ML15329A276
| ML15329A276 | |
| Person / Time | |
|---|---|
| Site: | Indian Point |
| Issue date: | 04/01/2003 |
| From: | Danson C Entergy Nuclear Operations |
| To: | Atomic Safety and Licensing Board Panel |
| SECY RAS | |
| References | |
| RAS 23735, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01 | |
| Download: ML15329A276 (25) | |
Text
{{#Wiki_filter:RIV000135 Submitted: November 9, 2012 ~ n ergy IPEC Unit# 3 Report No.: 03UT084 Page _1_ of.:J_ r ~ E t Ultrasonic Examination Report Sys. / Comp. 10: Extraction Steam I EX-02.9-02P Exam Item: EX-02.9*02P I Pipe, Elbow, Pipe, Elbow, Pipe DWG No. or Sketch: EC-H-50081 Rev. 2 WR/Mod: IP3*02*24847 QA Category: Non Cat ASME XI Class: N/A Cat: N/A Procedure: NDEP 9.4*12(1) Rev.: 4 Component Configuration: Pipe to Elbow to Pipe to Elbow to Pipe Orientation: 0 Degree Angle: 0 ° Mode: Longitudinal Type of Material: Size: 10" Carbon Steel Thickness: 0.250" Equipment Instrument: 002144201 Panametrics 36DL+ Due: 3/16/2004 Vertical Linearity Check Attenuator Llnearltv Check ~:~~:: ~ 1 ~~x 1 :a 1 £~ 1:1 JK 1 J& 1 aa 1 J& Itt~ 1 J& 1 BOo/N;; db 80% ~~12 db 40*~~~: db I 20% ~,12 db : (Signal 2 shall equal 50% of slgnal1
- 5% of full ~cale.)
(32 to 48) (16 to 24) (64-96) {64*96) Transducer: 502080 Panametrics 5 Mhz 0.312" Round D791/ Dual Element Wedge: N/A Search Unit Cable: 6' Self-Cont. Wedge Meas. Angle: N/A 0 Exit Point-Front: N/A " Couplant: 00245 Sonotech 1 Sono 600 Gel Thermometer: 103284 Due: 3/11/2004 Calibration Block: 102386 Step Wedge T=.1" *.5" Material: Carbon Steel Temperature 75 °F Simulator Block: N/A Reference Block: N/A Entry Surface: OD Component: N/A °F N/A 0f 72 Of Distance Amplitude Curve Each Major Screen Division = 100r=i""""r-f'"""",......,,......r-'f"""".-1"'""'1 Instrument Settings 0.100" 90~+-+-4-~~~-+-+-+~ 80~~~~-+~~~~~+-~1 70 -f---.*--1-__...;,-t*-t-1-1-IHI so 1 -t-~ ' -t-~-t--t--t--+-+-11 I so l~+-~.~~~,-+-+~--~~ Reflector 0.100" I 0.300" i 0.500" I o/o Orient. FSH Step 80 Step 80 Step 80 Calibration Times: Pos. dB 1.0 N/A 3.0 N/A 5.0 N/A 40 1~+-~~~-+-+-4--~~ 30 ~r-r-+-+-i-+-+-+-1-~ 20 ~T-r-+-+-+-+-+-1-4-~ 1or-r-r-+-+-+-+-1-1-1-; o~b-~~~~~~~~ I 1058 1 1145] 1.31o r !4cio] *}¥0] 1 2 3 4 5 6 7 8 9 10 Acceptance Standard: 87.5% of nominal as per AP-49 requirements. Range (ln.): 1.0" Thick Cal: 2-PT Velocity (in./J.Is): 2338 Sensitivity (dB): 56 Scan Sensitivity 80% Frequency (mHz): 5 Reject: Off Filter: Full Pulse Length: Fixed Damping: Fixed Mode Select: Dual Rep. Rate: Fixed DEC/Gate: On Jacks: T/R Recordable lndication(s): Yes Recording Level: N/A% DAC Evaluation Level: N/A o/o DAC 100 %Complete Limitations: None Remarks: Recordable Indications Reference pages 2 & 4 of 7. Examined EX*02.9*02P, EX*02.9-03E, EX-02.9*04P, EX-02.9-0SE, EX-02.9*06P. Examiner: ~ ~ Chrlstooher J. Danson Level: Ill Date: 4/1/2003 Examiner: ~p~~t"'*'*" "'::~*~ Date: 4/1/2003 Reviewed by: Date: 'i I 2..Lo.J t-j.q.. r ANII Review: Date: IPEC00020933 United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of: Entergy Nuclear Operations, Inc. (Indian Point Nuclear Generating Units 2 and 3) ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #: Identified: Admitted: Withdrawn: Rejected: Stricken: Other: RIV000135-00-BD01 11/5/2015 11/5/2015
