1 Burkhardt, Janet From:

Lingam, Siva Sent:

Tuesday, October 13, 2015 10:24 AM To:

Lingam, Siva

Subject:

Diablo Canyon 1 and 2 - PG&E Response to Questions on LAR 14-04 Associated with Leak Before Break for Fuel Structural Analysis (CAC Nos. MF4988 and MF4989) -

PUBLIC From:Schrader,Kenneth[1]

Sent:Wednesday,September23,20158:30PM To:George,Andrea<Andrea.George@nrc.gov>;Lingam,Siva<Siva.Lingam@nrc.gov>

Cc:Soenen,PhilippeR<PNS3@pge.com>;Wright,Michael(ENG)<MDW4@pge.com>;Nelson,EricP(DCPP)

<EPN1@pge.com>;Jahangir,Nozar<NxJ1@pge.com>;Zaitz,KristinMurray<KMMh@pge.com>;Schrader,Kenneth

<KJSe@pge.com>;Andrachek,Jim(andracjd@westinghouse.com)<andracjd@westinghouse.com>;DaveDunsavage (dunsavd@westinghouse.com)<dunsavd@westinghouse.com>;DaveSklarsky(sklarsdw@westinghouse.com)

<sklarsdw@westinghouse.com>

Subject:

[External_Sender]PG&EResponsetoQuestionsonLAR1404[CONTAINSPROPRIETARYINFORMATION]

Siva,Andrea,

BelowisthePG&Eresponsetothe5questionsoftheLAR1404,UseofLBBinthefuelstructuralanalysisanduseofthe fuelstructuralanalysistosatisfy10CFR50.46(b)(4).

1.Page2ofEnclosuretoletterdatedOctober2,2014states,inpart; Thechangeinthebreaklocationinthe2010fuelstructuralanalysiswasnotaddressedinthecorresponding10CFR 50.59evaluation.

Pleasestatethepurposeof10CFR50.59evaluationandprovideacopyoftheevaluation.

Response:Thepurposeforthe10CFR50.59evaluationwasfortheIntegratedHeadAssembly.

2.Page6ofEnclosuretoletterdatedOctober2,2014states,inpart;,SummaryoftheDiabloCanyonUnits1and2FuelStructuralAnalysisResultsfortheHosgriEarthquake andtheAccumulatorLineBreak,providesasummaryoftheresultsoftheDCPPFuelStructuralAnalysis.

PleaseprovideacomparisontoshowhowtheresultsoftheDCPPFuelStructuralAnalysisfortheHosgriEarthquakeand theAccumulatorLineBreakcomparewiththeoriginalanalysis.

Response:TheoriginalanalyseswereperformedforVantage5fuelanddocumentedinWestinghouseproprietary documentVantage5ReloadTransitionSafetyReportfortheDiabloCanyonPowerPlantUnits1and2,datedOctober 1988.Themaximumstructuralgridimpactforceswerecalculatedconsideringtwobreaklocations,areactorpressure vesselinletlimiteddisplacementLOCAbreakandadoubleendedreactorcoolantpumpoutletpipebreak,andthe limitingbreaklocationimpactforcewasused(basedonWCAP9401PAmethods).Themaximumstructuralgrid impactforceswerecalculatedconsideringaccelerationspectrafortheHosgriearthquake.TheresponsefortheLOCA accidentandseismicanalyseswerecombinedusingthesquarerootsumofsquares(SRSS)method.

ThemaximumZircaloyMIDgridforcesusingtheSRSSmethodweredeterminedforafullcoreofVantage5fueltobe

[]poundsforUnit1[lessthanthe[]poundsfortheAccumulatorlinebreakinpage4ofAttachment4tothe EnclosureofDCL14083]and[]poundsforUnit2[lessthanthe[]poundsfortheAccumulatorlinebreakinpage6

2 ofAttachment4totheEnclosureofDCL14083]whichwaslessthattheallowablegridcrushstrengthof[]poundsfor thegriddesignatthetime.TheLOCAanalysisforcesatthegridlocationwithlimitingSRSScombinedloadswere determinedtobe[]poundsforUnit1and[]poundsforUnit2.

