Part 21 - Deviation for Class 1E Solid State Relays (47H and 60Q)
ML16188A378
Person / Time
Site: Prairie Island  
Issue date: 06/24/2016
From: Batovsky D
ABB
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
52041
Download: ML16188A378 (4)


Text

0612412016 U.S. Nuclear Regulatory Commission Operations Center Event Report Page J Part 21 (PAR)

Event#

52041 Rep Org: ABB INC.

Supplier: ABB INC.

Notification Date I Time: 06/24/2016 13:20 (EDT)

Event Date I Time: 04/26/2016 (EDT)

Last Modification: 06/24/2016 Region: 1 Docket#:

City: CORAL SPRINGS Agreement State:

Yes County:

License #:

State: FL NRC Notified by: DENNIS BATOVSKY Notifications: RANDY MUSSER HQ Ops Officer: VINCE KLCO ROBERT ORLIKOWSKI Emergency Class: NON EMERGENCY PART 21/50.55 REACTORS 10 CFR Section:

21.21(d)(3)(i)

DEFECTS AND NONCOMPLIANCE PART 21 - DEVIATION FOR CLASS 1 E SOLID STATE RELAYS (47H AND 600)

The following information was excerpted from a received licensee fax:

R2DO R3DO EMAIL On April 26, 2016, ABB confirmed a customer complaint regarding a 600 relay received with an internal short circuit. The cause was determined to be a manufacturing deyiation from specification.

Records show a total of 53 suspect relays were provided to 2 customers (Prairie Island and Tennessee Valley Authority).

Based on the nature of the deviation, any installed relay would have failed upon application of power in the relay.

Therefore, the primary concern is that any relay, either in storage or installed with no power applied, may have this defect and will create a system malfunction upon power application.

If you have any questions regarding this notice, please contact the ABB Technical Support at (954) 752-6700.

June 24, 2016 Document Control Desk US Nuclear Regulatory Commission Washington, DC 20555-001

Subject:

10 C.F.R. Part 21 Notification of Deviation - Solid State Relays.

Dear Sir or Madam:

This letter provides notification of a deviation for Class lE Solid State Relays (47H and 60Q).

On April 26, 2016, ABB confirmed a customer complaint regarding a 60Q relay received with an internal short circuit between traces (DC control Power Input Tenninal 7 and AC Input Tenninal 2) on the back-plane module (ABB Part Number 612744-006). The cause was determined to be a manufacturing deviation from specification in the bare Printed Circuit Board (PCB).

Further, the dielectric testing process designed to detect such deviations was likely not carried out properly, leading to the relay being shipped with the deviation. While it is unlikely that additional deviations exist in shipped product, ABB cannot definitively rule out the possibility of others in the population.

Records show a total of 53 suspect relays were provided to 2 customers detailed in the separately attached document provided.

Based on the nature of the deviation - any installed relay would have failed upon application of power to the relay. Therefore, the primary concern is that any relay, either in storage or installed with no power applied, may have this defect and will create a system malfunction upon power application.

ABB does not have the capability to perform the evaluation to determine if a defect exists, and therefore in accordance with 10 C.F.R. 21.2l(b), we are notifying the purchasers or affected licensees of this determination so that they may evaluate the deviation, pursuant to IO C.F.R. 21.2l(a).

ABB recommends that the affected licensees evaluate their specific application and determine whether the deviation described in this notice affects their design basis. If it is determined that it does, the licensees should contact ABB to determine appropriate corrective action. Any relay that is not currently in use can be returned to ABB forinspection at no charge to the customer.

ABB is conducting the following action:

ABB issued a corrective action to improve Solid State Relays Hi-potential test process.

If you have any questions regarding this notice, please contact the ABB Technical Support 954-752-6700.

Very truly yours,

/~

-8~

t:J Dennis Batovsky Managing Director Protective Relays and Switches 4300 coral Ridge Drive Coral Springs FL 33065 Tel. (954) 752-6700 Fax (954) 345-5329 www. abb.us/substatlonautomation

CUSTOMER ORDER DATE PRAlRIE ISLAND DN18434 8/25/2015 NUCLEAR POWER PLANT TENNESSEE AA1669967 10/23/2015 VALLEY AUTHORITY (TV A)

TENNESSEE AAI603664 7/14/2015 VALLEY AUTHORITY (TV A)

Protective Relays and switches 4300 Coral Ridge Drive Coral Springs FL33065 1111 1111 STYLE 412N0175-1E 41215275-lE 41215375-lE 41215275-lE 41215375-lE Tel. (954) 752*6700 Fax [954) 345-5329 DESCRIPTION SERIAL QTY NUMBERS TYPE47H 201517176 2

CLASS lE 201517177 TYPE60Q 201517566 8

CLASS lE 201517567 201517568 201517569 201517570 201517571 201517572 201517573 TYPE60Q 201517574 4

CLASSIE 201517575 201517576 201517577 TYPE60Q 201515705 10 CLASS lE 201515706 201515707 201515708 201515709 201515710 201515711 201515712 201515713 201515714 TYPE60Q 201516124 5

CLASS lE 201516125 201516126 201516127 201516128 www.abb.us/substatlonautomatlon

CUSTOMER ORDER DATE Jl*llll STYLE TENNESSEE AA1656434 10/5/2015 41215275-lE VALLEY AUTHORITY (TV A)

Protective Relavs and Switches 4300 Coral Ridge Drive Coral Springs FL 33065 41215375-IE Tel. (954) 752*6700 FaK 1954) 345-5329 DESCRIP'O:ON SERIAL QTY NUMBERS TYPE60Q 201517168 16 CLASS lE 20.1517169 201517170

_j 201517171 201517172 201517173 201517174 201517175 201517313 201517314 201517315 201517316 201517317 201517318 201517319 201517320 TYPE60Q 201517321 8

CLASS IE 201517322 201517323 201517324 201517325 201517326 201517327 201517328 www. abb.us/substatlcnautomatlon