=o m * () 0 0 0 N 0 <.0 (.,) ~ * =Entergy Sys. I Comp. ID: Extraction Steam I EX-02.9-02P DWG No.: EC-H-50081 rev. 2 Configuration: See drawing below Acceptance Standard: E 0 c B A Q p 0 N M L 1 I 2 I N 3 4 I s 6 Material: Carbon Steel Size: 10" Thickness: 0.250" Datum Point: Outside Radius of Elbow 0.219" EX~l.9~2P 2" Grid Spacing Min: 0.274" Max.: 0A10"' Report No.: Page High Reading :~ Exam Item: Low Reading: 0.145" Grid Size: 2" WRIMod: 2 NDEP 9.4- "'1\\ Rev.4 Aeot 2 . -~101 1 03UT084 of 7 - --Pipe,EI~. Elbow, Pipe IP3-02-24847 QA Category: N00Cat.1 ASME XI Class: N/A Cat:~ Procedure: NDEP 9.4-12 {Q Rev.: OA20"' Ma.~t; o.38r 0!: \\~ r f- - Eti:~~:QZ ~~~\\ '~,LJ=j 7 Low~<<: 8 0.145"' A1/;"' (5 Just off of 011. 9 I 7 10 L' A1 f-' !L@:: ~a~~.o& 11 \\. EX~ 12 Min: 0.284" Looldng IllS MU! 0.447'" 13 Min: Q.281" 14 .-x:o.393"' 15 16 J \\. 17 Remarks: All thickness readings above are In thousandths of c~ ~ an inch. Examiner: 61~ristopher J. Danson Level: _II_L_ Date: 4101/2003 For Min. & Max. Readings reference above Sketch. ~Ei15t'~'w ~'"' Examiner: Level: Ill Date: 4/01/2003 Level:..::1Jb_ '-f/1.-/ o). Reviewed by: Date: ANII Review: ~/4 Date: Method Used: Grid Point Readings REA1.01
-u WlnPius oate.A:kl ~ EX.OZ.9~ g r.Ae~N~~~
- -_-_------~EX~.OZ.~9~~~n.2.---------~
. --------~------r,S~~~~D~~ .~~~.-.. ------~0"-4~~~~~----------------------------~ "-> Fie~~ : 2o Grid-- Erase Protection :
- oN--
g FieD_!!SCI~ :
- 10"ELBOIII Mil.A~
'il-147@011 ~ L~ Note : j EXTRACTiON STEAM - l.fe11. A~ng:
- 0~420 @jfi9 -
l~or ID : . C.J. DANSO~ I C,W. KIEH~ Color Legend
""0 Wi1Pius Da~ ~ EX-02.s& g~A~e~N~~--:--------~ . EX~~~9~~4~P~~--------------------------r.S~~~~D~~:------~ ~ ~~tm~~~--------------------------~ ~ FieD£e: ~ 2oGrid -- ~PicieciiOO : 10N - f5 Fie~~on:
- ,10"PIPE
- Min.A~ 0.274"@P03 w Location Note: EXT RATION STEAM ~.M~'ic. fl~ing: 0,~1Q"@ LOS. -..J l~(;)o : .: C:J. DANSO~ I C. W. KJEHL Repcd Date: 41212003
=ti m () WinPius Dat~ld EX.o2.9.oi gr.:Fi::;-ile--;B;-~-- -=- 20 ~
- -
- ..G~o;z.:..
- .9_
~;;:;::-: -.il.4;;-::- -:::-St.IYeY- ...,jl~_~-.-_ e-::_-__ _1""~ 0 04:-:c.NIIl-::::_~!LW:::: ~::---_-_-_-_-_-__ - _-__ -__ -__ - _-------~---_-__ - _-__ - _--__ N AeType : Er~~-~n_: IIIN g fii~ __p;;c;iP,tion:
- * "ia.-45 ~'Et.iiow* * -
Mh Reao:i-Q:
- lo.2B4@ cHi-* *
~ _t._ocaOOn _-_ "l_ote:__
- -eXfmr*ol-l*sTA"M -- *** * *
- --- ~ -~ B!it!l~nV~~~ *:...: _ W.
o.44t':~lor_-:_-__ ~----* ~~ I_D :. _
- lC:J. DANSON 1 c. w. KJEHL i
. r** t RI!P¢ Date: 412/2003
WinPius Oat~ r EX-02.9-0:fr. -1. .~ ~ ~ ~ (\\) ~ (l \\o,} ~ +.. -....t f2".r t..-m ~ t..tlt.l<>)- Repoft Date! 412(2J03
f A E t * * ~~ ~****:... Witr~s~rt.j~ e.:~~mr:nati:~rr~~p*or( , =' ' n ergy ' " ,' ' ',,' ' ' ~'if;i.ivn4,, . :.:<. ***: sy~d comp. 10.:
- ~)5:tfa~ttoh
- st~g~rri i ex~02;9~o2P.... *. *.Exam )t~~,: * ** P.ip_~*;**_EIJ?qw;. P,i_pS';* E:fb~.w; ]:lfpe *
- ""
- *.....,_ *\\.
. :*.... <** :*:--~*.*.~.. ".. ** ' ' :, ~6~~:Q:~j~~~i~~~llfo~~;r.::~~~< ~~,,,,;~~)( ',**** ~~~~., ~gt~~r:.~p *
- ~.< 4.
.;f,f~:;~t¢*:~~~~::::~:;*#~~~P~**~*~*~~7~~.~~:t~n**;; -* *. ~;~:~ ****?*~~**
- . * ;figuh?mijnt..
