DCL-16-013, Response to NRC Request for Additional Information Regarding Relief Request NDE-FWNS-U1/U2
| ML16027A358 | |
| Person / Time | |
|---|---|
| Site: | Diablo Canyon |
| Issue date: | 01/27/2016 |
| From: | Welsch J Pacific Gas & Electric Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| DCL-16-013, NDE-FWNS-U1/U2 | |
| Download: ML16027A358 (4) | |
Text
Pacific Gas and Electric Company January 27, 2016 PG&E Letter DCL-16-013 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Docket No. 50-275, OL-DPR-80 Docket No. 50-323, OL-DPR-82 Diablo Canyon Power Plant Unit 1 and Unit 2 James M. Welsch Vice President, Nuclear Generation 10 CFR 50.55a Response to NRC Request for Additional Information Regarding Relief Request NDE-FWNS-U1/U2
References:
- 1.
PG&E Letter DCL-15-1 06, "ASME Section Xllnservice Inspection Program Request for Relief NDE-FWNS-U 1 /U2 to Allow Use of Alternate Examination Volume Coverage Requirements," dated September 3, 2015 (ML15246A244)
Diablo Canyon Power Plant P.O. Box 56 Avila Beach, CA 93424 805.545.3242 E-Mail: JMWl @pge.com
- 2.
E-mail communication from NRC, "Diablo Canyon 1 and 2 - RAis for RR NDE-FWNS-U1/U2 to Allow Use of Feedwater Nozzle-to-Vessel Welds Alternate Examination Volume Coverage Requirements," dated December 15, 2015 (ML15350A039)
Dear Commissioners and Staff:
In Reference 1, Pacific Gas and Electric Company (PG&E) submitted relief request NDE-FWNS-U1/U2 for the Diablo Canyon Power Plant Units 1 and 2 third inservice inspection interval for NRC approval. In Reference 2, the NRC Staff provided a request for additional information (RAI) via an e-mail dated December 15, 2015.
The Enclosure to this letter provides PG&E's responses to the RAI questions.
This communication does not contain any new or revised regulatory commitments (as defined by NEI 99-04). If you have any questions or require additional information, please contact Mr. Hossein Hamzehee at (805) 545-4720.
Sincerely,
~/Yl~
James M. Welsch A
member of the STARS (Strategic Teaming and Resource Sharing)
Alliance Callaway
- Diablo Canyon
- Palo Verde
- Wolf Creek
Document Control Desk January 27, 2016 Page 2 rntt/4231/50033145 Enclosure cc:
Diablo Distribution cc/enc:
Marc L. Dapas, NRC Region IV Administrator Siva P. Lingam, NRC Project Manager PG&E Letter DCL-16-013 Gonzalo L. Perez, Branch Chief, California Department of Public Health Binesh K. Tharakan, Acting NRC Senior Resident Inspector State of California, Pressure Vessel Unit A
member of the STARS (Strategic Teaming and Resource Sharing)
Alliance Callaway
- Diablo Canyon
- Palo Verde
- Wolf Creek
Enclosure PG&E Letter DCL-16-013 PG&E Response to NRC Request for Additional Information Regarding Relief Request NDE-FWNS-U1/U2 NRC Question {a):
Identify whether the surface examinations required by ASME Code,Section XI, Table IWC-2500-1, Code Category C-8, Item Number C2.21 were performed for the SG feedwater nozzle-to-she// welds.
PG&E Response:
The surface examinations required by ASME Code,Section XI Table IWC-2500-1, Code Category C-8, Item Number C2.21 were performed for the SG feedwater nozzle-to-shell welds. 100 percent coverage was achieved.
NRC Question {b):
Provide a summary of the results for any surface examinations performed for the steam generator (SG) feedwater nozzle-to-shell welds.
PG&E Response:
The surface examinations did not detect any relevant indications. No defects were noted.
NRC Question {c):
Identify whether relief is also being requested from any of the applicable ASME Code,Section XI surface examination requirements for the SG feedwater nozzle-to-she//
PG&E Response:
The surface examinations were completed satisfactorily with 100 percent coverage.
Hence, Pacific Gas and Electric Company is not requesting relief from the surface examination requirements of the applicable ASME Code section for these nozzles.
NRC Question {d):
Describe the impact of any surface examinations performed for the SG feedwater nozzle-to-she// welds on the burden and bases assessments included in the relief request.
PG&E Response:
The magnetic particle examination is sensitive to defects that initiate on or propagate to the outside surface of the weld and adjoining examination area. This examination was 1
Enclosure PG&E Letter DC L 013 conducted using the ASME Code compliant procedure by qualified examiners and provides assurance that no surface breaking flaws exist on these nozzle welds. Hence, it has no impact on the compliance burden, and it has an ameliorating effect on the basis aspects (that were included in the relief request) due to the added confidence that no structural flaws exist.
