Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 April 6, 2016 Ms. Angela Hall Tennessee Department of Environment and Conservation Division of Water Resources William R. Snodgrass Tennessee Tower 312 Rosa L. Parks Avenue, 11th Floor.
Nashville, Tennessee 37243
Dear Ms. Hall:
r*
TENNESSEE VALLEY AUTHORITY (TVA)-SEQUOYAH NUCLEAR PLANT (SQN)-NPDES
. PE,RMIT NO. TN0026450 - DISCHARGE MONITORING REPORT (DMR) FOR March 2016 Enclosed is the March 2016 Discharge Monitoring Report for Sequoyah Nuclear Plant. Modifications are currently being performed on the Low Volume Waste Treatment pond discharge pipe to accommodate the installation of a C02 system for pH control. To facilitate the modification, all flows \\
to the pond were diverted to the Yard Pond. The Turbine Building sump (TBS) was aligned to the.
Yard Pond from March 15 - 31, 2016, and the Neutral Waste sump (NWS) was aligned to the Yard Pond from March 17 -31, 2016. Monitoring data for the TBS and the*NWS are given in Attachments 1 and 2, respectively.. This work is expected to continue through the end of April 2016.
There were no exceedances during the monitoring period. If you have any questions or need additional information, please contact Millicent Garland by email at mrmoore@tVa.gov or by phone at (423) 843-6714.
I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
I Sincerely, 1stopher J. Schwarz Site Vice President Sequoyah Nuclear Plant Enclosures cc (Enclosures):
- Chattanooga Environmental Field Office Division of Water Pollution Control State Office Building, Suite 550
- 540 Mccallie Avenue Chattanooga, Tennessee 37402-2013 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
TV A Sequoyah Nuclear Plant NPDES Permit.Number TN0026450 Turbine Building Sump Monitoring Data The turbine building sump was discharged directly to the yard drainage pond from 3/15/2016 to 3/31/2016. During this period, the turbine building sump was monitored in accordance with the narrative condition found in Part l.A.2 of the NPDES Permit TN0026450. There are no permit limits applicable at this monitoring point, which flows to the yard drainage pond, mixes with other flows in the diffuser pond, then discharges to the Tennessee River at Outfall 101.
Parameter Daily Minimum Monthly Avera2e Daily Maximum No. of Samples Flow 1.48 MGD l.52MGD 17 pH 8.40 s.u.
8.55 s.u.
2 O&G
<5.0mg/L
<5.0 mg/L 2
<5.0mg/L
<5.0mg/L 2
TV A Sequoyah Nuclear Plant
- NPDES Permit Number TN0026450 Neutral Waste Sump Monitoring Data The neutral waste sump was discharged directly to the yard drainage pond from 3/17/2016 to 3/31/2016. During this period, the neutral waste sump was monitored in accordance with the narrative condition found in Part l.A.2 of the NP DES Permit TN0026450. There are no permit limits applicable at this monitoring point, which flows to the yard drainage pond, mixes with other flows in the diffuser pond, then discharges to the Tennessee River at Outfall 101.
Parameter Daily Minimum Monthly Averae;e Daily Maximum No. of Samples Flow 0.127MGD 0.157MGD 15 pH 7.87 s.u.
7.93 s.u.
2 O&G
<5.0mg/L
<5.0 mg/L 2
<2.5 mg/L
<2.5 mg/L 2
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~-~~-SEQUO~~UCLEARPLANT ___ _
Addres_L _E.Q....BOX 2000 ___________ _
___... !INTEROFFICE Q.E.S-5N-SQNl _______ _
_ _ _ _§ODDY-DAISYJij7384_ _______ _
Fa~-~A-SEQUQYAHNUCLEARP~NC ____ _
Location_....!:!AMIL TOJi.COUNTY_ _________ _
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
DISCHARGE MONITORING REPORT (DMR)
TN0026450 101 G PERMIT NUMBER DISCHARGE NUMBER MAJOR (SUBR 01)
F-FINAL DIFFUSER DISCHARGE EFFLUENT Form Approved.
OMB No. 2040-0004 MO DAY I YEAR MO ATIN:Millicent Garland From! 16 I 03 I 01 I To I 16 I 03 DAY 31
- NO DISCHARGE D PARAMETER TEMPERATURE, WATER DEG.
CENTIGRADE 00010 1
0 EFFLUENT GROSS TEMPERATURE, WATER DEG.
CENTIGRADE 00010 z
0 INSTREAM MONITORING TEMP. DIFF. BETWEEN SAMP. &
UPSTRM DEG.C 00016 EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS VALUE CHLORINE, TOTAL RESIDUAL 50060 1
0 EFFLUENT GROSS VALUE TEMPERATURE* C, RATE OF CHANGE 82234 0
EFFLUENT GROSS NOTE: Read instructions before complelin~ this form.
EX OF TYPE QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE
~~A=V=E=RA=G=E~--.~-M=AX-IM=U=M=---.-U-N=IT=s~*""'-M~IN=IM=U-M~-~-A-V=E=RA=G=-E-=...--MAX--IM=U=M-_,,,,,_U=N=IT=S~
ANALYSIS SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT
- *:. ~'l:>ERMit *:
. REQWIREr.'IE!fF SAMPLE MEASUREMENT
. *;PERM1r:* *
.. REQUiR~ME~T *:
SAMPLE MEASUREMENT
.* PEJ31v11T..
