UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Joseph W. Shea Vice President, Nuclear Licensing Tennessee Valley Authority 1101 Market Street, LP 3R-C Chattanooga, TN 37402-2801 October 6, 2015

SUBJECT:

BROWNS FERRY NUCLEAR PLANT, UNIT 1 - REQUEST FOR ADDITIONAL INFORMATION RELATED TO RELIEF REQUEST FOR THE USE OF ALTERNATIVES TO CERTAIN AMERICAN SOCIETY OF MECHANICAL ENGINEERS, BOILER AND PRESSURE VESSEL CODE, SECTION XI REQUIREMENTS (CAC NO. MF6401) (CNL-15-125)

Dear Mr. Shea:

By application dated June 26, 2015 (Agencywide Documents Access and Management System Accession No. ML15181A448), Tennessee Valley Authority submitted a license relief request for the Browns Ferry Nuclear Plant, Unit 1. The proposed relief requests the use of alternatives to certain American Society of Mechanical Engineers Boiler and Pressure Vessel Code,Section XI requirements.

The U.S. Nuclear Regulatory Commission (NRC) staff is reviewing your submittal and has determined that additional information is required to complete the review. The specific information requested is addressed in the enclosure to this letter. A response to the enclosed request for additional information is requested to be provided by October 30, 2015.

The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for staff review and contribute toward the NRC's goal of

efficient and effective use of staff resources. If circumstances result in the need to revise the requested response date, please contact me at (301) 415-1447 or Farideh.Saba@nrc.gov.

Docket No. 50-259

Enclosure:

Request for Additional Information cc w/enclosure: Distribution via Listserv Sincerely, Farideh E. Saba, Senior Project Manager Plant Licensing 11-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

REQUEST FOR ADDITIONAL INFORMATION RELIEF REQUEST FOR THE USE OF ALTERNATIVES TO CERTAIN ASME B&PV CODE, SECTION XI, REQUIREMENTS TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT, UNIT 1 DOCKET NO. 50-259 By letter dated June 26, 2015 (Agencywide Documents Access and Management System Accession No. ML15181A448), Tennessee Valley Authority submitted a relief request for the Browns Ferry Nuclear Plant, Unit 1. The proposed relief requests the use of alternatives to certain American Society of Mechanical Engineers Boiler and Pressure Vessel Code,Section XI requirements.

The U.S. Nuclear Regulatory Commission (NRC) staff has determined that the additional information below is needed to complete its review of the application.

The fluence value used in the June 26, 2015, request is based on the December 18, 2013, license amendment request.

NRC staff noted that the fluence at the clad-to-base metal interface in Table 3 of the June 26, 2015, submittal does not match that from Table B-5 of the December 18, 2013, license amendment request.

Clarify the above inconsistency and revise the June 26, 2015, letter (as needed) to accurately reflect the fluence on the beltline, circumferential (girth) weld.

Enclosure

J.Shea efficient and effective use of staff resources. If circumstances result in the need to revise the requested response date, please contact me at (301) 415-1447 or Farideh.Saba@nrc.gov.

Docket No. 50-259

Enclosure:

Request for Additional Information Sincerely,

/RA CPfefferkorn for/

Farideh E. Saba, Senior Project Manager Plant Licensing 11-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation cc w/enclosure: Distribution via Listserv DISTRIBUTION:

PUBLIC RidsACRS_MailCTR Resource RidsNrrDpr Resource RidsNrrDorllpl2-2 Resource RidsNrrPMBrownsFerry Resource RidsNRRLIC109 Resource PPurtscher, NRR RidsNrrLALRonewicz Resource AHon, NRR ADAMS A ccess1on N ML15274A5 o.:

OFFICE NRR/DORL/LPL3-2/PM NAME JHauser DATE 10/ 5 /2015 OFFICE NRR/DE/EVIB/BC*

NAME JMcHale DATE 09/30/2015 LPL2-2 R/F RidsNrrDeEvib Resource RidsNrrDorl Resource RidsNrrLABClayton Resource RidsRgn2MailCenter Resource RidsNrrDorlDpr Resource JHauser, NRR CPfefferkorn, NRR 74

  • b 1vema11 NRR/DORL/LPL2-2/PM NRR/DORL/LPL2-2/LA FSaba (CPfefferkorn for)

BClayton (LRonewicz for) 10/5/2015 10/2/2015 NRR/DORL/LPL2-2/BC NRR/DORL/LPL2-2/PM SHelton (AHon for)

FSaba (CPfefferkorn for) 10/6/2015 10/6/2015 OFFICIAL RECORD COPY