HCH-2016-028, Submittal of Discharge Monitoring Report for June 2016

From kanterella
(Redirected from ML16211A053)
Jump to navigation Jump to search
Submittal of Discharge Monitoring Report for June 2016
ML16211A053
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 07/21/2016
From: Davison P
Public Service Enterprise Group
To:
Office of Nuclear Reactor Regulation, State of NJ, Dept of Environmental Protection, Office of Permit Management
References
HCH-2016-028, NJ0025411
Download: ML16211A053 (14)


Text

f'.. *- .... _. PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, New Jersey 08038-0236 JUL 212016 PSEG Nuclear LLC HCH-2016-028 CERTIFIED MAIL RETURN RECEIPT REQUESTED ARTICLE NUMBER: 7013 1710 0000 6324 5264 Department of Environmental Protection Office of Permit Management Division of Water Quality PO Box 420 Trenton, N.J. 08625_;0420 NEW JERSEY POLLUTANT DISCHARGE ELIMINATION SYSTEM DISCHARGE MONITORING REPORT HOPE CREEK GENERATING STATION NJPDES PERMIT NJ0025411

Dear Sir or Madam:

Attached is the Discharge Monitoring Report for the Hope Creek Generating Station for the month of June 2016.

This report is required by and prepared specifically for the New Jersey Department of Environmental Protection (NJDEP). It presents only the observed results of measurements and analyses required to be performed by the above agencies. The choice of the measurement devices and analytical methods are controlled by the EPA and the NJDEP, not by the company, and there are limitations on the accuracy of such measurement devices and analytical techniques even when used and maintained as required. Accordingly, this report is not intended as an assertion that any instrument has measured, or that any reading or analytical result represents the true value with absolute accuracy, nor is it an endorsement of the suitability of any analytical or measurement procedure.

If you have any questions concerning .this report, please feel free to contact Travis Zigo at (856) 339-2493.

Sincerely,

?~}.O~~

Paul J. Davison Site Vice President - Hope Creek 95*2168 REV. 7/99

JUL 21 2016 HCH-2016-028 2 NJPDES DMR Attachments C Executive Director, DRBC USNRC - Docket number 50-354

JUL 21 2016 HCH-2016-028 3 NJPDES DMR EXPLANATION OF CONDITIONS June 2016 The following explanations are included to clarify possible deviation from permit conditions.

General - The columns labeled "No. Ex" on the enclosed DMR tabulate the number of daily discharge values outside the indicated limits.

Data reporting and accuracy reflect the working environment, the design capabilities and reliability of the monitoring instruments and operating equipment.

Deviations from required sampling, analysis monitoring and reporting methods and periodicities are indicated on the respective transmittal sheet with explanations below.

Results reported on the Discharge Monitoring Report forms are consistent with permit limits, data supplied from contract laboratories, the December 2007 revision of the NJDEP Monitoring Report Form Reference Manual and specific guidance from DEP personnel.

For DSN 461 A, on 6/6/16 and 6/26/16, sampling frequency was increased for Total Residual Chlorine to obtain additional operating information.

JUL 21 2016 HCH-2016-028 4 NJPDES DMR EXPLANATION OF EXCEEDANCES June 2016 The following exceedances are included in the attached report and explained below.

DSN No. EXPLANATION No Exceedances

HCH-2016-028 5 NJPDES DMR COUNTY OF SALEM STATE OF NEW JERSEY I, Paul J. Davison, of full age, being duly sworn according to law, upon my oath depose and say:

1. I am the Site Vice President-Hope Creek for PSEG Nuclear, and as such am authorized to sign Hope Creek's Discharge Monitoring Reports submitted to the New Jersey Department of Environmental Protection pursuant to the Station's New Jersey Pollutant Discharge Elimination System permit.
2. I certify under penalty of law that I have personally examined and am familiar with the information submitted in this document and all attachments and that, based on my inquiry of those individuals immediately responsible for obtaining the information, I believe the submitted information is true, accurate and complete. I am aware that there are significant penalties for submitting false information including the possibility of fine and imprisonment.
3. The signature on the attached Discharge Monitoring Reports is my signature and I am submitting this affidavit in satisfaction of the requirement that my signature be notarized.

Paul J. Davison Site Vice President - Hope Creek Sworn and subscribed before me this ~ / s+ day of July, 2016.