REQUIREMENT
. ~. _,.,*
SAMPLE MEASUREMENT
- ,PERMIT
. REQUIR~MENT 1761 Reqii\\ilon;
- M~fAvs*
11'11 0.3 2;0 DAILY.MX 03 MGD 03 MGD 62 DEG C/HR 04 0
31/31 RCORDR 29.4 DEG.C.
17.8 04 0
31 / 31 MODELO DEG.C.
~*".****~~*:-:**.~ <, /.;f~*.~~*~~*, '; :.
~~: :.,.c.\\~9*~.;, ' ~J.
,:,, *..:,- DAILY;MX.
3.7 04 0
31/31 CALCTD DEG.C.
0 31 / 31 RCORDR
<'.¢ONJI' 'RC6ReR;
- t-1~p1:1$**.
. ; *.i. '*******" : .:". : '",**"!**.~*"':
03 0
31 / 31 CALCTD MGD GRAB 13 / 31 0.022 0.016 19 0
. p.1.
, 0~1 MG/L
... MO.'AVG * *. *. DAILY MAx
.:;.FIVE PER: CALC:to:
.*WEl;:K 0
31/31 CALCTD
- . CON:tl. CAlClJ>.*
- Nuous.
- NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my
~~~--
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the Site Vic~
person or persons who manage the system, or those persons directly responsible for.gathering 423 843-7001 16 04 06 Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE I
information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA I NUMBER YEAR MO DAY TYPED OR PRINTED CODE COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference all attachments here)
No closed mode operation. The following injections occurred: Floguard MS6236 (max calc. was 0.03 mg/L, limit 0.20 mg/L, Spectrus BD1500 (max calc. was 0.016 mg/L, limit 2.0 mg/L).
Prf#Vi~ ~sJ.itigns mav be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~ __
NA-SEQUO~~UCLEARPLANT ___ _
AddreS.L _..E.Q,_BOX 2000 -
___ __(!NTEROFFICE OPS-5N-SQNl _______ _
___ _§ODDY-DAISUij73BL _______ _
Fa~
_IVA-SEQUO~HNUCLEARPLANL ____ _
Locati~.J:!AMl~~COUNTY_ _________ _
ATIN:Millicent Garland NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPOES)
DISCHARGE MONITORING REPORT (DMRJ TN0026450 From I
101 T I
I DISCHARGE NUMBER I MAJOR (SUBR 01)
F-FINAL Form Approved.
OMB No. 2040-0004 BIOMONITORING FOR OUTFALL 101 EFFLUENT
- NO DISCHARGE D NOTE: Read instructions before completinQ this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE F====A~V~E~RA~G~E=~r===M~AX=IM~U~M=~=U~N~IT~S=+-=M~l~N~IM~U~M==~=A~V~E~RA~G=E='""F=~MAX=~IM~U~M=~=U~N~IT~S~
ANALYSIS IC25 STATRE 7DAY CHR CERIODAPHNIA Monitoring Not Re uired TRP38 1
0 EFFLUENT GROSS IC25 STATRE 7DAY CHR PIMEPHALES TRP6C 0
EFFLUENT GROSS NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penally of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, Site Vice President accurate, and complete. I am aware that there are*significant penalties for submitting false information, including the possibility of fine and Imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
Toxicity was not sampled in March 2016.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used
~L--
Vice~:s1ue~t SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR AUTHORIZED AGENT 23
~* ;;
TELEPHONE DATE 423 843-7001 16 04 06 I
AREA I NUMBER YEAR MO DAY CODE Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~ __
NA-SEQUO~~UCLEARPLANT ___ _
Addres,L _f.Q....BOX 2000 ___________ _
___.J!.NTEROFFICE OPS-5N-SQ.lil _______ _
_§.ODDY-MISYJ.~738L _______ _
Facjfily_ JYA-_fil:QUOYAH NUCLEAR PLANT_ -
LocaliO.!L _tlAMIL TOJi_COUNTX.... -
ATTN:Millicent Garland NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES}
DISCHARGE MONITORING REPORT (DMR}
TN0026450 103 G PERMIT NUMBER DISCHARGE NUMBER I YEAR I Fromi 16 I MO DA I I
I MO 03 I 01 I To I 16 I 03 DAY 31 MAJOR (SUBR 01)
F-FINAL Form Approved.
OMB No. 2040-0004 LOW VOL. WASTE TREATMENT POND EFFLUENT
- NO DISCHARGE. D NOTE: Read instructions before complelini:i this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE F=A-V_E_RA_G_E=~==M-AX=IM_U_M=.,..,,,=U-N-IT-S=+-=M=IN-IM_U_M==y-'=A-V_E_RA_G=E=""'j""'=-MAX=-IM_U_M=.,..,,,=U-N-IT-S-=-=t ANALYSIS PH 00400 0
EFFLUENT GROSS SOLIDS, TOTAL SUSPENDED 00556 0
EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE 1 099 MEASUREMENT SAMPLE MEASUREMENT
. :*:PERMIT-'. \\i :;
.* *. REQUIREMENT...
c * *
~*
SAMPLE MEASUREMENT
- . '*PERivllfc,-*.* *,.
