NL-16-2206, Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process

From kanterella
(Redirected from ML16320A214)
Jump to navigation Jump to search
Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process
ML16320A214
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 11/15/2016
From: Pierce C
Southern Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NL-16-2206
Download: ML16320A214 (13)


Text

I Charles R. Pierce Regulatory Affairs D1rector

.NOV 1 5 2016 Docket Nos.: 50-424 50-425 Southern Nuclear Operating Company, Inc.

40 lnvemess Center Parkway Post Office Box 1295 Birmingham, AL 35201 Tel 205.992.7872 Fax 205.992.7601 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001

.t& Southern Nuclear NL-16-2206 Vogtle Electric Generating Plant-Units 1 and 2 Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process Ladies and Gentlemen:

In accordance with the provisions of 10 CFR 50.90 Southern Nuclear Operating Company (SNC) is submitting a request for an amendment to the Technical Specifications (TS) for Vogtle Electric Generating Plant (VEGP), Units 1 and 2.

The proposed amendment would modify TS by relocating references to specific American Society for Testing and Materials (ASTM) standards for fuel oil testing to licensee-controlled documents and adding alternate criteria to the "clear and bright" acceptance test for new fuel oil. provides a description of the proposed changes, the requested confirmation of applicability, and plant-specific verifications. Enclosure 2 provides the current TS pages marked up to show the proposed changes. Enclosure 3 provides revised (clean) TS pages. provides current TS Bases pages marked up to show the proposed changes.

SNC requests approval of the proposed license amendments by November 30, 2017, with the proposed changes being implemented within 90 days of issuance of the amendment.

In accordance with 10 CFR 50.91 (b)(1), "State Consultation," a copy of this application and its reasoned analysis about no significant hazards considerations is being provided to the designated Georgia officials.

If you have any questions, please contact Ken McElroy at 205.992.7369.

U. S. Nuclear Regulatory Commission NL-16-2206 Page 2 Mr. C. R. Pierce states he is Regulatory Affairs Director of Southern Nuclear Operating Company, is authorized to execute this oath on behalf of Southern Nuclear Operating Company and, to the best of his knowledge and belief, the facts set forth in this letter are true.

C. R. Pierce Regulatory Affairs Director CRP/GKMIGLS Sworn to and subscribed before me this )5 ¢" dayoffVo~

afcw,v_£~t Notary Public My commission expires: /0

  • 2J
  • Zo I 1

Enclosures:

1. Basis for Proposed Change
2. VEGP Technical Specification Marked Up Pages
3. VEGP Technical Specification Clean Typed Pages
4. VEGP Technical Specification Bases Marked Up Pages (for information only) cc: Southern Nuclear Operating Company Mr. S. E. Kuczynski, Chairman, President & CEO Mr. D. G. Bast, Executive Vice President & Chief Nuclear Officer Mr. B. K. Taber, Vice President-Vogtle 1 & 2 Mr. M. D. Meier, Vice President-Regulatory Affairs Mr. B. J. Adams, Vice President-Engineering Mr. D. R. Madison, Vice President-Fleet Operations Mr. D. D. Sutton, Regulatory Affairs Manager-Vogtle 1 & 2 RType: CVC7000 U.S. Nuclear Reaulatorv Commission Ms. C. Haney, Regional Administrator Mr. R. E. Martin, NRR Senior Project Manager-Vogtle 1 & 2 Mr. E. T. Coffman, Senior Resident Inspector-Vogtle 1 & 2 State of Georgia Mr. J. H. Turner, Director-Environmental Protection Division 2016.

Vogtle Electric Generating Plant-Units 1 and 2 Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process Basis for Proposed Change to NL-16-2206 Basis for Proposed Change Table of Contents 1.0 Description 2.0 Assessment 3.0 Regulatory Analysis 4.0 Environmental Evaluation E1-1 to NL-16-2206 Basis for Proposed Change

1.0 DESCRIPTION

The proposed amendment would modify Technical Specifications (TS) by adding alternate criteria to the "clear and bright" acceptance test for new fuel oil. The Unit 1 and 2 VEGP TS already have references to specific American Society for Testing and Materials (ASTM) standards for fuel oil testing in a licensee-controlled document, hence this change is not requested.

The changes are consistent with Nuclear Regulatory Commission (NRC) approved lndustryffechnical Specification Task Force (TSTF) Standard Technical Specifications (STS}

change TSTF-37 4 Revision 0. The availability of this TS improvement was published in the Federal Register on April 21, 2006 (71 FA 20735), as part of the consolidated line item improvement process (CLIIP).

