>'~lfa~'ndoor activity interference or disruption of sleep would not be expected in residences located in areas adjacent to the rights-of-way due to transmission line audible noise.

~

~

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION BEFORE THE ATOMIC SAFETY AND LICENSING BOARD In the Matter of PENNSYLVANIA POWER AND LIGHT CO.

A!'D ALLEGHANY ELECTRIC COOPERATIVE INC.

(Susquehanna Steam Electric Station, Units 1 and 2)

Docket Nos. 50-3'7 50-388 STATEMENT OF MATERIAL FACT AS TO WHICH IT IS CONTENDED THAT THERE EXISTS A GENUINE ISSUE TO BE HEARD 1.

While the experimental procedures necessary to adequately establish the influence of such fields on life forms are highly complex, various experiments have provided preliminary evidence that some biological subjects may sense, or respond to electric fields.

In some cases, response was obtained at quite low field levels similar to those found in the vicinity of transmission lines.

These preliminary indications of response in test animals are indicative of interaction of the fields with central nervous system functions or manifestations of chronic stimulation.