.* * :*~ *.: .... *.. :*.,:**-:***.. * *. : : ~ -:* . ~.lii~~}f.~fti~?( . 1?27q-1,:R~.!J~itl~!rJ~s:,&~.DLt... ~u.:~: ~i~~{20d.t.._:.. <>,. *.:.. : .. ~ ***::.::........,;;.,.** **:.. *.
- .. *. Vettle-al*lmearlt,/Check. * ::. *.. *...... * :.: :* :.. :. *:....... :*.. * * * * :** :.AttenuatorJ::fmratitl[ Checl{ ::.: :-.;. "*...
- * *~1a.11ar 11:100,.. M.f *8l>'-1.1*o* L60* I* sO::.r 40 1. *30 J *21k l 10:1
. :11!Mk*s*dt; **1 S0%-.12 dl:i 1'*-.fo%..- 6 <fb *1**wG + '12f9b' l..
- * *. *Sigi'lliF2>:rNIA' *.NrA:I:NIA -N/A:I<N/AI.:NTAl*ntAI NIAI.N/~d.N/AI *.**.
- .. :.. -:N/A. *
- .* *. *JifA *.
._... : NIA * *.. .Nfff.
- . *.*.{sfgrta12~hall eguai5Q% -::o~sig~ar v *s*!O-ot.rarrscaie.)- * *. _*:*.* {:fi.fo4.8)'.* * (16 tQ'24)" * * (li4"96)...
(64.~6) *
- .:. T.~iil,~:~du~~(~.. *
- * :~i~93j:*~~r.i~iif~(r:rc~:
- s.Mht*o,~i~;f.: ~o.4~ci : ii'791~~~M f.D.tJ,ai *~iem.eilt we~~~:~ ~iA
~.ea.rclj.Unl~ C~ple:. - 6\\~Qif~Co.!ii... *. *.. W~d,9.~ b.1,1ia.:S ** Ap~M:. ~/A:.~. E~itP:oint:.'Frbntr'.. N/A * (:*!l:tn~~~~~ $~~~~~$*~~:~~~o}!t{~~~~f;ii~~,.~on S,tj*t ~~~>!iWiob~. r*~~1~ **..
- tle'fereu~e*:eJock: ** * : N/A
- .NIA:-~F' *...
w=.==r=~=r":!""T""'"il';.....-'1,,.,.,R""'T':= .. _~"'ii Retlect~r. ~r;:nt.. *.. /~~~ Pp$:, : ti.B * *. * >~~~~~2~~): :. :*~~~~: * ::-.. *:... * *
- r:"-:-'*~-,. :-~~ep * * ;~o:
- 1':o: ! **NfA:
- V~I.QcJtY.(JrU~s) r* *... 2>~43
.. =~~;_L - -,. ~*.* *.. ~~~~: *. = ~~ ; :~ ~~ !i~J!~l~~. *
- ~.o. *
- * * ~r *:_::__-(-*
Flltar:.. . Furr. -46, *. ~ *
- *
- Phi.se Length:.
- Ft,C.ed *
- ~d
- i2il.,..
- ~~ :..._ ~---*? _:. c:*a**l**,.:b'::a:. t.,,;.*o
- ~ :n<*:_~im
- .**e
.. ***.*.* * *.. **:.*. ~. :**.~.M.~: .:~~:~~ct: ~i~:W'*... :. .. 1a ~ .~ **
- R R t
- Fi~&ci * *....
t osoa I *o73U. -} : 'O.~zo: ' I :WA'--l~/%1 : * ~I?**. a* ~ 1
- :'~;** :.<P.':'t..*2 **~f - 4 :: ~.&: *f
- ~r>~-~:~o ;_:~~- ~:;,:*,:**;:-::*>. **.*--.*...... -:*<-*..,.*.:. **j;~;a.te:
. ~~~~ - N7A%DAC: .... ~ . *. ~.... \\. IPEC00020940
=u m () 0 0 2 0 c.o ~ ~ NDEP 9.4,- 'll RevA I
- lllt 2 j. 1 of 1 03UT141
--=:::;:-Entergy Page 2 of 7 Report No.: ___ Sys./ Comp. ID: _ _ -=E::.:x-:tra:;:;c~ti~o:..:n,;::S:.;te:-=a;:-m:...:l__ Material: Carbon Steer High Reading: 0.428". Exam ltem: ___ Pipe Elbow,Pipe, EX.-02.9:o2P Size: _......;:;.::;;..::;.::1.:::0::"" :.=;.:..___:.. Low Reading: 0.158:' ElbOw. Pipe DWG No.: __ E:;:.C;::..*.:.;Hc..:-5:..::0c:;. 08=-1:...;rec.:;..;-:v -:..::2:;___ Thickness: 0.250" Grtd Size: " - WR I Mod: lP3-02-24847 Configuration: See drawing* below Datum Point: Outsi4e Radius of Elbow QA Cat~ory: NOOCat. 1. ASME XI Class:~ Cat:~ Acceptance Standard: --=::...::;=:.::::o~...::.;:;;=:. __ 0.219;, Procedure: NDEP 9.4-12 (I) Rev.: __ 4_ EX*OZ.9-02P 2" Grid Spacing 3 ~ EU2 9=jiZP E)(-92.9-lOP ---+ ~ A1,- Min: 0.. 318" Min: o.366" A1::)a11.11!1iq a '+' N 0 p Q 5 6 7 0 P Q A 8 C 0 EX.OU:02P LOOking PIS Max;,0,400~*o=~~ " ~ ~ .Al Max: 0:3.77" ~ L EX.02,9:071; 8 1. 2
- 9.