- ,)~E_OUl~EMl:NT *
~
SAMPLE MEASUREMENT 1.274
'-r' 7.4 03 MGD NAME/TITLE PRINCIPAL EXECUTIVE OFFICER Christopher J. Schwarz I Certify under penally of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false Site Vice President 1-----------------1information, including the possibility of fine and imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here) 7.9 12 0
3 / 31 GRAB SU 13.8 13.8 19 0
1/31 GRAB MG/L 19 0
1 / 31 GRAB MG/L 4 / 31 INST AN 0
i < *o.*,* *y*,*
... 1*
TELEPHONE DATE 423 843-7001 16 04 06 AREA NUMBER YEAR MO DAY CODE The Turbine Building Sump (TBS) was discharged directly to the Yard Pond (YP) on March 15 - March 31, 2016. The neutral waste sump also was aligned to the Yard Pond March 17 - 31, 2016.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different}
Na~ _
_!VA-SEQUO~~UCLEARPLANT ___ _
Addres,L _E.Q._BOX 2000 ___________ _
___.J!.NTEROFFICE OPS-5N-SQNl _______ _
___§ODDY-MISYJ_~738L _______ _
~~-~A-SE~O~HNUCLEARP~NC ____ _
Locatio.n_.J::!AMILTOJ:LCOUNTY_ _________ _
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDESJ DISCHARGE MONITORING REPORT (DMRJ TN0026450 110 G PERMIT NUMBER DISCHARGE NUMBER MAJOR (SUBR 01)
F-FINAL RECYCLED COOLING WATER EFFLUENT Form Approved.
OMB No. 2040-0004 ATTN:Millicent Garland I.
¥0NITORING PERIOD
- NO DISCHARGE ~...
PARAMETER TEMPERATURE, WATER DEG.
CENTIGRADE 00010 0
EFFLUENT GROSS VALUE TEMPERATURE, WATER DEG.
CENTIGRADE 00010 z
0 INSTREAM MONITORING TEMP. DIFF. BETWEEN SAMP. &
UPSTRM DEG.C 00016 1
0 EFFLUENT GROSS VALUE FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 0
EFFLUENT GROSS VALUE CHLORINE, TOTAL RESIDUAL 50060 0
EFFLUENT GROSS VALUE TEMPERATURE - C, RATE OF CHANGE 82234 1
0 EFFLUENT GROSS VALUE NOTE: Read instructions before completin!I this form.
EX OF TYPE Ix QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE F=--A-V_E_RA_G_E=""'"'"9r-=M-AX=IM_U_M==-=r-U-N-IT-S=*"""'=M-l-N-IM-U-M==~=A-V-E-RA-G=E=..,..=-MAX=-IM-U-M=.....,=U-N-IT-S-ANALYSIS SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT i~~"~l,~'.""*...:,
~'. ***"*"~~'!..,.
- \\.. ::'>>:.:***
. ?PERMIT.. :. ' '.. :.. "'*******
'REO~fR~M*':,N~*. *.* >.~*\\'.
- SAMPLE MEASUREMENT
- .:*:* 'PERM1t
. ~J:qUlRf:MENT.
SAMPLE MEASUREMENT
- *PERMIT* * - *
- ;REQUiREfqENT
~
SAMPLE MEASUREMENT
- ~*f**** :. '::,
- Reqr:rillc),1,., **
- o:AIL:.Y-MX.*
-.Y.*
03 MGD 04
.. *J?°ERMIT, :
REQUiR~rvii:tfr 2'
DEG C SAMPLE MEASUREMENT
- PERMIT.
'.REQUIREMENT*
DAILYMX*
- "'~**-~~** ;; ". 'REPOR:t:**
,, ', '., *.. DAILY MX 30*5 '.. ~**.*
- '*~: : * '* ;.... :.. *,DAll'Y*ivlx'.'*
. ** : :. 5:. '
- -~:~-.*DAILY 'MX' *
,.., '(f1 0"1
- * * ;rilf:© Av(;. * ;. * -DAILY MX
- 04 DEGC 04 DEGC 04 DEGC 19 MG/L CONJ:IN' CALCTD',
)Jolls....
'. ' ' i corlltu;i,; *'RCORDR
- * * ~*uous*.. :. *
- : :*Five per: 'CA~Ci;~*
- .. ; \\1\\1~01<',.,.,.
,CONTIN.CALCTD :
-U0US. _
NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of Jaw that this document and all attachments were prepared under my
/4£J~-
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference all attachments here}
No Discharge this Period EPA Form 3320-1 (REV 3/99)
Previous editions may be used
~
SiteVi~~nt SIGNATURE OF PRINClPArtXECUTIVE OFFICER OR AUTHORIZED AGENT 423 843-7001 16 04 06 I
AREA I NUMBER YEAR MO DAY CODE Page 1 of 1
PERMITIEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name _
_!VA-SEQUO~~UCLEARPLANT ___ _
Addres§_.£.Q...BOX 2000 ___________ _
___ _[NTEROFFICE OPS-SN-SQ.ti) _______ _
___ _§ODDY-MISY._Iij73BL _______ _
Fa~-~A-SEQUOYAHNUCLEARP~NC ____ _
LocaliO.!L.JjAMIL TOJi.COUNTX_ -
ATIN:Millicent Garland NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
DISCHARGE MONITORING REPORT (DMR)
TN0026450 I
110 T I
I DISCHARGE NUMBER I MAJOR (SUBR 01)
F *FINAL RECYCLED COOLING WATER EFFLUENT
- NO DISCHARGE. I xx I ***
Form Approved.