ThemaximumIFMgridforcesusingtheSRSSmethodweredeterminedforafullcoreofVantage5fueltobe[]pounds forUnit1[lessthanthe[]poundsfortheAccumulatorlinebreakinpage4ofAttachment4totheEnclosureofDCL 14083]and[]poundsforUnit2[lessthanthe[]poundsfortheAccumulatorlinebreakinpage6ofAttachment4 totheEnclosureofDCL14083]whichwaslessthattheallowablegridcrushstrengthof[]poundsforthegriddesign atthetime.TheLOCAanalysisforcesatthegridlocationwithlimitingSRSScombinedloadsweredeterminedtobe[]

poundsforUnit1and[]poundsforUnit2.

3.Page5ofEnclosuretoletterdatedOctober2,2014states,inpart; TheLOCAloadforDCPPwasbasedontheloadsassociatedwithapostulatedpiperuptureintheaccumulatorline,the RCSbranchlinethatproducedthemostlimitingloads.TheearthquakeloadforDCPPwasbasedontheloadsassociated withtheHosgriearthquake.TheHosgriearthquakegridloadsweredeterminedbyanalysistobemorelimitingthanthe DoubleDesignEarthquakeandDesignEarthquakeloads.ThelimitingLOCAload,combinedwiththeHosgriearthquake loadusingtheSquareRootSumofSquares(SRSS)methoddidnotresultinanygriddeformationforDCPP.

PleasestatetheoverallimpactofShorelineFaultontheearthquakeloadsconsideredfortheevaluationdocumentedin letterdatedOctober2,2014?

TheNRCinalettertoPG&EonOctober12,2012(NRCReviewofShorelineFaultaccessionnumberML12073106) issuedtheresultsoftheirindependentconfirmatoryassessmentunderResearchInformationLetter,RIL1201)thestaff concludedthatShorelinescenarioshouldbeconsideredasalesserincludedcaseundertheHosgrievaluationandthe licenseshouldupdatethefinalsafetyanalysisreport,asnecessary,toincludetheshorelinescenario..Asaresultthe DiabloCanyonFSARhasbeenupdatedasrequestedbythestaff.ThereforethedesignbasisforDiabloCanyonremains astheDesignEarthquake/DoubleDesignEarthquakeandHosgrievaluation(asaboundingcase),andnoadditional analysisorreviewforshorelinefaultisnecessary.

4.Page3ofEnclosuretoletterdatedOctober2,2014,inpart;

TheNRCapprovedBELOCAmethodologyalsoaddressesgriddeformationinfuelassembliesthatarelocatedonthe peripheryofthecore,ifitisdeterminedtooccur,basedonthefuelstructuralintegrityanalyses(Reference9).However nogriddeformationwascalculatedtooccurinthefuelstructuralintegrityanalysesthatwereperformedforDCPP.

Reference9(WCAP12945PA)isapplicableonlytoUnit1analysis.Unit2analysiswasperformedinaccordancewith WCAP16009PA.PleaseprovidereferencetothedocumentprovidingjustificationfornogriddeformationforUnit2.

Response

TheBELOCAanalysesdonotdeterminewhetherthereisanypotentialfuelgriddeformation.Thefuelstructural analysesdetermineifthereisanypotentialfuelgriddeformation.

AsummaryofthefuelstructuralintegrityanalysisresultsforUnit2arediscussedonPage6ofAttachment4tothe EnclosureofDCL14083inthesectionentitled,Unit2CombinedSeismic(HosgriEarthquake[HOS])andLOCA (AccumulatorLineBreak[ACC])LoadCase.

ThequotedstatementintheisonlydiscussingthattheNRCapprovedBELOCAmethodologywouldaddressfuelgrid deformation,ifitisdeterminedtooccur,andnotthattheBELOCAmethodologycalculatespotentialfuelgrid deformation.

