Perry Nuclear Power Plant, Unit 1 Table 1. Current Design Basis Flood Hazards for Use in the MSA Mechanism Stillwater Elevation Waves/

Runup Reference Design Basis Hazard Elevation Local Intense Precipitation 620.5 ft NGVD29 Minimal 620.5 ft NGVD29 FHRR Rev. 0 Section 2.1.1 & Table 2 Failure of Dams and Onsite Water Control/Storage Structures Not included in DB Not included in DB Not included in DB FHRR Rev. 0 Section 2.1.3 & Table 2

Streams and Rivers Major Stream 624.0 ft NGVD29 Not applicable 624.0 ft NGVD29 FHRR Rev. 0 Section 2.1.2 & Table 2 Minor Stream 619.5 ft NGVD29 Not applicable 619.5 ft NGVD29 FHRR Rev. 0 Section 2.1.2 & Table 2 Storm Surge High Water 580.5 ft NGVD29 27.4 ft 607.9 ft NGVD29 FHRR Rev. 0 Section 2.1.4 & Table 2 FHRR Rev. 0 Section 2.1.8 & Table 2 Seiche Seiche is Combined with Storm Surge in CDB Not included in DB Not included in DB Not included in DB FHRR Rev. 0 Section 2.1.4 & Table 2 Tsunami Not included in DB Not included in DB Not included in DB FHRR Rev. 0 Section 2.1.5 & Table 2 Ice-Induced Flooding No Impact on the Site Identified No Impact on the Site Identified No Impact on the Site Identified FHRR Rev. 0 Section 2.1.6 & Table 2

Perry Nuclear Power Plant, Unit 1 Table 1. Current Design Basis Flood Hazards for Use in the MSA Mechanism Stillwater Elevation Waves/

Runup Reference Design Basis Hazard Elevation Note 1: Reported values are rounded to the nearest one-tenth of a foot.

Channel Migrations/Diversions Not included in DB Not included in DB Not included in DB FHRR Rev. 0 Section 2.1.7 & Table 2

Perry Nuclear Power Plant, Unit 1 Table 2. Reevaluated Flood Hazards for Flood-Causing Mechanisms for Use in the MSA Mechanism Stillwater Elevation Waves/

Runup Reevaluated Hazard Elevation Reference Note 2: Reevaluated hazard mechanisms bounded by the current design basis (see Table 1) are not included in this table Note 3: Reported values are rounded to the nearest one-tenth of a foot.

Local Intense Precipitation 621.3 ft NGVD29 Minimal 621.3 ft NGVD29 FHRR Rev 1 Section 3.8.4 & Table 5 Power Block 620.5 ft NGVD29 Minimal 620.5 ft NGVD29 FHRR Rev 1 Section 3.8.4 North of Power Block at the Service Water Pumphouse Building and the Emergency Service Water Pumphouse Building Streams and Rivers 628.5 ft NGVD29 Not applicable 628.5 ft NGVD29 FHRR Rev. 1 Section 3.1.4 & Table 5 Major Stream 619.7 ft NGVD29 Not applicable 619.7 ft NGVD29 FHRR Rev. 1 Section 3.1.4 & Table 5 Minor Stream Storm Surge 581.9 ft NGVD29 27.6 ft 609.5 ft NGVD29 FHRR Rev. 1 Section 3.7.4 & Table 5 High Water: East of the Power Block Along the Shoreline Bluff Slopes (Probable Maximum Storm Surge Resulting from a Probable Maximum Wind Storm)

Note 1: The licensee is expected to develop flood event duration parameters and applicable flood associated effects to conduct the MSA. The staff will evaluate the flood event duration parameters (including warning time and period of inundation) and flood associated effects during its review of the MSA.

Note 4: "The Perry Local datum is originally based on and within the tolerance levels of the NGVD 29 datum."

(

Reference:

FHRR Rev. 1 Section 3)