OMB No. 2040-0004 NOTE: Read instructions before completin~ this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM IC25 STATRE 7DAY CHR CERIODAPHNIA TRP38 1
0 0
EFFLUENT GROSS VALUE IC25 STATRE 7DAY CHR PIMEPHALES TRP6C 1
0 0
EFFLUENT GROSS VALUE SAMPLE MEASUREMENT
,~
'. {,
NAME!TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. ram aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference all attachments here)
No Discharge this Period EPA Form 3320-1 (REV 3199)
Previous editions may be used
'\\,,
~/\\..C£_
c;
~-ite Vice P.[:6si ny SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR AUTHORIZED AGENT EX OF TYPE UNITS ANALYSIS 23
/servik:~ *col\\11i?os;
'*~~~~~t} :;~j;;;~;~ii'f;*;\\)
TELEPHONE DATE 423 843-7001 16 04 06 I
AREA I NUMBER YEAR MO DAY CODE Paqe 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~ _
_!VA-SEQUO~~UCLEARPLANT ___ _
Addres,L _E'..Q..BOX 2000 ___________ _
___.J!.NTEROFFICE OPS-5N-SQ~.l- ______ _
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES}
DISCHARGE MONITORING REPORT (DMR)
TN0026450
- 110 G MAJOR (SUBR 01)
F-FINAL Form Approved.
OMB No. 2040-0004
---~ODDY-DAISYJ.ij73BL _______ _
PERMIT NUMBER Fac.]!i!y _
_IVA-SEQUO~HNUCLEARP~NL ____ _
Locatio.n_..!!AMIL TO.Ji.COUNTY_ _________ _
DISCHARGE NUMBER WASTEWATER & STORM WATER EFFLUENT ATTN:Millicent Garland PARAMETER OXYGEN, DISSOLVED (DO) 00300 0
EFFLUENT GROSS SOLIDS, TOTAL SUSPENDED 00530 0
EFFLUENT GROSS SOLIDS, SETTLEABLE 00545 0
EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS NO DISCHARGE ~...
From I 16 I 03 I 01 To I 16 03 31 NOTE: Read instructions before comple!inr:i this form.
EX OF TYPE I><
QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE F="'~A-V-ERA-.-G-E-===M-N<=IM_U_M===U-N_IT_S={-=-M-1-N-IM_U_M==,...,.=A-V_E_RA_G=E=....-==~MN<=-IM_U_M=~=U-N-l-TS--=i ANALYSIS SAMPLE MEASUREMENT
.*. *.~RERMit '.>~ ;:**
- .REGllJiREMENt
- .
SAMPLE MEASUREMENT SAMPLE MEASUREMENT
- . uli,1ti..*"* '* ', *
. *.*li~if*tili \\. '-
- **,l
.' ~ ~'..:: : ': '
'" **'*"'!'..~***.,,.. '**:*~*-**....100.
,,.;~.
- .. *~" **.* * * * *...
- ... :" 'DAILY;M)C:
SAMPLE MEASUREMENT 03
. REJ°j~~~ENT: ::.R~C.?~on:,
'R~qtMO.n;:
MGD <'*... ti**-*"'-**"
i;.. :M04W.G*. '*. bAIL¥Mi
- SAMPLE MEASUREMENT
- RERMl'f,,
- REQLlii;tEME;NT
- SAMPLE MEASUREMENT
-PERMIT REQU(R.EMENT -
SAMPLE MEASUREMENT
- PERMIT:
,,~~q~iREMENJ**. *
- c.
~* '
- 19 MG/L 19 MG/L 25 MUL
. '. mMci:I.... GMEf
.*',wEl:I(' ***.... *.. *.
. : :r:w1ci::1.*: ; GRA~, *
"\\
1C
- :~w~.I;~.* .::*~:.. **,-. *:, ~.
' * ; ~NCE/ j:Sf:IMA*: *
- BATCH:... *:_ :,. ~-.**.
NAMEfflTLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of Jaw that this document and all attachments were prepared under my
?7,.((/?/ -
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submilted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering ~ --......_
Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, te Vice Pr~elem ""
423 843-7001 16 04 06 accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECtJTIVE I
information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA I NUMBER YEAR MO DAY TYPED OR PRINTED CODE COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference at/ attachments here)
During this reporting period, there has been no flow from the Dredge Pond other than that resulting from rainfall. No Discharge this Period EPA Form 3320-1 (REV 3/99)
Previous editions may be used PaQe 1 of 1
Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 April 6, 2016 Ms. Angela Hall Tennessee Department of Environment and Conservation Division of Water Resources William R. Snodgrass Tennessee Tower 312 Rosa L. Parks Avenue, 11th Floor.
Nashville, Tennessee 37243
Dear Ms. Hall:
r*
TENNESSEE VALLEY AUTHORITY (TVA)-SEQUOYAH NUCLEAR PLANT (SQN)-NPDES
. PE,RMIT NO. TN0026450 - DISCHARGE MONITORING REPORT (DMR) FOR March 2016 Enclosed is the March 2016 Discharge Monitoring Report for Sequoyah Nuclear Plant. Modifications are currently being performed on the Low Volume Waste Treatment pond discharge pipe to accommodate the installation of a C02 system for pH control. To facilitate the modification, all flows \\
to the pond were diverted to the Yard Pond. The Turbine Building sump (TBS) was aligned to the.