2.1 ASSESSMENT

2.2 Applicability of TSTF-374. and Published Safety Evaluation Southern Nuclear Operating Company (SNC) has reviewed the TSTF-374 (Reference 1),

and the NRC model safety evaluation (SE) (Reference 2} as part of the CLIIP. SNC has concluded that the information in TSTF-374, as well as theSE prepared by the NRC staff are applicable to Vogtle Electric Generating Plant (VEGP), Units 1 and 2, and justify this amendment for the incorporation of the changes to the VEGP Units 1 and 2 TS.

2.3 Optional Changes and Variations SNC is not proposing any variations or deviations from the requested TS changes described in the TSTF-374, Revision 0, or the applicable parts of the NRC staff's model safety evaluation published in the Federal Register on February 22, 2006 (71 FAN 9179).

(Note: VEGP TS already have references to specify ASTM standards for fuel oil testing in a licensee controlled document. This change, therefore is not required.)

VEGP TS Bases do not list ASTM version number except in References section. Since it is in the References section, it's still controlled pursuant to 1 OCFR 50.59.

3.1 REGULATORY ANALYSIS

3.2 No Significant Hazards Consideration Determination Southern Nuclear Operating Company (SNC) has reviewed the proposed no significant hazards consideration determination (NSHCD) published in the Federal Register as part of the CLIIP. SNC has concluded that the proposed NSHCD presented in the Federal Register notice is applicable to VEGP Units 1 and 2 and is hereby incorporated by reference to satisfy the requirements of 10 CFR 50.91 (a).

3.3 Verification and Commitments As discussed in the notice of availability published in the Federal Register on April 21, 2006 (71 FR 20735) for this TS improvement, plant-specific verifications were performed as follows:

SNC has proposed TS Bases consistent with TSTF-37 4, which provide guidance and details on how to implement the new requirements. In addition, SNC has a E1-2 to NL-16-2206 Basis for Proposed Change Bases Control Program consistent with Section 5.5 of the Standard Technical Specifications (STS).

4.0 ENVIRONMENTAL EVALUATION The amendment changes requirements with respect to the installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20. The NRC staff has determined that the amendment adopting TSTF-37 4, Rev 0, involves no significant increase in the amounts and no significant change in the types of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that TSTF-374, Rev 0, involves no significant hazards considerations, and there has been no public comment on the finding in Federal Register Notice 70 FRN 9179, February 22, 2006. Accordingly, the amendment meets the eligibility criteria for categorical exclusion set forth in 1 0 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendment.

5.1 REFERENCES

1. TSTF-374, Revision 0, "Revision toTS 5.5.13 and Associated TS Bases for Diesel Fuel Oil."
2. NRC Model Safety Evaluation (71 FRN 9179).

E1-3

Vogtle Electric Generating Plant-Units 1 and 2 Application for Technical Specification Change TSTF-374, Revision toTS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process VEGP Technical Specification Marked Up Pages to NL-16-2206 VEGP Technical Specification Marked Up Page Programs and Manuals 5.5 or a water and sediment content within limits.

5.5 Programs and Manuals 5.5.13 5.5.14 Diesel Fuel Oil Testing Program (continued)

1.

an API gravity or an absolute specific gravity within limits, or an API gravity or specific gravity within limits when compared to the supplier's certificate;

2.

a flash point within limits for ASTM 2D fuel oil, and, if gravity was not determined by comparison with supplier's certification, a kinematic viscosity within limits for ASTM 2D fuel oil; and

3.

a clear and bright appearance with proper color,.-----__J

b.

Other properties for ASTM 2D fuel oil are within limits within 30 days following sampling and addition to storage tanks; and

c.

Total particulate concentration of the fuel oil is s 1 0 mg/1 when tested every 31 days.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Diesel Fuel Oil Testing Program surveillance frequencies.

Technical Specifications (TSl Bases Control Program This program provides a means for processing changes to the Bases of these Technical Specifications.

a.

Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews

b.

Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:

1.

a change in the TS incorporated in the license; or

2.

a change to the updated FSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.

d.

The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the FSAR.

e.

Proposed changes that meet the criteria of (b) above shall be reviewed and approved by the NRC prior to implementation. Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).

(continued)

Vogtle Units 1 and 2 5.5-14 Amendment No. +W (Unit 1)

Amendment No. 4-aO (Unit 2)

E2-1

Vogtle Electric Generating Plant-Units 1 and 2 Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process VEGP Technical Specification Clean Typed Pages

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.13 5.5.14 Diesel Fuel Oil Testing Program (continued)

1.

an API gravity or an absolute specific gravity within limits, or an API gravity or specific gravity within limits when compared to the supplier's certificate;

2.

a flash point within limits for ASTM 2D fuel oil, and, if gravity was not determined by comparison with supplier's certification, a kinematic viscosity within limits for ASTM 2D fuel oil; and

3.

a clear and bright appearance with proper color or a water and sediment content within limits.

b.

Other properties for ASTM 2D fuel oil are within limits within 30 days following sampling and addition to storage tanks; and

c.