3 5.Regardingtheapplicabilityofthefuelstructuralanalysisresults(whichutilizeLBB)tosatisfy10CFR50.46(b)(4),

thecoolablegeometryECCSperformancecriteria,theNRCstaffpositiondoesnotsupportapprovalofthisportionofthe LAR.TheNRCstaffpositionontheapplicabilityofLBB,itsapplicabilitytolocaldynamiceffectsonly,andits nonapplicabilitytoECCSperformance(sinceECCSaddressesglobaldynamiceffects)iswelldocumentedinNUREG0800, StandardReviewPlan,Section3.6.3,andinFederalRegisternotices51FR12502,datedApril11,1986,FinalRuleto modifyGDC4;52FR41288,datedOctober27,1987,2ndFinalRuletoModifyGDC4;53FR1131,datedApril8,1988; and,54FR18649,datedMay2,1989.

Response

PG&EunderstandsLBBcannotbeusedfortosatisfyECCSperformancecriteria.

PG&Erequestsapprovaltousethefuelassemblystructuralanalysisresultstosatisfy,inpart,theEmergencyCore CoolingSystemPerformanceAcceptanceCriterion,10CFR50.46(b)(4),"CoolableGeometry."Thewordsinpartare includedinthePG&EdescriptionofthechangebecausetheDiabloCanyonECCSanalysesforpeakcladdingtemperature andlongtermcorecoolingtomeet10CFR50.46requirementsdomodeladoubleendedguillotinebreakinthecoldleg asrequiredby10CFR50.46.Thefuelassemblystructuralanalysesareperformedtodetermineifanyfuelgrid deformationoccursandtheseresultsarethenusedasaninputtotheECCSanalysestodemonstratecompliancewith 50.46(b)(4)fuelcoolablegeometryrequirementsinaccordancewiththeNRCapprovedWestinghouseBELOCA methodology(WCAP12945PA,AppendixC).Thefuelstructuralanalyses,unliketheECCSanalyses,require considerationofaconcurrentearthquakeandLOCAperSection4.2oftheSRP.

Thedeterminationoftheconfigurationofthefuelgrids(deformationornodeformation)fortheECCSanalysis,basedon thefuelstructuralanalysesforthelimitingRCSbranchlinebreakbasedonapplicationofleakbeforebreak,hasbeen approvedbytheNRCmultipletimesforlicensees(mostrecentlyfortheTurkeyPointExtendedPowerUprate).In Section4.2oftheNRCSafetyEvaluationfortheTurkeyPointExtendedPowerUprate,thestaffstated(includedinPage 9oftheEnclosureofthePG&EletterDCL14083)ThelicenseeevaluatedseismicandLOCAloadingusingtheapproved methodologydescribedinWCAP9401PAformixedcoreofDRFAandupgradefueldesigns,andafullcoreofthe upgradefueldesignattheEPUconditions.ByletterdatedMay18,2011,thelicenseeprovidedinitialresponsestothe NRCstaffRAI.ThecoreplatemotionsandverticalimpactsonthenozzleswereusedintheseismicandLOCAanalysesfor theEPUconditions.Thelicenseeappliedseverallimitingfuelloadingconfigurationsforthemixedcore.Thelargest branchlinebreaks,eithertheaccumulatorline(ACC)break,surgelinebreak,orRHRlinebreak,wereconsideredwhen generatingLOCAhydraulicforcingfunctionsusedasinputtotheanalysis.PG&Eisrequestingapprovaltoperformwhat wasapprovedforTurkeyPoint,thatistousethelargestbranchlinebreak(eithertheaccumulatorlinebreak,surgeline break,orRHRlinebreak)whengeneratingLOCAhydraulicforcingfunctionsforthefuelstructuralanalysis.

Thanks,

KennethJ.Schrader RegulatoryServicesPacificGas&ElectricCo.

email:kjse@pge.com Phone:8055454328 Fax:8055453459