Yard Pond from March 15 - 31, 2016, and the Neutral Waste sump (NWS) was aligned to the Yard Pond from March 17 -31, 2016. Monitoring data for the TBS and the*NWS are given in Attachments 1 and 2, respectively.. This work is expected to continue through the end of April 2016.
There were no exceedances during the monitoring period. If you have any questions or need additional information, please contact Millicent Garland by email at mrmoore@tVa.gov or by phone at (423) 843-6714.
I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
I Sincerely, 1stopher J. Schwarz Site Vice President Sequoyah Nuclear Plant Enclosures cc (Enclosures):
- Chattanooga Environmental Field Office Division of Water Pollution Control State Office Building, Suite 550
- 540 Mccallie Avenue Chattanooga, Tennessee 37402-2013 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
TV A Sequoyah Nuclear Plant NPDES Permit.Number TN0026450 Turbine Building Sump Monitoring Data The turbine building sump was discharged directly to the yard drainage pond from 3/15/2016 to 3/31/2016. During this period, the turbine building sump was monitored in accordance with the narrative condition found in Part l.A.2 of the NPDES Permit TN0026450. There are no permit limits applicable at this monitoring point, which flows to the yard drainage pond, mixes with other flows in the diffuser pond, then discharges to the Tennessee River at Outfall 101.
Parameter Daily Minimum Monthly Avera2e Daily Maximum No. of Samples Flow 1.48 MGD l.52MGD 17 pH 8.40 s.u.
8.55 s.u.
2 O&G
<5.0mg/L
<5.0 mg/L 2
<5.0mg/L
<5.0mg/L 2
TV A Sequoyah Nuclear Plant
- NPDES Permit Number TN0026450 Neutral Waste Sump Monitoring Data The neutral waste sump was discharged directly to the yard drainage pond from 3/17/2016 to 3/31/2016. During this period, the neutral waste sump was monitored in accordance with the narrative condition found in Part l.A.2 of the NP DES Permit TN0026450. There are no permit limits applicable at this monitoring point, which flows to the yard drainage pond, mixes with other flows in the diffuser pond, then discharges to the Tennessee River at Outfall 101.
Parameter Daily Minimum Monthly Averae;e Daily Maximum No. of Samples Flow 0.127MGD 0.157MGD 15 pH 7.87 s.u.
7.93 s.u.
2 O&G
<5.0mg/L
<5.0 mg/L 2
<2.5 mg/L
<2.5 mg/L 2
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~-~~-SEQUO~~UCLEARPLANT ___ _
Addres_L _E.Q....BOX 2000 ___________ _
___... !INTEROFFICE Q.E.S-5N-SQNl _______ _
_ _ _ _§ODDY-DAISYJij7384_ _______ _
Fa~-~A-SEQUQYAHNUCLEARP~NC ____ _
Location_....!:!AMIL TOJi.COUNTY_ _________ _
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
DISCHARGE MONITORING REPORT (DMR)
TN0026450 101 G PERMIT NUMBER DISCHARGE NUMBER MAJOR (SUBR 01)
F-FINAL DIFFUSER DISCHARGE EFFLUENT Form Approved.
OMB No. 2040-0004 MO DAY I YEAR MO ATIN:Millicent Garland From! 16 I 03 I 01 I To I 16 I 03 DAY 31
- NO DISCHARGE D PARAMETER TEMPERATURE, WATER DEG.
CENTIGRADE 00010 1
0 EFFLUENT GROSS TEMPERATURE, WATER DEG.
CENTIGRADE 00010 z
0 INSTREAM MONITORING TEMP. DIFF. BETWEEN SAMP. &
UPSTRM DEG.C 00016 EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS VALUE CHLORINE, TOTAL RESIDUAL 50060 1
0 EFFLUENT GROSS VALUE TEMPERATURE* C, RATE OF CHANGE 82234 0
EFFLUENT GROSS NOTE: Read instructions before complelin~ this form.
EX OF TYPE QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE
~~A=V=E=RA=G=E~--.~-M=AX-IM=U=M=---.-U-N=IT=s~*""'-M~IN=IM=U-M~-~-A-V=E=RA=G=-E-=...--MAX--IM=U=M-_,,,,,_U=N=IT=S~
ANALYSIS SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT
- *:. ~'l:>ERMit *:
. REQWIREr.'IE!fF SAMPLE MEASUREMENT
. *;PERM1r:* *
.. REQUiR~ME~T *:
SAMPLE MEASUREMENT
.* PEJ31v11T..
REQUIREMENT
. ~. _,.,*
SAMPLE MEASUREMENT
- ,PERMIT
. REQUIR~MENT 1761 Reqii\\ilon;
- M~fAvs*
11'11 0.3 2;0 DAILY.MX 03 MGD 03 MGD 62 DEG C/HR 04 0
31/31 RCORDR 29.4 DEG.C.
17.8 04 0
31 / 31 MODELO DEG.C.
~*".****~~*:-:**.~ <, /.;f~*.~~*~~*, '; :.
~~: :.,.c.\\~9*~.;, ' ~J.
,:,, *..:,- DAILY;MX.
3.7 04 0
31/31 CALCTD DEG.C.
