Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 January 19, 2016 State of Tennessee Department of Environment and Conservation Division of Water Pollution Control Enforcement & Compliance Section 6th Floor, L & C Annex 401 Church Street Nashville, Tennessee 37243-1534

Dear Mr. Patrick Cromer:

TENNESSEE VALLEY AUTHORITY (TIVA) - SEQUOYAH NUCLEAR PLANT (SON) - NPDES PERMIT NO. TN0026450 - 2015 BIOCIDEICORROSION TREATMENT PLAN (BICTP) ANNUAL REPORT Enclosed is a copy of the 2015 B/CTP annual report for SON. Biodetergent 73551 was not added during CY 2015. All other treatments were conducted in accordance with the approved B/CTP.

If you have any questions or need additional information, please contact Millicent Garland at (423) 843-6714 or by e-mail at mrmoore@tva.gov of Sequoyah's Environmental staff.

I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the in formation, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. /

am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.

Sincerely, Site Vice President Sequoyah Nuclear Plant Enclosures cc (Enclosures):

Mr. Vojin Janjik Chattanooga Environmental Field Office State of.Tennessee Division of Water Pollution Control Dept. of Environment and Conservation State Office Building, Suite 550 Division of Water Pollution Control 540 McCallie Avenue 6th Floor, L & C Annex Chattanooga, Tennessee 37402-2013 401 Church Street Nashville, Tennessee 37243-1534 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk

/

Washington, D.C. 20555_

TN0026450SN SQN 2015 Biocide/Corrosion Treatment Plan Annual Report Towerbrom 960 Duration Quantity in Pounds in Hours Analytical Results (lbs/day)

(hrs/day) mass balance calculation (mg/L)

  1. of Month Maximum Average Limit Maximum Maximum Average Limit samples Days in Service (based on days in

~service)________

January 200 200 1425 12.00 0.047 0.031 0.10 10 10 February 200 88 1425 12.00 0.043 0.017 0.10 8

8 March 200 105 1425 4.00 0.033 0.020 0.10 10 10 April 225 188 1425 4.00 0.046 0.024 0.10 18 15 May 700 493 1425 23.98 0.033 0.026 0.10 21 20 June 650 291 1425 23.98 0.036 0.019 0.10 25 23 July 300 180 1425 4.00 0.035 0.021 0.10 23 23 August 200 176 1425 4.00 0.028 0.018 0.10 23 23 September 200 145 1425 6.50 0.038 0.017 0.10 22 22 October 800 498 1425 23.98 0.041 0.020 0.10 26 26 November 800 347 1425 23.98 0.032 0.022 0.10 19 19 December 200 192 1425 4.00 0.027 0.020 0.10 15 12 Jan. - Dec.

220 211 Per the B/CTP approval: "Whole Effluent toxicity testing (biomonitoring) of Outfall1101 and Outall 110 shall be undertaken once per year when oxidizing biocides are being used."

Outfall1101: Toxicity was sampled October 18 - 23, 2015.

Test Results: Pimephales promelas: IC25 >100%

Ceriodaphnia dubia: lC25 > 100%

Outfall 110: There has been no discharge from Outfall 110 January - December 2015.

TN0026450 SQN 2015 Biocide/Corrosion Treatment Pian Annual Report Flogard MS6236 Duration Quantity in Pounds in Hours Analytical Results (lbs/day)

(hrs/day) mass balance calculations (rag/L)

  1. of Days in Month Maximum Averagle Limit Maximum Maximum Average Limit samples Service January 418 311 2275 24.00 0.030 0.030 0.2 23 23 February 418 293 2275 24.00 0.032 0.030 0.2
  • "19 19 March 418 329 2275 24.00 0.030 0.030 0.2 22 22 April 418 261 2275 24.00 0.030 0.030 0.2 22 22 May 418 282 2275 24.00 0.050 0.034 0.2 11 11 June 278 196 2275 16.00 0.030 0.030 0.2 8

