UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 TERMINAL BLOCK QUALIFICATION IE Bulletin No. 78-02 Date:
January 30, 1978 Page 1 of 3 Description of Circumstances:
On January 18, 1978, Connecticut Yankee Atomic Company performed a
screening test intended to verify previous analyses of the environmental qualifications of unprotected terminal blocks used inside containment.
The test was performed at the Franklin Institute Research Laboratories, Philadelphia, Pennsylvania.
The test specimen was a Marathon M-6012 terminal block.
It was exposed to a steam environment which was designed to envelope the calculated LOCA environmental conditions in the Haddam Neck containment.
The pressure selected for the test was 40 psig for a period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
C The temperature profile consisted of a rise from an initial temperature of 100 degrees Fahrenheit to 275 degrees Fahrenheit within ten seconds, followed by a steady state operation at 275 degrees Fahrenheit for four hours.
This was followed by a drop of temperature to 140 degrees Fahrenheit within one hour, followed by a repetition of the initial temperature rise to 275 degrees Fahrenheit (within ten seconds).
The temperature then remained constant at 275 degrees Fahrenheit for the remaining 19 hours2.199074e-4 days <br />0.00528 hours <br />3.141534e-5 weeks <br />7.2295e-6 months <br /> of the test period.
During the initial screening test, 525 volts, single phase, 60 Hertz, AC voltage was applied to two pairs of terminals on. the test specimen.
Inability of the terminals to hold the voltage was defined before the test as an appropriate failure criterion.
The test was initiated on January 19, 1978.
The terminal block functioned as intended during the first 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> of the test at which time one of the pairs of terminals failed the test.
The cause of failure is still under investigation.
The failure occurred during an operator error resulting in a pressure and temperature excur-sion which is outside the envelope of the intended test.
Because of this, the licensee reran the test.
A
IE Bu letin No 78-O2 Date:
January 30, 1978 Page 2 of 3 The second screening test was initiated on January 25, 1978.
This test included three test specimens:
(1) an unprotected Marathon terminal block identical to the one used in the first test; (2) an unprotected Westinghouse terminal block; and (3) a GE terminal block enclosed in a NEMA type 12 box identical to the ones in use in the Haddam Neck plant.
The test specimens were exposed to an environment having temperature and pressure profiles essentially the same as those of the first test, minus the inadvertant overpressure transient.
All the test specimens success-fully operated through the two temperature rise profiles in the test sequence.
However, after 21 hours2.430556e-4 days <br />0.00583 hours <br />3.472222e-5 weeks <br />7.9905e-6 months <br /> in the test environment, the lower pair of terminals of the unprotected Marathon terminal block failed.
The failed terminal points were'isconnected and the test was completed.
No further failures occurred.
The failure mechanism of the terminal blocks during the first and second tests appears to be similar, i.e.,
the terminal pair that failed in each of the tests'as the lower pair on the terminal block.
Detailed analyses are in progress to identify the exact cause of failure.
Actions to be Taken by Licensees and Permit Holders:
FOR ALL POWER REACTOR FACILITIES WITH AN OPERATING LICENSE OR A CON-STRUCTION PERMIT:
1.
Determine whether or not unprotected terminal blocks are used in your facility in systems which must function in the post-accident environment; 2.
If such terminal blocks are used, identify the systems involved and provide the documentation which demonstrates that these terminal blocks have been environmentally qualified; and 3.
If documentation is not available, provide your plans and schedule for achieving full qualification of affected circuits.
4.
For holders of operating licenses, your response to this Bulletin is required to be in this office within 14 calendar days of the date of issue of this Bulletin.
5.
For holders of construction permits, your response to this Bulletin is required to be mailed within 30 calendar days of the date of issue of this Bulletin.
7
IE Bulletin No. 78-02 Date:
January 30, 1978 Page 3 of 3 Copies of your response are to be provided in the same time frame directly to the Director, Office of Nuclear Reactor Regulation, and to the Director of Reactor Operations Inspection, U.S. Nuclear Regulatory Commission, Washington, D.C.
20555.
Approved by GAO, B180225 (R0072); clearance expires 7-31-80.
Approval was given under a 'blanket clearance specifically for identified generic problems.