JENNIFER M. TURNER NOTARY PUBLIC OF NEW JERSEY ID # 2332557 My Commission Expires 8/8/2020

New Jersey Department of Environmental Protection Pl46815 Division of Water Quality Surface Water Discharge Monitoring Report Submittal Form NJPDES PERMIT MONITORING PERIOD MONITORED LOCATION:

I Month I Day I Year I Month I Day I Year I 461A - DSN 461A - DSW NJ0025411 I 6 I 1 I 2016 I To I 6 I 30 I 2016 I PERMITTEE: LOCATION OF ACTIVITY: REPORT RECIPIENT:

PSE&G NUCLEAR LLC HOPE CREEK GENERATING STATION PSE&G PO BOX 236 - ALLOWAY CREEK NECK RD ARTIFICIAL ISLAND TRAVIS ZIGO HANCOCKS BRIDGE, NJ 08038 FOOT OF BUTTONWOOD RD PO BOX 236 I Hl5 LOWER ALLOWAYS CREEK, NJ 08038 HANCOCKS BRIDGE, NJ 08038 REGION I COUNTY: Southern I Salem County CHECK IF APPLICABLE: D No Discharge this Monitoring Period !ZI Monitoring Report Comments Attached WHO MUST SIGN The highest ranking official having day-to-day managerial and operational responsibilities for the discharging facility shall sign the certification or, in his absence a person designated by that person. For a local agency, the highest ranking operator of the treatment works shall sign the certification. Where the highest ranking operator, does not have the ability to authorize capital expenditures and hire personnel, a person having that responsibility or person designated by that person shall also sign the second certification at the bottom of this page. If the local agency has contracted with another entity to operate the treatment works, the highest-ranking official of the contracted entity shall sign the certification.

I certify under penalty of law that I have personally examined and am familiar with the information submitted in this document and all attachments, and that, based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of and/or imprisonment, pursuant to N.J.A.C. 7: 14A-6.9(B). The New Jersey water Pollution Control Act provides for penalties up to $50,000 per violation.

Paul J. Davison. Site Vice President-Hope Creek N/A NAME AND TITL~ PRINCIPA~ECUTIVE OFFICER, AUTHORIZED AGENT, OR *LICENSED OPERATOR GRADE AND REGISTRY NUMBER (IF APPLICABLE)

,.,_i~,U~ 856-339-1555 DATE AREA CODE/PHONE NUMBER

  • For a local agency where the highest-ranking operator does not have the ability to authorize capital expenditures and hire personnel, a person having that responsibility or person designated by that person shall sign the following cert(fication:

I certify under penalty of law and in accordance with N.J.S.A. 58:1 OA-6F(5) that I have reviewed the attached discharge monitoring reports.

N/A N/A N/A N/A NAME AND TITLE SIGNATURE DATE AREA CODE/PHONE NUMBER

Surface Water Discharge Monitoring Report Pl46815 PERMIT NUMBER: MONITORED LOCATION: MONITORING PERIOD: FACILITY NAME:

NJ0025411 461A DSN 461A- DSW 6/1/2016 TO 6/30/2016 HOPE CREEK GENERATING STATION NO. FREQ.OF SAMPLE PARAMETER QUANTITY OR LOADING UNITS UNITS EX. ANALYSIS TYPE Flow, In Conduit or Thru Treatment Plant 50050 1 Effluent Gross Value Flow, In Conduit or Thru Treatment Plant 50050 7 Intake From Stream pH 00400 1 Effluent Gross Value LC50 Statre 96hr Acu Mysid Bahia TAN3E 1 Effluent Gross Value IC25 Statre 7day Chr Mysid Bahia TBP3E 1 Effluent Gross Value Chlorine Produced Oxidants

  • CPOX 1 Effluent Gross Value Comments: If there are any questions regarding the monitoring report form, please contact Heather Genievich of the Bureau of Surface Water Permitting at (609) 292-4860.
  • See... (;>'Plo....:.CL.~o,._;, c:i-t Co,;:,d;-\-k,1.':>'S Pre-Print Creation Date: 41112016 Page 1of3

Surface Water Discharge Monitoring Report Pl46815 PERMIT NUMBER: MONITORED LOCATION: MONITORING PERIOD: FACILITY NAME:

NJ0025411 4Ei1A DSN 461A- DSW 6/1/2016 TO 6/30/2016 HOPE CREEK GENERATING STATION NO. FREQ. OF SAMPLE PARAMETER QUANTITY OR LOADING UNITS QUALITY OR CONCENTRATION UNITS EX. ANALYSIS TYPE Temperature, oC 00010 1 Effluent Gross Value Temperature, oC 00010 7 Intake From Stream Carbon, Tot Organic (TOC) 00680 1 Effluent Gross Value Carbon, Tot Organic (TOC) 00680 2 Effluent Net Value Carbon, Tot Organic (TOC) 00680 7 Intake From Stream Sulfate, Total (as 504) 00945 1 Effluent Gross Value Comments: If there are any questions regarding the monitoring report form, please contact Heather Genievich of the Bureau of Surface Water Permitting at (609) 292-4860.

