Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Jerud Hanson Nuclear Energy Institute 1201 F St., NW Suite 1100 Washington, DC 20004-1218
SUBJECT:
LICENSE RENEWAL INTERIM STAFF GUIDANCE, LR-ISG-2016-01, CHANGES TO AGING MANAGEMENT GUIDANCE FOR VARIOUS STEAM GENERATOR COMPONENTS
Dear Mr. Hanson:
I am writing to inform the Nuclear Energy Institute of the opportunity to comment on the draft License Renewal Interim Staff Guidance (LR-ISG), LR-ISG-2016-01, Changes to Aging Management Guidance for Various Steam Generator Components. Enclosed is a copy of the Federal Register notice that announces the U.S. Nuclear Regulatory Commissions (NRCs) request for comments and provides instructions on how to submit comments.
Based on recent operating experience and staffs review of the analyses performed by the industry, the NRC staff has determined that the existing guidance in NUREG-1800, Revision 2, Standard Review Plan for Review of License Renewal Applications for Nuclear Power Plants (SRP-LR), and NUREG-1801, Revision 2, Generic Aging Lessons Learned (GALL) Report, should be revised to provide updated recommendations for aging management of steam generator divider plate assemblies, tube-to-tubesheet welds, tubesheets, and heads (i.e.,
channel or lower/upper heads) within the scope of Title 10 of the Code of Federal Regulations Part 54.
Examples of the major changes are: (a) addition of visual inspections of steam generator head internal areas to GALL Report Section XI.M19, Steam Generators, to detect signs of cracking or loss of material (e.g., detection of rust stains and gross cracking or distortion); (b) changes to SRP-LR Sections 3.1.2.2.11 and 3.1.3.2.11, Cracking due to Primary Water Stress Corrosion Cracking that describe further evaluation regarding primary water stress corrosion cracking (PWSCC) in divider plate assemblies and tube-to-tubesheet welds; and (c) changes to the aging management review items in the GALL Report and SRP-LR to provide updated guidance for managing cracking due to PWSCC and loss of material due to boric acid corrosion in steam generator components.
We also plan to consider the information in this LR-ISG and make corresponding changes when finalizing the aging management guidance for the subsequent license renewal period (i.e., up to 80 years of operation), which is documented in draft NUREG-2191, Generic Aging Lessons Learned for Subsequent License Renewal Report (GALL-SLR), and draft NUREG-2192, Standard Review Plan for Review of Subsequent License Renewal for Nuclear Power Plants (SRP-SLR), if it is practicable to do so in terms of the development schedule for subsequent license renewal guidance.
May 27, 2016
To inform other stakeholders of the opportunity to provide comments on the draft LR-ISG-2016-01, courtesy copies of this letter are being sent to subscribers of an NRC electronic mailing list on general license renewal topics.
If you have any questions, please contact Dr. Seung Min of my staff by telephone at 301-415-2045 or by e-mail at Seung.Min@nrc.gov.
Sincerely,
/RA/
Dennis C. Morey, Acting Deputy Director Division of License Renewal Office of Nuclear Reactor Regulation
Enclosure:
As stated cc: Reactor License Renewal Stakeholder Group Listserv
ML16102A232 (Package), ML16102A308 (Letter), ML16102A268 (Draft LR-ISG), ML16099A259 (FRN)
- concurrence via email OFFICE ME:DLR:RARB STA:NRR/DE STA:NRR/DLR BC:DLR:RSRG NAME SMin
- KKarwoski
- AHiser SBloom DATE 4/7/2016 4/8/2016 4/7/2016 5/6/2016 OFFICE LA:DLR:RPB1 OGC BC:DLR:RARB DD:DLR (Acting)
NAME
- IBetts
- JLindell DMorey DMorey DATE 4/18/2016 5/25/2016 5/3/2016 5/ 27 /2016
Letter to J. Hanson from D. Morey dated May 27, 2016
SUBJECT:
LICENSE RENEWAL INTERIM STAFF GUIDANCE, LR-ISG-2016-01, CHANGES TO THE AGING MANAGEMENT GUIDANCE FOR VARIOUS STEAM GENERATOR COMPONENTS DISTRIBUTION:
E-MAIL:
PUBLIC RidsNrrDlr Resource RidsNrrDlrRpb1 Resource RidsNrrDlrRpb2 Resource RidsNrrDlrRarb Resource RidsNrrDlrRapb Resource RidsNrrDlrRasb Resource RidsNrrDlrRerb Resource RidsNrrDlrRpob Resource RidsNrrDra Resource RidsNrrDe Resource RidsNrrDss Resource RidsOgcMailCenter Resource RidsOpaMail Resource RidsOcaMailCenter Resource SMin, NRR KKarwoski, NRR AHiser, NRR MGray, RI SVias, RII AStone, RIII GMiller, RIV