8 July 574 299 2275 24.00 0.040 0.032 0.2 23 23 August 1160 791 2275 20.00 0.030 0.030 0.2 19 "19 September 418 276 2275 24.00 0.030 0.030 0.2 22 22 October 331 261

-* 2275 19.00 0.030 0.030 0.2 2

2 November 418 292 2275 24.00 0.050 0.036 0.2 17 17 December 418 283 2275 24.00 0.050 0.035 0.2 20 20 Jan. - Dec.

208 208 Per the B/CTP approval: "Flogard MS6236 is injected into the RCW system continuously, except during periods of other chemical injection due to common injection lines. Flogard MS6236 is injected into the ERCW Train A &

B system intermittently."

TN0026450 Q

SQN Spectrus CT1 300 Quantity in Pounds (lbs/day)

Duration in Hours (hrs/day)

Maximum Analyticai Results mass balance calculations (mgIL)

Month Maximum -Averaae Limit MaxmumAveaa

  1. of Samples Days in Service Limit 4

1

.1.

L January February March April May June July August September October November December Jan. - Dec.

483 483 483 483 221 301 325 302 325 196 855 855 855 855 855 24.00 24.00 24.00 24.00 11.00 0.030 0.030 0.030 0.030 0.030 0.029 0.030 0.030 0.030 0.030 0.05 0.05 0.05 0.05 0.05 7

3 5

6 4

7 3

5 6

4 25 25 Per the B/CTP approval: "Whole Effluent toxicity testing (biomonitoring) of Outfall 101 and Outall 110 shall be undertaken once per year when non-oxidizing biocides are being used."

Outfall 101: Toxicity was sampled August 9 - 14, 2015, during the Spectrus CT1300 treatment.

Test Results: Pimepha/es promelas: 1C25 >100%

Ceriodaphnia dubia: 1025 > 100%

Outfall 110: There has been no discharge from Outfall 110 January *- December 2015.

Tennessee Valley Authority, Post Office Box 2000, Soddy Daisy, Tennessee 37384-2000 January 19, 2016 State of Tennessee Department of Environment and Conservation Division of Water Pollution Control Enforcement & Compliance Section 6th Floor, L & C Annex 401 Church Street Nashville, Tennessee 37243-1534

Dear Mr. Patrick Cromer:

TENNESSEE VALLEY AUTHORITY (TIVA) - SEQUOYAH NUCLEAR PLANT (SON) - NPDES PERMIT NO. TN0026450 - 2015 BIOCIDEICORROSION TREATMENT PLAN (BICTP) ANNUAL REPORT Enclosed is a copy of the 2015 B/CTP annual report for SON. Biodetergent 73551 was not added during CY 2015. All other treatments were conducted in accordance with the approved B/CTP.

If you have any questions or need additional information, please contact Millicent Garland at (423) 843-6714 or by e-mail at mrmoore@tva.gov of Sequoyah's Environmental staff.

I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the in formation, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. /

am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.

Sincerely, Site Vice President Sequoyah Nuclear Plant Enclosures cc (Enclosures):

Mr. Vojin Janjik Chattanooga Environmental Field Office State of.Tennessee Division of Water Pollution Control Dept. of Environment and Conservation State Office Building, Suite 550 Division of Water Pollution Control 540 McCallie Avenue 6th Floor, L & C Annex Chattanooga, Tennessee 37402-2013 401 Church Street Nashville, Tennessee 37243-1534 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk

/

Washington, D.C. 20555_

TN0026450SN SQN 2015 Biocide/Corrosion Treatment Plan Annual Report Towerbrom 960 Duration Quantity in Pounds in Hours Analytical Results (lbs/day)

(hrs/day) mass balance calculation (mg/L)

  1. of Month Maximum Average Limit Maximum Maximum Average Limit samples Days in Service (based on days in

~service)________

January 200 200 1425 12.00 0.047 0.031 0.10 10 10 February 200 88 1425 12.00 0.043 0.017 0.10 8