3 10 11 5 12 8 13 7 8 14 a 15 16 l--0.156" ~ 17 ~ LOW Reading M3p iill:!!i.~~ Low Re<Odlng Map Rematl<s: Alf thiclmess readings above are In thousandths of an ineh. For Min. &,Max *. ~eadiMS ~fetence,abl>V.e Sk8.tch. Reteren.ce abQve for Low Reading. M*ap. Reference above for Obstr~tetlons. Method Used: Grid Point Readi'ngs t- 0.194" 1:1!.:!!2-Bl!E: obstructions: 0.183" A10, N09 - weld o let Min: :o:iar* EX~~.OIE _j ---T+---f'lr_.- Max: o.428" Miil: 0-19f' A1 4 LAi-17 Mall: 0.425" EX:92.9::08P Min: 0.31.0" Max:0.393" Examiner: cXLA / f,-.A_,..,_ Luz A. Legaspy Level: _1_1 L_ Date: _4..:::/.=.09"-'/=20.:.;0:..::3'--1 .,tl v- ~/ ~} Examiner: -~/"" ...-/l.Y RichardW. Ford Levei: _II_L_ Date: Reviewed.by: _ _ +-}-'_:> '-C-=--~L.-...1 - "'-=J
- =*'if--*)1---
______ Level: :ITt Date: w/:.11.- II 4/09/2003 i.J/1 'f/o-;1 ANI! Review: ______
- ,_-,!....-------------'-- Date: _____ -!
REA1.01
WWlPiusDa~ fX.-02.9& =o m () ONg r::~:;-_e~TN;--,~ ... -.--*. :-_---~~fX;::-;-;;-02.::::-_9:::-:.();;:;7P;;-------.-.* ---------====-=-~-=--=-~--------------r;:~;--urv-~-0;;-ate-:--_
- _____ ---r.,0:-;4109103=
.* =_:-__ -_-_-__ -__ -_-__ -____ - __ -_-_-_-__ -_-_-_-__ -_...,._-_-_-----. "'",~g 20 Grid Er-Protection: ' ON g AeOe$cription-:
- o
- *p-;e
- M~.Reaclnii - - --- 1 0.316'~@-M"rn ** * -- ~ Location _*_ ~,.. '. - '!liT~ sliP;;~ -- - -- -- - -- : -... *~ r~~ 1l11 - lnspectodD: _ __ LA.~~Pr'._!'I.~.FOR.Q . -=-=~=-:.-:-.= . :. -~~~-- 1 p f :r.. ~.!!l' v/t'1/o3-Report Date: 411 012003
Report Dale: 411012003
O -~ '-l._'k ~'$ e:j'$, I ~v-'- ~.£ t'):;;#,'"' ~ ~. I I I I I ~ I ~ r- ¥i.o:-;;.-- L I ~ ~ ~*
- r X!: iiO:
1 1 ~ I r I ~
- 1 r
~. ~ 1 r t 1 t~
- * ~
~ Report Dille: 411012003
=u m () r*. I gr-F~~~N~Mre--:---------.!~EX~ . ~~9~~~------------------------------~~~- .--~o~~:------
~
~ 0~4~~~~----- ---*~---- --=~----
~.
~ ~{~~~ ~~~~-* : ~.~~----***------*-*........ --- *------*. -~~:r~.:-----*-- 1 ~.~97"@P03 c.o ------.. - -r;------**--* -** - ... - --- ~----- ~ ~1!~-'----** -*...f:..EXTRACTIONSTEAM ____..*.* __ ----- ______ J!!.!!-. Reading:_~----! 0.425@':!...~----*---********-- __.. ____.. __ l~ct~.!Q.: __ --* f l.:...~lE~~~Vf..FD~Q_- -*---------*-*- !--~-- --*--- - --}--**------* *- =~-:_~---~==~--~--* ___ _:~:...=-.=--=~~-=--=~~:=;:.==-~=-==-:.~-------~_:-~- =-----~~- ---=- ~..-.:~*---- *-
Wiljllus Da~ EX02,sot ~ **..... ~ .? ~r.::... ~~"~...,, t:.r,i>t_
- * ~
~ ~ .~. ~~:~* ~ ~~ I I ~ I I ~ ~~ 1 I 1 I Rep_ortDate:.411012003
__ --*r _- ~ - B:n/;4rfill --_ ~ .UlJt~$ooitJ=t.~rriin~ttcin* ~~P.hrt --- _-- __ _,_... ~.ttrOJ
- fP:ECHnit~# 3
-*Re:p~:>r:f:*t.~.o.:.. Q3U1:142-. <-"" Syo., t<>n~p.to, 9it<~titro'n. si*a!" ftifo:tc1;0ii.E .;.."' '"'" ~ii{M,~*;~)k' *r 4. * * * ' **.. **.*...*
- t~ :~:.=~~~:~~.~\\~~~~-:.:~~ -~ ¢*i!1#A.*.*.