0 31 / 31 RCORDR
<'.¢ONJI' 'RC6ReR;
- t-1~p1:1$**.
. ; *.i. '*******" : .:". : '",**"!**.~*"':
03 0
31 / 31 CALCTD MGD GRAB 13 / 31 0.022 0.016 19 0
. p.1.
, 0~1 MG/L
... MO.'AVG * *. *. DAILY MAx
.:;.FIVE PER: CALC:to:
.*WEl;:K 0
31/31 CALCTD
- . CON:tl. CAlClJ>.*
- Nuous.
- NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my
~~~--
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the Site Vic~
person or persons who manage the system, or those persons directly responsible for.gathering 423 843-7001 16 04 06 Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECUTIVE I
information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA I NUMBER YEAR MO DAY TYPED OR PRINTED CODE COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference all attachments here)
No closed mode operation. The following injections occurred: Floguard MS6236 (max calc. was 0.03 mg/L, limit 0.20 mg/L, Spectrus BD1500 (max calc. was 0.016 mg/L, limit 2.0 mg/L).
Prf#Vi~ ~sJ.itigns mav be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~ __
NA-SEQUO~~UCLEARPLANT ___ _
AddreS.L _..E.Q,_BOX 2000 -
___ __(!NTEROFFICE OPS-5N-SQNl _______ _
___ _§ODDY-DAISUij73BL _______ _
Fa~
_IVA-SEQUO~HNUCLEARPLANL ____ _
Locati~.J:!AMl~~COUNTY_ _________ _
ATIN:Millicent Garland NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPOES)
DISCHARGE MONITORING REPORT (DMRJ TN0026450 From I
101 T I
I DISCHARGE NUMBER I MAJOR (SUBR 01)
F-FINAL Form Approved.
OMB No. 2040-0004 BIOMONITORING FOR OUTFALL 101 EFFLUENT
- NO DISCHARGE D NOTE: Read instructions before completinQ this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE F====A~V~E~RA~G~E=~r===M~AX=IM~U~M=~=U~N~IT~S=+-=M~l~N~IM~U~M==~=A~V~E~RA~G=E='""F=~MAX=~IM~U~M=~=U~N~IT~S~
ANALYSIS IC25 STATRE 7DAY CHR CERIODAPHNIA Monitoring Not Re uired TRP38 1
0 EFFLUENT GROSS IC25 STATRE 7DAY CHR PIMEPHALES TRP6C 0
EFFLUENT GROSS NAME/TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penally of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, Site Vice President accurate, and complete. I am aware that there are*significant penalties for submitting false information, including the possibility of fine and Imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here)
Toxicity was not sampled in March 2016.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used
~L--
Vice~:s1ue~t SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR AUTHORIZED AGENT 23
~* ;;
TELEPHONE DATE 423 843-7001 16 04 06 I
AREA I NUMBER YEAR MO DAY CODE Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~ __
NA-SEQUO~~UCLEARPLANT ___ _
Addres,L _f.Q....BOX 2000 ___________ _
___.J!.NTEROFFICE OPS-5N-SQ.lil _______ _
_§.ODDY-MISYJ.~738L _______ _
Facjfily_ JYA-_fil:QUOYAH NUCLEAR PLANT_ -
LocaliO.!L _tlAMIL TOJi_COUNTX.... -
ATTN:Millicent Garland NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES}
DISCHARGE MONITORING REPORT (DMR}
TN0026450 103 G PERMIT NUMBER DISCHARGE NUMBER I YEAR I Fromi 16 I MO DA I I
I MO 03 I 01 I To I 16 I 03 DAY 31 MAJOR (SUBR 01)
F-FINAL Form Approved.
OMB No. 2040-0004 LOW VOL. WASTE TREATMENT POND EFFLUENT
- NO DISCHARGE. D NOTE: Read instructions before complelini:i this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE EX OF TYPE F=A-V_E_RA_G_E=~==M-AX=IM_U_M=.,..,,,=U-N-IT-S=+-=M=IN-IM_U_M==y-'=A-V_E_RA_G=E=""'j""'=-MAX=-IM_U_M=.,..,,,=U-N-IT-S-=-=t ANALYSIS PH 00400 0
EFFLUENT GROSS SOLIDS, TOTAL SUSPENDED 00556 0
EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE 1 099 MEASUREMENT SAMPLE MEASUREMENT
. :*:PERMIT-'. \\i :;
.* *. REQUIREMENT...
c * *
~*
SAMPLE MEASUREMENT
- . '*PERivllfc,-*.* *,.
- ,)~E_OUl~EMl:NT *
~
SAMPLE MEASUREMENT 1.274
'-r' 7.4 03 MGD NAME/TITLE PRINCIPAL EXECUTIVE OFFICER Christopher J. Schwarz I Certify under penally of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false Site Vice President 1-----------------1information, including the possibility of fine and imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXPLANATION OF ANY VIOLATIONS (Reference all attachments here) 7.9 12 0
3 / 31 GRAB SU 13.8 13.8 19 0
1/31 GRAB MG/L 19 0
1 / 31 GRAB MG/L 4 / 31 INST AN 0
i < *o.*,* *y*,*
... 1*
TELEPHONE DATE 423 843-7001 16 04 06 AREA NUMBER YEAR MO DAY CODE The Turbine Building Sump (TBS) was discharged directly to the Yard Pond (YP) on March 15 - March 31, 2016. The neutral waste sump also was aligned to the Yard Pond March 17 - 31, 2016.