Pre-Print Creation Date: 41112016 Page 2 of3

Surface Water Discharge Monitoring Report Pl46815 PERMIT NUMBER: MONITORED LOCATION: MONITORING PERIOD: FACILITY NAME:

NJ0025411 4(i1A DSN 461A- DSW 6/1 /2016 TO 6/30/2016 HOPE CREEK GENERATING STATION NO. FREQ. OF SAMPLE PARAMETER QUANTITY OR LOADING UNITS QUALITY OR CONCENTRATION UNITS EX. ANALYSIS TYPE Boron, Total (as B) 01022 1 Effluent Gross Value Heat (summer)

(per Hr.)

81386 1 Effluent Gross Value

Copper, Total Recoverable 01119 1 Effluent Gross Value Lab Certification #

99999 99 Lab Comments: If there are any questions regarding the monitoring report form, please contact Heather Genievich of the Bureau of Surface Water Permitting at (609) 292-4860.

Pre-Print Creation Date: 41112016 Page 3 of 3

New Jersey Department of Environmental Protection Pl46815 Division of Water Quality Surface Water Discharge Monitoring Report Submittal Form NJPDES PERMIT MONITORING PERIOD MONITORED LOCATION:

NJ0025411 I Month I Day I Year I I Month I Day I Year I 461 C - DSN 461 C - DSW internal I 6 I 1 I 2016 I To I 6 I 30 I 2016 I PERMITTEE: LOCATION OF ACTIVITY: REPORT RECIPIENT:

PSE&G NUCLEAR LLC HOPE CREEK GENERATING STATION PSE&G PO BOX 236 -ALLOWAY CREEK NECK RD ARTIFICIAL ISLAND TRAVIS ZIGO HANCOCKS BRIDGE, NJ 08038 FOOT OF BUTTONWOOD RD PO BOX 236 I Hl5 LOWER ALLOWAYS CREEK, NJ 08038 HANCOCKS BRIDGE, NJ 08038 REGION I COUNTY: Southern I Salem County CHECK IF APPLICABLE: D No Discharge this Monitoring Period D Monitoring Report Comments Attached WHO MUST SIGN The highest ranking official having day-to-day managerial and operational responsibilities for the discharging facility shall sign the certification or, in his absence a person designated by that person. For a local agency, the highest ranking operator of the treatment works shall sign the certification. Where the highest ranking operator does not have the ability to authorize capital expenditures and hire personnel, a person having that responsibility or person designated by that person shall also sign the second certification at the bottom of this page. If the local agency has contracted with another entity to operate the treatment works, the highest-ranking official of the contracted entity shall sign the certification.

I certify under penalty of law that I have personally examined and am familiar with the information submitted in this document and all attachments, and that, based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of and/or imprisonment, pursuant to N.J.A.C. 7: 14A-6.9(B). The New Jersey water Pollution Control Act provides for penalties up to $50,000 per violation.

Paul J. Davison, Site Vice President- Hope Creek N/A GRADE AND REGISTRY NUMBER (IF APPLICABLE) 7 l ;i_l \ \" 856-339-1555 DATE AREA CODE/PHONE NUMBER

  • For a local agency where the highest-ranking operator does 1101 have the ability to authorize capital expenditures and hire personnel, a person having that responsibility or person designated by that person shall sign the following cert(fication:

I certify under penalty oflaw and in accordance with N.J.S.A. 58:10A-6F(5) that I have reviewed the attached discharge monitoring reports.

N/A N/A N/A N/A NAME AND TITLE SIGNATURE DATE AREACOD~PHONENUMBER

Surface Water Discharge Monitoring Report Pl46815 PERMIT NUMBER: MONITORED LOCATION: MONITORING PERIOD: FACILITY NAME:

NJ0025411 4Ei1C DSN 461C - DSW intern<<l 61112016 TO 6/30/2016 HOPE CREEK GENERATING STATION NO. FREQ. OF SAMPLE PARAMETER QUANTITY OR LOADING UNITS UNITS EX. ANALYSIS TYPE Flow, In Conduit or Thru Treatment Plant 50050 1 Effluent Gross Value Solids, Total Suspended 00530 1 Effluent Gross Value Petrol Hydrocarbons, Total Recoverable 45501 1 Effluent Gross Value Carbon, Tot Organic (TOC) 00680 1 Effluent Gross Value Lab Certification #

99999 99 Lab Comments: If there are any questions regarding the monitoring report form, please contact Heather Genievich of the Bureau of Surface Water Permitting at (609) 292-4860.