- p~z~~,. :~&#~~~~~)
,~~.,.. *....
- oom~onfint
.cpn'figur~trorj*: Er~:o:w.
- '_-drle:ritation: * !l O~gr.~e:
j:yaa ot-Mat~rfa1:. :- _,ca(bon's~e~l . *.,.~$gr~: o o
- Modi!:. L<fQgJ,u41nal
. * --:~t~~( ** ~ o*"' * * * 'Tni¢~ries_s:!'. :e_.~e:s.. ' .. :_* ~~~da:~~::~~~:.;:.~($)~ - '~!!%}).f:no;p~~!:~~i~$2~!~!~~~~i~:.W!~: __ \\~~:ruatro~*-Le~e_i!*... '. 1'00.' ~/o Cbmpf~'te ' Limit~Uons:. Npne *.... :* *... *. :. : --. _Rema-fk~di~co{dable-lndicatiort!?*_:R~feren~~:pagld#r3:.. :...,_ -.: :*. *. *.. . Exatnit:led :I;X7o2~1 ~9~.E~. Us~q P.flfv.!~l,i:S!{~s~~ib.Ostt~d:3**. gf,;(l. ~s.,PEl'r. fAC Engine6r.Ji:lg.dJret;tien *. *
- ~*-.. *.* :.:****. ** * ***. :_
_Exarriirier: --;-~- -_~2:::0 ~ -c-~ - ::!~:!:
- _'-':J
- ~ --.E_~!::
- *.t:
- ~ ~
i:! ":~~:~:_£<"'-* ~
- ~..:..* *1. R~lcru
- hlla!tf.dQ.-*:Y..W'f:... JF:.Qor~.i:I;L-'J;'L~e~ve!il'I£
.::*.!!JIILb:.-~ o~te_: ~t~:212*0.~3
- =b_y_:_;____;_.;__-'-_-r[:.....
?o.:-
- *-~~E-=-
~.:.:.: __,..:.:.;.;.... ~-;;<< ~:_=-"J"'"f:J-** .<_,-f
- :~
.*~~"-
- ~
- -"..J!Nu:.:~....... ~J1'ivi!J;
_ ~~t*.:..1N:uA::~.._ --_.. _- :!?Y,ft"~/6 ~* ** ANII Revlew: ~ - -~-~-= . -'-:--*;.;...*...... '""r"'" . -'-l'"".~""
- ~.,.,
, __ _..,:"". - -'""* --------'----"'-"--~"""'"'-~~*~ - o.ate: __. __._.;.;___ ... :......... ~. -...,;..,...... -~........ -....,.,.. IPEC00020947 .f... ~: ~..
=u m () 0 0 0 N 0 <0 .j:lo. (X) ** -=-Entergy /'-.. RepOrt No.: Page NDEP 9.~tno Rev.4 I [ ~t2 -~ l of1 03UT142 ---~----- 2 of 3 Sys. I Comp. 10: __ ..::Ex=-;IT:;act;:;;io::-:n.,.:S'=te:;a;:.m~/-- Material: _--::C:..:a:.:.;rbo:..:* :.:.;n:..,:S:..:tee=I--'.. High Reading: 0.419" Exam Item: --EX--02.1-03ETEiiiOw EX:-02.1-03E Size: 10" Low Reading: 0.224" DWG No.: --.;;:E.::;C.:.-H.;;..*.::..50:..:0;.;.7.:.1..;.re""v"-."'2*__ Thickness: 0.36.5" Grid Size: "- WR I Mod: IP3-=02-24847. C:onfigurat.ion: __ ..::S:.::ee=*..::d~raw::.:.:.:;in~gz...b:::;e::.:lo.::..w::._..;__ Datum Poi.nt: Outside Radius of Elbow QA Category: ~Cat. 1' ASM.E XI Class: NIA Cat: NIA Acceptance Standard: 0.319" Proc~ure: NDEP 9.4-12 (I) Rev.: 4 EX-02.1-03E 3" Grid Spacing Used previously established grid, Per F AC Engineering Pirection I J)<~_ AB* OD EX-92 1-93£ Looking DIS 4 6 7' 8 Remarks:* EX"921:9SE Low Rea\\ling f!lap All thickness readings above are* in thousandths of a.n int:\\1. Fof Min. & Ml!llC ~adings *reference above Sj(etch. Reference a.boVe for Low*Readfri!i* Map: Method Used: Giid Point Readings FLOw ('q_ EX.021.02P -S l .J r A1 'IL EX.02.1:03E Min: 0.260" L E)(.():.1o04P Max: 0.419" Examiner:~ Richard W... Ford Level:_l_ll.-_ Date\\ 4/1212003 Examiner: ___ 1
- ~=_-~.,....
. _:/~;:.:..
- *-~
. - * ~n-1 L..4,__ _ ____:N:.::,IA::.!. 1.-evel: ~ Dafe:_........;:::NI"'-'A'---l Reviewed by:_~--+-..._:......;~~........t~~~~~~~r::=.---- Level: [IC Date: 't/!'t/o:J ANII Review: _________ /'-'__:f._/1..:.. Date: ----:::R-::::E'A-:-1--o-11
~rsys*.