EPA Form 3320-1 (REV 3/99)
Previous editions may be used Page 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different}
Na~ _
_!VA-SEQUO~~UCLEARPLANT ___ _
Addres,L _E.Q._BOX 2000 ___________ _
___.J!.NTEROFFICE OPS-5N-SQNl _______ _
___§ODDY-MISYJ_~738L _______ _
~~-~A-SE~O~HNUCLEARP~NC ____ _
Locatio.n_.J::!AMILTOJ:LCOUNTY_ _________ _
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDESJ DISCHARGE MONITORING REPORT (DMRJ TN0026450 110 G PERMIT NUMBER DISCHARGE NUMBER MAJOR (SUBR 01)
F-FINAL RECYCLED COOLING WATER EFFLUENT Form Approved.
OMB No. 2040-0004 ATTN:Millicent Garland I.
¥0NITORING PERIOD
- NO DISCHARGE ~...
PARAMETER TEMPERATURE, WATER DEG.
CENTIGRADE 00010 0
EFFLUENT GROSS VALUE TEMPERATURE, WATER DEG.
CENTIGRADE 00010 z
0 INSTREAM MONITORING TEMP. DIFF. BETWEEN SAMP. &
UPSTRM DEG.C 00016 1
0 EFFLUENT GROSS VALUE FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 0
EFFLUENT GROSS VALUE CHLORINE, TOTAL RESIDUAL 50060 0
EFFLUENT GROSS VALUE TEMPERATURE - C, RATE OF CHANGE 82234 1
0 EFFLUENT GROSS VALUE NOTE: Read instructions before completin!I this form.
EX OF TYPE Ix QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE F=--A-V_E_RA_G_E=""'"'"9r-=M-AX=IM_U_M==-=r-U-N-IT-S=*"""'=M-l-N-IM-U-M==~=A-V-E-RA-G=E=..,..=-MAX=-IM-U-M=.....,=U-N-IT-S-ANALYSIS SAMPLE MEASUREMENT SAMPLE MEASUREMENT SAMPLE MEASUREMENT i~~"~l,~'.""*...:,
~'. ***"*"~~'!..,.
- \\.. ::'>>:.:***
. ?PERMIT.. :. ' '.. :.. "'*******
'REO~fR~M*':,N~*. *.* >.~*\\'.
- SAMPLE MEASUREMENT
- .:*:* 'PERM1t
. ~J:qUlRf:MENT.
SAMPLE MEASUREMENT
- *PERMIT* * - *
- ;REQUiREfqENT
~
SAMPLE MEASUREMENT
- ~*f**** :. '::,
- Reqr:rillc),1,., **
- o:AIL:.Y-MX.*
-.Y.*
03 MGD 04
.. *J?°ERMIT, :
REQUiR~rvii:tfr 2'
DEG C SAMPLE MEASUREMENT
- PERMIT.
'.REQUIREMENT*
DAILYMX*
- "'~**-~~** ;; ". 'REPOR:t:**
,, ', '., *.. DAILY MX 30*5 '.. ~**.*
- '*~: : * '* ;.... :.. *,DAll'Y*ivlx'.'*
. ** : :. 5:. '
- -~:~-.*DAILY 'MX' *
,.., '(f1 0"1
- * * ;rilf:© Av(;. * ;. * -DAILY MX
- 04 DEGC 04 DEGC 04 DEGC 19 MG/L CONJ:IN' CALCTD',
)Jolls....
'. ' ' i corlltu;i,; *'RCORDR
- * * ~*uous*.. :. *
- : :*Five per: 'CA~Ci;~*
- .. ; \\1\\1~01<',.,.,.
,CONTIN.CALCTD :
-U0US. _
NAMEITITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of Jaw that this document and all attachments were prepared under my
/4£J~-
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference all attachments here}
No Discharge this Period EPA Form 3320-1 (REV 3/99)
Previous editions may be used
~
SiteVi~~nt SIGNATURE OF PRINClPArtXECUTIVE OFFICER OR AUTHORIZED AGENT 423 843-7001 16 04 06 I
AREA I NUMBER YEAR MO DAY CODE Page 1 of 1
PERMITIEE NAME/ADDRESS (Include Facility Name/Location if Different)
Name _
_!VA-SEQUO~~UCLEARPLANT ___ _
Addres§_.£.Q...BOX 2000 ___________ _
___ _[NTEROFFICE OPS-SN-SQ.ti) _______ _
___ _§ODDY-MISY._Iij73BL _______ _
Fa~-~A-SEQUOYAHNUCLEARP~NC ____ _
LocaliO.!L.JjAMIL TOJi.COUNTX_ -
ATIN:Millicent Garland NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
DISCHARGE MONITORING REPORT (DMR)
TN0026450 I
110 T I
I DISCHARGE NUMBER I MAJOR (SUBR 01)
F *FINAL RECYCLED COOLING WATER EFFLUENT
- NO DISCHARGE. I xx I ***
Form Approved.
OMB No. 2040-0004 NOTE: Read instructions before completin~ this form.