Total particulate concentration of the fuel oil is s 1 0 mg/1 when tested every 31 days.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Diesel Fuel Oil Testing Program surveillance frequencies.

Technical Specifications <TS) Bases Control Program This program provides a means for processing changes to the Bases of these Technical Specifications.

a.

Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews

b.

Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:

1.

a change in the TS incorporated in the license; or

2.

a change to the updated FSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.

d.

The Bases Control Program shall contain provisions to ensure that the Bases are maintained consistent with the FSAR.

e.

Proposed changes that meet the criteria of (b) above shall be reviewed and approved by the NRC prior to implementation. Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).

(continued)

Vogtle Units 1 and 2 5.5-14 Amendment No.

Amendment No.

(Unit 1)

(Unit 2)

Vogtle Electric Generating Plant-Units 1 and 2 Application for Technical Specification Change TSTF-374, Revision to TS 5.5.13 and Associated TS Bases for Diesel Fuel Oil Using the Consolidated Line Item Improvement Process VEGP Technical Specification Bases Marked Up Pages (for information only) to NL-16-2206 VEGP Technical Specification Bases Marked Up Pages (for information only)

BASES SURVEILLANCE REQUIREMENTS Vogtle Units 1 and 2 SR 3.8.3.3 (continued)

Diesel Fuel Oil, Lube Oil, and Starting Air 8 3.8.3

b. Verify in accordance with the tests specified in ASTM 0975 (Ref. 7) that the sample has an API Gravity of within 0.3 degrees at 60°F, or a specific gravity of within 0.0016 at 60/60°F, when compared to the supplier's certificate or an absolute specific gravity at 60/60°F of;::: 0.82 and~ 0.89 or an API gravity at 60°F of;::: 27 degrees and~ 42 degrees when tested in accordance with ASTM 01298 (Ref. 6), a kinematic viscosity at 40°C of ;::: 1.9 centistokes and~ 4.1 centistokes, if gravity was not determined by comparison with supplier's certification, and a flash point of ;::: 125°F; and
c. Verify that the new fuel oil has a clear and bright appearance with proper color when tested in accordance with ASTM 04176 or a water and sediment content within limits when tested in accordance with ASTM 02709 (Ref. 6).

Failure to meet any of the above limits is cause for rejecting the new fuel oil, but does not represent a failure to meet the LCO concern since the fuel oil is not added to the storage tanks.

Within 31 days following the initial new fuel oil sample, the fuel oil is analyzed to establish that the other properties specified in Table 1 of ASTM 0975 (Ref. 7) are met for new fuel oil when tested in accordance with ASTM 0975, except that the analysis for sulfur may be performed in accordance with ASTM 01552, ASTM 02622, or ASTM 04294 (Ref. 6).

The 31 day period is acceptable because the fuel oil properties of interest, even if they were not within stated limits, would not have an immediate effect on DG operation. This Surveillance ensures the availability of high quality fuel oil for the DGs.

Fuel oil degradation during long term storage shows up as an increase in particulates, due mostly to oxidation. The presence of particulates does not mean the fuel oil will not burn properly in a diesel engine. The particulates can cause fouling of filters and fuel oil injection equipment, however, which can cause engine failure.

Particulate concentrations should be determined in accordance with ASTM 05452 (Ref. 6) which provides for obtaining a field sample and subsequent laboratory testing.

8 3.8.3-11 E4-1 (continued)

REVISION ~

to NL-16-2206 VEGP Technical Specification Bases Marked Up Pages (for information only)

BASES SURVEILLANCE REQUIREMENTS REFERENCES Vogtle Units 1 and 2 Diesel Fuel Oil, Lube Oil, and Starting Air B 3.8.3 SR 3.8.3.7 (continued)

The SR is modified by a Note that excepts the performance of this SR when the associated DG is required OPERABLE by LCO 3.8.2. This exception is consistent with the SR performance exceptions in LCO 3.8.2 for SRs that might impact the OPERABILITY of the DGs.

1.

FSAR, Paragraph 9.5.4.2.

2.

Regulatory Guide 1.137.

3.

ANSI N195-1976, Appendix B.

4.

FSAR, Chapter 6.

5.

FSAR, Chapter 15.

6.

ASTM Standards: D4057-06; D1298-06; D4176-04; D1552-07; D2622-07; D4294-08a; D5452-08; D2709-96.

7.

ASTM Standards, D975-07.

8.

Southern Company Services Calculation number X4C2403V08, Standby Diesel Generator Fuel Oil Consumption and Storage Tank Capacity.

9.

Southern Company Services Calculation numbers X4C2403V11 and X4C2403V12, Emergency Diesel Generator Lube Oil Inventory Technical Specification Values.

10.

Southern Company Services Calculation number X4C2403V09, Emergency Diesel Generator Starting Air Pressure Technical Specification Value.