- -,=c-o.mpE.
- ,o* *.nf~t;gyra
- c*t**o*n* *s*,_te_a* *m*
__,.e:.o 1 2 1
- r.9@_.,~2°P 0
- ;~ El<<iihhlat!on. ~!'Port ~r:~~:z.£ur<~l
- ExamJlem:
Pi~~iP.ipe,PipE!,Pipe,Eib'Ow,Efbo~,Eib9W \\... :*'.. oW~* N~. Qr Sketch: EC*H:59tJ_s1*Rev. t
- w~M~a:.
fp*a~o3~1s257 < ** ci~,Sa_t~'gpey:
- N9n Cat.ASME;X.I,Cl<JS.s~ :Nf.A:
C~t:.. NiA*. ~-tQc~~d;~:* NbtP--9.'4*12(1)' c:: :..,.........,. * *.,.. 0
- Rev;-:
4 ~~*... *.
- : c.iMMfient'C~*riflguration:. Pip~ *(<;Pi~e to.J,ip*a to PIP.e-; Efb~w:t~~:lii~~~~;~eib~W.:. :
- * *-O~J~~t~fi6n~
- .o:Degree tyM::~t--~~j~ii.~l~ *
- Gatbon'Steel*
.*: ;:~ ;M_~Ie:. o..o Mode: longltu.dj!J'id 'SJ~-~-: _*19:'.
- Thickness:
0.365 ~ -~*.
- _:.s*C{uipm&nt.
ios.trt.t!'fi~ilt:. : 1021}1}:9*.. Pa'riarii~tflcs 3:soL:t-* Due:o2126!~PQ4
- V~rttBai.ur1*Q-a*rtty.Chec!(
- Atfenuator:.lin.e~rfty,Check
- s:i~~*al;f *j*too'j: *so } S'Q.j JO; 1-fl.O*.,*.so'
~~A~ 1, }~j' 29*1 ?~I 1* aow ~*6 -db **1~ :so%- :f2 db 1 40o/~+ 6 *db **1.*2_o% + 1 z __ 'd6 'I : Slgnal~
- _!~[~_-NtA~-~A-.NiA-.f.liA. *N'tA'* _,[~:Nt~;_Nik_ *~~--
.* ~ ':N/A.. ': _.: -N/~ . J:!lt(... N/A...... A~iglial2 s.halt*equai.'.S.O%' o.f~ignal. 1
- 5.Pk. ofJ9!1)~~1&..l
- (az 1!>.48).. :.
(1.~ fo '24) * (64-~'6) (!)*hs*sr n*n~duc;~r: *
- 5!)2ll55 *P.an~~me.fries *s.:rvniz: :o.aii!l 'R(;!und ;th:~1 tci~ii(;l:ler:Oent W~;~9~le: :NtA
- Sea'r~tt~~n((cable:
6; s~Jf~Co~t.
- W~Cise::~~~s. Ang,t_~l..
- N7A ~
~.><ft Poinf-Fnmt: NtA "
- *qoup;l~nf *oq~45 :Son<>te~h i *son.o);oo_ G~I.
l)l~l'fui:!.J;JJQt~r: * *1"o}74'6. . Due:.8/7/2003 'Temperature.. .
- CaH6jatipn~B.Iock>
16ao61
- -stepWedg$ T= ;25**--*1.'1 : Marerl~I;.Carb.on st~el *
- 6f.ii'F
- s~~~iai9.~'*sl~,dk:
- NiP.<
NJA.°F
- -R~~~~..efid~ BJ(>ck:
- NIA NiA*-Df= *
.. :e~{~hsu'frii:ci.a: dP. co.rhpcment:
- 66-: ~F
- ~- :~'OJiial'lc~,.Arrtplifude curve
- lnstrutnent :.S~Uing$
~*.::.*:~-~~~~*~~*~JlS~*-*sbr8ari*:ot~tst.on
- ==~ *. o:1QQ',.
- ~
~.. R~nge (1~;):.. t.o:,*..
- (_~r_;;.:_*'.;<-~:*O
_s_,_;.~".*,:_} 1 .l .-~ef!e~tot..,QrlenJ,_ F.~.. t -~Ol!, tis * * 'rh'ltkCal:
- i;PT *,_
- o~~w*. * *. ;~teP. * *.:a.Q
- 2:s *.:NIA. '*
~V~iP~lty:(iih/fis>~* t~a~.
- ao.:
1 ~ Oi~o.a*:
- "-~t~p- * * ~~-o ~
- 5:(}-..,J~;A. *
~en~JifVIti(CJ~k* .-:~s;
- ~o* :..
a. J:.:S.o. ~*...*.... -.~_:s _.. :t. ep_.. so. *
- i:s.. i;JrA * "sc~n. s&nsjfivity ** so%
~-~
- 1 :Q~Q". *. :.. ~t~P. _::: ~o~,1:0.o: N/A
.-:f.rkq~en~y '{m~);. s' . s*o
- ~e)ed:
- *
- Off.
- ~ *
- r=iiler.
- F.utl 49..