Pre-Print Creation Date: 41112016 Page 1of1

New Jersey Department of Environmental Protection Pl46815 Division of Water Quality Surface Water Discharge Monitoring Report Submittal Form NJPDES PERMIT MONITORING PERIOD MONITORED LOCATION:

Mouth Day Year Mouth Da Year NJ0025411 6 1 2016 To 6 30 2016 462B - DSN 462B - DSW Internal PERMITTEE: LOCATION OF ACTIVITY: REPORT RECIPIENT:

PSE&G NUCLEAR LLC HOPE CREEK GENERATING STATION PSE&G PO BOX 236 - ALLOWAY CREEK NECK RD ARTIFICIAL ISLAND TRAVIS ZIGO HANCOCKS BRIDGE, NJ 08038 FOOT OF BUTTONWOOD RD PO BOX 236 I Hl5 LOWER ALLOWAYS CREEK, NJ 08038 HANCOCKS BRIDGE, NJ 08038 REGION I COUNTY: Southern I Salem County CHECK IF APPLICABLE: D No Discharge this Monitoring Period D Monitoring Report Comments Attached WHO MUST SIGN The highest ranking official having day-to-day managerial and operational responsibilities for the discharging facility shall sign the certification or, in his absence a person designated by that person. For a local agency, the highest ranking operator of the treatment works shall sign the certification. Where the highest ranking operator does not have the ability to authorize capital expenditures and hire personnel, a person having that responsibility or person designated by that person shall also sign the second certification at the bottom of this page. If the local agency has contracted with another entity to operate the treatment works, the highest-ranking official of the contracted entity shall sign the certification.

I certify under penalty of law that I have personally examined and am familiar with the information submitted in this document and all attachments, and that, based on my inquiry of those individuals immediately responsible for obtaining the information, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of and/or imprisonment, pursuant to N.J.A.C. 7: 14A-6.9(B). The New Jersey water Pollution Control Act provides for penalties up to $50,000 per violation.

Paul J. Davison, Site Vice President- Hope Creek N/A NAME AND TITLE OF PRINCIPAL EXECUTIVE OFFICER, AUTHORIZED AGENT, OR *LICENSED OPERATOR GRADE AND REGISTRY NUMBER (IF APPLICABLE)

~vJlJ. O~ . 1l21l \b 856-339-1555 SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER, AUTHORIZED AGENT, OR *LICENSED OPERATOR DATE AREA CODE/PHONE NUMBER

  • For a local agency where the highest-ranking operator does not have the ability to authorize capital expenditures mid hire personnel, a person having that responsibility or person designated by that person shall sign the following certification:

I certify under penalty of law and in accordance with N.J.S.A. 58: 1OA-6F(5) that I have reviewed the attached discharge monitoring reports.

N/A N/A N/A N/A NAME AND TITLE SIGNATURE DATE AREACODlliPHONENUMBER

Surface Water Discharge Monitoring Report Pl46815 PERMIT NUMBER: MONITORED LOCATION: MONITORING PERIOD: FACILITY NAME:

NJ0025411 4628 DSN 4628 - DSW Interna 6/1/2016 TO 6/30/2016 HOPE CREEK GENERATING STATION NO. FREQ.OF SAMPLE PARAMETER QUANTITY OR LOADING UNITS UNITS EX. ANALYSIS TYPE Flow, In Conduit or Thru Treatment Plant 50050 1 Effluent Gross Value BOD, 5-Day (20 oC) 00310 G Raw Sew/influent BOD, 5-Day (20 oC) 00310 1 Effluent Gross Value BOD, 5-Day (20 oC) 00310 K Percent Removal Solids, Total Suspended 00530 G Raw Sew/influent Solids, Total Suspended 00530 1 Effluent Gross Value Comments: If there are any questions regarding the monitoring report form, please contact Heather Genievich of the Bureau of Surface Water Permitting at (609) 292-4860.

Pre-Print Creation Date: 41112016 Page 1of2

Surface Water Discharge Monitoring Report Pl46815 PERMIT NUMBER: MONITORED LOCATION: MONITORING PERIOD: FACILITY NAME:

NJ0025411 46128 DSN 4628 - DSW lnternCJ 6/1/2016 TO 6/30/2016 HOPE CREEK GENERATING STATION NO. FREQ.OF SAMPLE PARAMETER QUANTITY OR LOADING UNITS QUALITY OR CONCENTRATION UNITS EX. ANALYSIS TYPE Solids, Total Suspended 00530 K Percent Removal Oil and Grease 00556 1 Effluent Gross Value Nitrogen, Ammonia Total (as N) 00610 1 Effluent Gross Value Enterococci 61211 1 Effluent Gross Value Coliform, Fecal General 74055 1 Effluent Gross Value Lab Certification #

99999 99 Lab Comments: If there are any questions regarding the monitoring report form, please contact Heather Genievich of the Bureau of Surface Water Permitting at (609) 292-4860.

Pre-Print Creation Date: 41112016 Page 2 of2