2
Pacific Gas and Electric Company January 27, 2016 PG&E Letter DCL-16-013 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Docket No. 50-275, OL-DPR-80 Docket No. 50-323, OL-DPR-82 Diablo Canyon Power Plant Unit 1 and Unit 2 James M. Welsch Vice President, Nuclear Generation 10 CFR 50.55a Response to NRC Request for Additional Information Regarding Relief Request NDE-FWNS-U1/U2
References:
- 1.
PG&E Letter DCL-15-1 06, "ASME Section Xllnservice Inspection Program Request for Relief NDE-FWNS-U 1 /U2 to Allow Use of Alternate Examination Volume Coverage Requirements," dated September 3, 2015 (ML15246A244)
Diablo Canyon Power Plant P.O. Box 56 Avila Beach, CA 93424 805.545.3242 E-Mail: JMWl @pge.com
- 2.
E-mail communication from NRC, "Diablo Canyon 1 and 2 - RAis for RR NDE-FWNS-U1/U2 to Allow Use of Feedwater Nozzle-to-Vessel Welds Alternate Examination Volume Coverage Requirements," dated December 15, 2015 (ML15350A039)
Dear Commissioners and Staff:
In Reference 1, Pacific Gas and Electric Company (PG&E) submitted relief request NDE-FWNS-U1/U2 for the Diablo Canyon Power Plant Units 1 and 2 third inservice inspection interval for NRC approval. In Reference 2, the NRC Staff provided a request for additional information (RAI) via an e-mail dated December 15, 2015.
The Enclosure to this letter provides PG&E's responses to the RAI questions.
This communication does not contain any new or revised regulatory commitments (as defined by NEI 99-04). If you have any questions or require additional information, please contact Mr. Hossein Hamzehee at (805) 545-4720.
Sincerely,
~/Yl~
James M. Welsch A
member of the STARS (Strategic Teaming and Resource Sharing)
Alliance Callaway
- Diablo Canyon
- Palo Verde
- Wolf Creek
Document Control Desk January 27, 2016 Page 2 rntt/4231/50033145 Enclosure cc:
Diablo Distribution cc/enc:
Marc L. Dapas, NRC Region IV Administrator Siva P. Lingam, NRC Project Manager PG&E Letter DCL-16-013 Gonzalo L. Perez, Branch Chief, California Department of Public Health Binesh K. Tharakan, Acting NRC Senior Resident Inspector State of California, Pressure Vessel Unit A
member of the STARS (Strategic Teaming and Resource Sharing)
Alliance Callaway
- Diablo Canyon
- Palo Verde
- Wolf Creek
Enclosure PG&E Letter DCL-16-013 PG&E Response to NRC Request for Additional Information Regarding Relief Request NDE-FWNS-U1/U2 NRC Question {a):
Identify whether the surface examinations required by ASME Code,Section XI, Table IWC-2500-1, Code Category C-8, Item Number C2.21 were performed for the SG feedwater nozzle-to-she// welds.
PG&E Response:
The surface examinations required by ASME Code,Section XI Table IWC-2500-1, Code Category C-8, Item Number C2.21 were performed for the SG feedwater nozzle-to-shell welds. 100 percent coverage was achieved.
NRC Question {b):
Provide a summary of the results for any surface examinations performed for the steam generator (SG) feedwater nozzle-to-shell welds.
PG&E Response:
The surface examinations did not detect any relevant indications. No defects were noted.
NRC Question {c):
Identify whether relief is also being requested from any of the applicable ASME Code,Section XI surface examination requirements for the SG feedwater nozzle-to-she//
PG&E Response:
The surface examinations were completed satisfactorily with 100 percent coverage.
Hence, Pacific Gas and Electric Company is not requesting relief from the surface examination requirements of the applicable ASME Code section for these nozzles.
NRC Question {d):
Describe the impact of any surface examinations performed for the SG feedwater nozzle-to-she// welds on the burden and bases assessments included in the relief request.
PG&E Response:
The magnetic particle examination is sensitive to defects that initiate on or propagate to the outside surface of the weld and adjoining examination area. This examination was 1
Enclosure PG&E Letter DC L 013 conducted using the ASME Code compliant procedure by qualified examiners and provides assurance that no surface breaking flaws exist on these nozzle welds. Hence, it has no impact on the compliance burden, and it has an ameliorating effect on the basis aspects (that were included in the relief request) due to the added confidence that no structural flaws exist.
2