8 March 200 105 1425 4.00 0.033 0.020 0.10 10 10 April 225 188 1425 4.00 0.046 0.024 0.10 18 15 May 700 493 1425 23.98 0.033 0.026 0.10 21 20 June 650 291 1425 23.98 0.036 0.019 0.10 25 23 July 300 180 1425 4.00 0.035 0.021 0.10 23 23 August 200 176 1425 4.00 0.028 0.018 0.10 23 23 September 200 145 1425 6.50 0.038 0.017 0.10 22 22 October 800 498 1425 23.98 0.041 0.020 0.10 26 26 November 800 347 1425 23.98 0.032 0.022 0.10 19 19 December 200 192 1425 4.00 0.027 0.020 0.10 15 12 Jan. - Dec.

220 211 Per the B/CTP approval: "Whole Effluent toxicity testing (biomonitoring) of Outfall1101 and Outall 110 shall be undertaken once per year when oxidizing biocides are being used."

Outfall1101: Toxicity was sampled October 18 - 23, 2015.

Test Results: Pimephales promelas: IC25 >100%

Ceriodaphnia dubia: lC25 > 100%

Outfall 110: There has been no discharge from Outfall 110 January - December 2015.

TN0026450 SQN 2015 Biocide/Corrosion Treatment Pian Annual Report Flogard MS6236 Duration Quantity in Pounds in Hours Analytical Results (lbs/day)

(hrs/day) mass balance calculations (rag/L)

  1. of Days in Month Maximum Averagle Limit Maximum Maximum Average Limit samples Service January 418 311 2275 24.00 0.030 0.030 0.2 23 23 February 418 293 2275 24.00 0.032 0.030 0.2
  • "19 19 March 418 329 2275 24.00 0.030 0.030 0.2 22 22 April 418 261 2275 24.00 0.030 0.030 0.2 22 22 May 418 282 2275 24.00 0.050 0.034 0.2 11 11 June 278 196 2275 16.00 0.030 0.030 0.2 8

8 July 574 299 2275 24.00 0.040 0.032 0.2 23 23 August 1160 791 2275 20.00 0.030 0.030 0.2 19 "19 September 418 276 2275 24.00 0.030 0.030 0.2 22 22 October 331 261

-* 2275 19.00 0.030 0.030 0.2 2

2 November 418 292 2275 24.00 0.050 0.036 0.2 17 17 December 418 283 2275 24.00 0.050 0.035 0.2 20 20 Jan. - Dec.

208 208 Per the B/CTP approval: "Flogard MS6236 is injected into the RCW system continuously, except during periods of other chemical injection due to common injection lines. Flogard MS6236 is injected into the ERCW Train A &

B system intermittently."

TN0026450 Q

SQN Spectrus CT1 300 Quantity in Pounds (lbs/day)

Duration in Hours (hrs/day)

Maximum Analyticai Results mass balance calculations (mgIL)

Month Maximum -Averaae Limit MaxmumAveaa

  1. of Samples Days in Service Limit 4

1

.1.

L January February March April May June July August September October November December Jan. - Dec.

483 483 483 483 221 301 325 302 325 196 855 855 855 855 855 24.00 24.00 24.00 24.00 11.00 0.030 0.030 0.030 0.030 0.030 0.029 0.030 0.030 0.030 0.030 0.05 0.05 0.05 0.05 0.05 7

3 5

6 4

7 3

5 6

4 25 25 Per the B/CTP approval: "Whole Effluent toxicity testing (biomonitoring) of Outfall 101 and Outall 110 shall be undertaken once per year when non-oxidizing biocides are being used."

Outfall 101: Toxicity was sampled August 9 - 14, 2015, during the Spectrus CT1300 treatment.

Test Results: Pimepha/es promelas: 1C25 >100%

Ceriodaphnia dubia: 1025 > 100%

Outfall 110: There has been no discharge from Outfall 110 January *- December 2015.