PARAMETER QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE AVERAGE MAXIMUM UNITS MINIMUM AVERAGE MAXIMUM IC25 STATRE 7DAY CHR CERIODAPHNIA TRP38 1
0 0
EFFLUENT GROSS VALUE IC25 STATRE 7DAY CHR PIMEPHALES TRP6C 1
0 0
EFFLUENT GROSS VALUE SAMPLE MEASUREMENT
,~
'. {,
NAME!TITLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. ram aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
TYPED OR PRINTED COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference all attachments here)
No Discharge this Period EPA Form 3320-1 (REV 3199)
Previous editions may be used
'\\,,
~/\\..C£_
c;
~-ite Vice P.[:6si ny SIGNATURE OF PRINCIPAL EXECUTIVE OFFICER OR AUTHORIZED AGENT EX OF TYPE UNITS ANALYSIS 23
/servik:~ *col\\11i?os;
'*~~~~~t} :;~j;;;~;~ii'f;*;\\)
TELEPHONE DATE 423 843-7001 16 04 06 I
AREA I NUMBER YEAR MO DAY CODE Paqe 1 of 1
PERMITTEE NAME/ADDRESS (Include Facility Name/Location if Different)
Na~ _
_!VA-SEQUO~~UCLEARPLANT ___ _
Addres,L _E'..Q..BOX 2000 ___________ _
___.J!.NTEROFFICE OPS-5N-SQ~.l- ______ _
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES}
DISCHARGE MONITORING REPORT (DMR)
TN0026450
- 110 G MAJOR (SUBR 01)
F-FINAL Form Approved.
OMB No. 2040-0004
---~ODDY-DAISYJ.ij73BL _______ _
PERMIT NUMBER Fac.]!i!y _
_IVA-SEQUO~HNUCLEARP~NL ____ _
Locatio.n_..!!AMIL TO.Ji.COUNTY_ _________ _
DISCHARGE NUMBER WASTEWATER & STORM WATER EFFLUENT ATTN:Millicent Garland PARAMETER OXYGEN, DISSOLVED (DO) 00300 0
EFFLUENT GROSS SOLIDS, TOTAL SUSPENDED 00530 0
EFFLUENT GROSS SOLIDS, SETTLEABLE 00545 0
EFFLUENT GROSS FLOW, IN CONDUIT OR THRU TREATMENT PLANT 50050 1
0 EFFLUENT GROSS NO DISCHARGE ~...
From I 16 I 03 I 01 To I 16 03 31 NOTE: Read instructions before comple!inr:i this form.
EX OF TYPE I><
QUANTITY OR LOADING QUALITY OR CONCENTRATION NO.
FREQUENCY SAMPLE F="'~A-V-ERA-.-G-E-===M-N<=IM_U_M===U-N_IT_S={-=-M-1-N-IM_U_M==,...,.=A-V_E_RA_G=E=....-==~MN<=-IM_U_M=~=U-N-l-TS--=i ANALYSIS SAMPLE MEASUREMENT
.*. *.~RERMit '.>~ ;:**
- .REGllJiREMENt
- .
SAMPLE MEASUREMENT SAMPLE MEASUREMENT
- . uli,1ti..*"* '* ', *
. *.*li~if*tili \\. '-
- **,l
.' ~ ~'..:: : ': '
'" **'*"'!'..~***.,,.. '**:*~*-**....100.
,,.;~.
- .. *~" **.* * * * *...
- ... :" 'DAILY;M)C:
SAMPLE MEASUREMENT 03
. REJ°j~~~ENT: ::.R~C.?~on:,
'R~qtMO.n;:
MGD <'*... ti**-*"'-**"
i;.. :M04W.G*. '*. bAIL¥Mi
- SAMPLE MEASUREMENT
- RERMl'f,,
- REQLlii;tEME;NT
- SAMPLE MEASUREMENT
-PERMIT REQU(R.EMENT -
SAMPLE MEASUREMENT
- PERMIT:
,,~~q~iREMENJ**. *
- c.
~* '
- 19 MG/L 19 MG/L 25 MUL
. '. mMci:I.... GMEf
.*',wEl:I(' ***.... *.. *.
. : :r:w1ci::1.*: ; GRA~, *
"\\
1C
- :~w~.I;~.* .::*~:.. **,-. *:, ~.
' * ; ~NCE/ j:Sf:IMA*: *
- BATCH:... *:_ :,. ~-.**.
NAMEfflTLE PRINCIPAL EXECUTIVE OFFICER I Certify under penalty of Jaw that this document and all attachments were prepared under my
?7,.((/?/ -
TELEPHONE DATE direction or supervision in accordance with a system designed to assure that qualified Christopher J. Schwarz personnel properly gather and evaluate the information submilted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering ~ --......_
Site Vice President the information, the information submitted is, to the best of my knowledge and belief, true, te Vice Pr~elem ""
423 843-7001 16 04 06 accurate, and complete. I am aware that there are significant penalties for submitting false SIGNATURE OF PRINCIPAL EXECtJTIVE I
information, including the possibility of fine and imprisonment for knowing violations.
OFFICER OR AUTHORIZED AGENT AREA I NUMBER YEAR MO DAY TYPED OR PRINTED CODE COMMENTS AND EXP~NATION OF ANY VIO~TIONS (Reference at/ attachments here)
During this reporting period, there has been no flow from the Dredge Pond other than that resulting from rainfall. No Discharge this Period EPA Form 3320-1 (REV 3/99)
Previous editions may be used PaQe 1 of 1