- ~u(~e.':,Lergth:
~ixed -~6:
- Damping:
Flxetl .~0: M. OCJ. Q:_S.Bl9Ct:
- ~
.*_ "t. - raJ. caUlrr.aticin Ti'mes.:. .:1 o:t--+-+---+-'-+--i---+-+--1---+-lt I 1 1 1 =*,,, bt 1 . Tli I Rep. Rate: Fixed. _13ntl_ * *-r4~Q- * -*.t~po _
- ~vt/-L fv.t:_A
- PEG/Gate:
on fil:. 1: *2 a 4: 5 6 7 :8* -9* 1G
- -J~~ks:
- TIR:
.-~*':.
- : A~c~pt~nee* s*tand.iud:.
s7;$.'% othom1nal.a$,f!ef.A.~-49:i~~*~,~~*rne!_l~s,
- Re'cor~able Jndlcatic)l'1(s): N6'* *.
Re~orcfii}~):.evef: * 'NiA'liic... oAc. Evaluation Level: NTA.~J~:oAG
- ::_ ti>ff '9;;. c.ompletEJ,Lirnitati,oris:.:.Ngrte..
Re~arks: ii'aselin~. ex~m ~n EX~Oi9.-02P :&* EX'-q~,~*g~#j)rptni:r ref.e~~ric~-pa~e~2;of 3: . ~as~ll.!'~ ex~m on :~ur: eJb~w}:-x~q2,~~q~.EJ~.:.4S.:'e{b~wex.n~.9*o~ ~~~J.~pce p~ge} of l: L:ioe* sc.~n perFA:CiEngineerin:g d)rectlo~:~ *..
- * * * :(;)!;£
( IPEC00020950
-u m () 0 0 0....., 0 <0 (}\\ -=-Entergy Sys. I Gomp. 10: Extraction Steam I 'Material: Carbon St.eel 6X~02.9-.02P Size: 10~' DWG No.: EC~H-50081 Rev,. 2 Thickness: 0.365" ConfiQuratiqn: See drawina below Datum Point: Oulliide Rad.ius*oft:\\b.oW Acceptance Standard: 0.319" EX-02.9"02*P Report No.; Pa.ge High Rei!ding: ~ Low Reading: 0.364" Exam Item: Grid*Size: N/A WRlMod: 2 NOEP 9.4,.t""!\\ Rev.4 r 1 ;ent2 '-"~ ol'1 03UT151 of 3 Pipe, Pipe, Pipe, Pipe IP3-03-15257 QA Cat!!!gciry: NOnGat, 1 ASME.xr Class: NIA Gat:~ Procedt~re: NDEP 9.4-12 (I) Rev.: _4 Line Scan as Per FAC Engineering Direction
- '!~........
~ ~ ~ ~ ~ ~ ~ Min:O;nt;r Min: o.m* M l~; 0.380" Mil>: o.381" ~ . MaX::o:426"" MIX: OA.tt' Mu:M2!" -:o-~ ~ ~o~ ~ o~ ~~=v ~ ~ . ~ ~ ':~=- ~ ~ Mln:O.:l67" Min; o.:mr 2 Min: 0.3&6"
==: Wtla:' 0.381" 4 Mln:'0.367"' Male O.A2!S"' M11a.:0~1r Max; OA%4"' M~ 0.407"' ~:0~41'tr Max: 0.42V ""CI;(O <i.408"' ~- ~ ~ ~ ~ ~ ~ ~ Min: '0.37$" Mln:0.374" Mln:0.374" ..,n,::0.365""" Max:OAOr Max:O..,.,. Mak: 0.41t" Ma>i:0-411" 6 1 l 2 3 t 4 6 24" '!K' 24" r rr Remark$: All thickness readings above are in. thouSandths of flL~~ William G. Halle~ an.inc.h. Examiner: Lev.el: _,_,_ Date: 411512003 For Min *. & Max. Rea.dlri~ tefel"enCII'aV&Skett!l. Ba*ellnit 'Pij)e:eilam for EX-02:9-0tP. & EX..02.9~P. Exami.oer: y-/k t N/A Level: N/A Da,te: N/A 'f/J,/o3 Reviewed by: Level: _:;;;g;_ Date: P~w:J < ANII Review: tv )lJ-Date: Method Used: Line Scan ReadinQs REA1*01
=o m 0 0 0 0 ~ co ~
- i.
-=-Entergy Sys. / Comp. ID: __ ..=Exl:c;::,: ra;::c;.::,tio:,:n.:.,S::.:t::;,ea::,;m:..:.*.:...'-- Materiai: _ _::C::::arb~o~n;:::.st!:::ee;:::l'--- High Reading: 0.418" Report No.~ Page_ NOEP 9,J""'?Q) Rev.4 I nent2
- "de1 of 1 03UT151 3
of 3 Exam Item: -:---=E;.;;Iboloi.~-=E;;.;;Ib.;;..owc.:'-=E-"Ib;;:.;r:NI.:___-i EX-02..9-02P Size: __ ___,,..:1~0,.,' '.,---- Low Reading: 0.375" DWG No., _---;E;:,:;C:.,:-H..:,-.;,50::,::0~8.,:,.1 ;;;Re;,:
- v~. 2.::;_-
ThicknesS: 0.365" Grid Size:t-lli\\ WR /Mod: IP3-0S:.15257-Conftg4ratio.n: __ ..;S::::ee=*.:::d:..:ra::.:W1~*:_:;ngl2..:be=IO:..:.W:.___ Datum POint: Outside Radius of Elbow
- 08. Category: NOrlCat 1 ASME XI Class:
N/A Cat: N/A Acceptance Standard: 0.319" Procedure: N.DEP 9.4-12'{1) Rev.: 4 Extradoa. EX:ll29.P3f M*ln:O,S~" Max:o.4iS" EX:929:()3E 0 Min_: o:s86'* 1 Max: 0.412" lnicados EX.02WE
- Min: 0.380" Max: 0,404" e-xma:Oae Min: o.3a4" Max: 0.406" 90"Eib0w EX-02.9-02P Line Scan as Per FAC Engineering Direction Extrados EX-02i=Q3E Mln:0.391" Male 0.418
EX:02 9-{!3E 0 Mtn: 0.3111"., 2 Max: 0.406" lnt~o EX.029'.03E Min: 0.375 Max: 0:404" EX:029-Q3E fX'..o?9:03E Min: 0.37,8 Max: 0.408" Pipe Stamp scanatpUnd bevet-10STOWPI! P'(017S ~ Min: 0.386" -- "\\a.x: o:4::~za~ scan. around.bev,et Min: 0.386 Max:0.415" Pipe.~ J TFA10STOWFB!>I$67 Remarks! All. tlliCkness;TE!adings. above are. in. thouil9ndths Of Examiner: ~ vl~r:=William G. H'alley ExarT.!ine.r; J?tb:IJ: NIA .an inch *. F'or'.Min. & MaX: ~ead.ings refereil:ce: above; Sketch. BaseUne*90° El.bow exa.m for i:X;o:2.9-03E:: Baseline *s* Elbow.exam for EX-42.9,0~. Reviewed by: AN II Review: (V}/f Method Used: Line Scan Readings Level: II Date: Level: N/A Date: Level: TIT Date: Date; 4/15/2003 N/A, '-1/ Jt/*'3 REA1-01
~~===::r ___ _::......_'.)~~!~' ~,", :?2 '~ ~~ ~.; ~~- <; ;/ HAR ! r:c: *.
- "' J
- *.*:i:**. *, £FERENCE DRAWINGS'.,_,.,_,... < .. :i'.:;L *~.:>~:~~.::.~~:.:~**. 11'16"
~--*.- t.iNCO!HROUEO DRAWING ,.4J-. o..t<> HAR 1.1 20DJ C;lt;!'EC?! - E'""'..t'... *~ 1 **~l,., *~:~ _ dra.. ~r:() c... ~., no.: :'f'.' c
IPEC00020955
- 1.
- 2.
- 3.
- 4.
~.*
- I
.I TRAVELER PACKAGE CHECKLI~ '¥ Prelnspection briefing given by Erosion/Corrosion Engineer ~7 El ng. (j _L) d!i UTTech ~- UTTech UTTech Traveler package contents J m: UTTech
- a.
Copy of procedure NDEP 9.4-12
- b.
Calibration sheet
- c.
Drawing with point highlighted
- d.
Data sheet
- e.
E/C Engineers phone number Location verified against drawing: UTTech Preinspection point setup per procedure NDEP-9.4-12: (If gridding Is used)
- a.
Correct grid size used
- b.
Grid correctly laid out
- c.
Grid lettered and numbered correctly
- d.
Grid low stress stamped correctly
- e.
Area up/downstream of component pr. perly laid out EIC Eng. aJ.
- I_
UTTech
- 5.
Data Logger UT ech
- a.
Inspection point used as file name
- b.
Operators ID correct
- c.
Instrument ID correct _L
- 6.
Data Sheet UTTech
- a.
Flow direction correct
- b.
Sketch drawn correctly
- c.
Component number verified ~
- 7.
Calibration Sheet correct UT Tech 5J(i ~
- 8.
Daily review complete E/C Eng. NOTE: UT Technician sign-off is required prior to start of inspection activity. Engineering sign-off is required after verification of activity. ~ ate R12 Traveler
Inspection Point Work Order Pipe Size, inches Tnom Screen (87.5% Tnom) Screen (70o/o Tnom) Grid Size, in. Pipe Class Pipe Spec, Grade Fitting Spec, Grade Schedule Design Pressure, psi INDIAN POINT 3 R012 Design Temperature °F Allowable Stress, psi IPEC00020956 EX-02.9-02P IP3-02-24847 10 0.250 0.219 0.175 2" A-3 A-53 Gr. B A-234 WPB 20 250 400 15000
Inspection Point Work Order Pipe Size, inches Tnom Screen (87.5°/o Tnom) Screen (70°/o Tnom)
- Grid Size, in.
Pipe Class Pipe Spec, Gra~e Fitting Spec, Grade Schedule Design Pressure, psi INDIAN POINT 3 R012 Design Temperature °F Allowable Stress, psi IPEC00020957 EX-02.9-~( £)t1JANS /() N 03£ -i:£.2) I P3-02-2484 7 10 ~ (?. 4j J(! ~ 0, 25~ A-3 A-53 Gr. 8 A-234 WPB 400 15000}}