UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 Mr. Thomas D. Gatlin Vice President, Nuclear Operations South Carolina Electric & Gas Company Virgil C. Summer Nuclear Station Post Office Box 88, Mail Code 800 Jenkinsville, SC 29065 May 19, 2015
SUBJECT:
VIRGIL C. SUMMER NUCLEAR STATION, UNIT NO. 1 - REQUEST FOR ADDITIONAL INFORMATION REGARDING ALTERNATIVE REQUEST (TAC NO. MF5612)
Dear Mr. Gatlin:
By letter dated January 20, 2015, the South Carolina Electric & Gas Company (SCE&G, the licensee) submitted an alternative request for Virgil C. Summer, Unit 1. SCE&G proposed to use a root mean square error criterion for sizing flaws that is greater than that allowed by American Society of Mechanical Engineers (ASME) Code for Reactor Pressure Vessel nozzles to safe-end cold leg welds.
The NRC staff has determined that additional information is needed to continue the review as discussed in the Enclosure. We request that SCE&G respond to these RAls within 30 days of the date of this letter. Please note that the NRC staff's review is continuing and further requests for information may be developed.
Docket No. 50-395
Enclosure:
Request for Additional Information cc w/encl: Distribution via Listserv Sincerely, Shawn Williams, Senior Project Manager Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
REQUEST FOR ADDITIONAL INFORMATION ALTERNATIVE REQUEST DEPTH SIZING ROOT MEAN SQUARE ERROR CRITERIA VIRGIL C. SUMMER NUCLEAR STATION, UNIT NO. 1 DOCKET NO. 50-395 The U.S. Nuclear Regulatory Commission (NRC) staff reviewed the South Carolina Electric &
Gas Company (SCE&G) alternative request, RR-4-07, dated January 20, 2015 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML15022A655), for the Virgil C. Summer Nuclear Station, Unit 1. The request pertains to Supplement 10, Appendix VII I of Section XI qualification requirements related to flaw depth sizing root mean square error (RMSE) criteria.
The NRC staff has determined that the following request for additional information (RAI) is required to complete its review.
RAI No.1 The NRC authorizes a proposed alternative pursuant to 10 CFR 50.55a(z)(1) only if the alternative is equivalent in quality to the ASME Code requirement. The NRC staff finds that the licensee's proposed alternative RMSE criteria in RR-4-07 is not equivalent in quality to the Supplement 10, Appendix VIII of Section XI requirements. Furthermore, the NRC staff has approved similar requests submitted in the past by other plants, under impractically in accordance with 10 CFR 50.55a(g)(6)(i). Therefore, the NRC staff suggests that the licensee revises RR-4-07 to state that the licensee is requesting relief pursuant to 10 CFR 50.55a(g)(5)(iii).
RAI No. 2 In the past, the NRC staff approved similar requests (e.g., Accession Nos. ML13064A425 and ML14073A544) provided that the licensee's proposed alternative also included the following compensatory measures.
If any cracks are detected and measured by Ultrasonic Testing (UT) as 50 percent through wall depth or greater, and to remain inservice without mitigation or repair, a flaw evaluation shall be performed and submitted for the NRC review and approval prior to reactor startup. The flaw evaluations shall include:
the inner profile of the weld, pipe, and nozzle in the region at and surrounding the flaw an estimate of the percentage of potential surface areas with UT probe lift-off information on mechanism which caused the crack If any cracks are detected and measured by the UT as less than 50 percent through wall depth, adding the industry proposed correction factor (procedure RMSE - 0.125 inch) to the depths of Enclosure any flaw found by the UT prior to flaw evaluation for flaws less than 50 percent through wall satisfactorily reduces the effect of the increased sizing error associated with not meeting the ASME Code required 0.125 inch RMSE.
The above measures will provide reasonable assurance of structural integrity of the examined welds. Therefore, the NRC staff suggests that the licensee revises RR-4-07 to include the above compensatory measures; or justify why these compensatory measures are not needed.
RAI No. 3 (a) Provide materials of construction for the subject pipes, elbows, and welds.
(b) Provide dimensions (e.g., wall thickness and diameter) for the subject welds.
(c) Provide a sketch of the welds.
Mr. Thomas D. Gatlin Vice President, Nuclear Operations South Carolina Electric & Gas Company Virgil C. Summer Nuclear Station Post Office Box 88, Mail Code 800 Jenkinsville, SC 29065 May 19, 2015
SUBJECT:
VIRGIL C. SUMMER NUCLEAR STATION, UNIT NO. 1 - REQUEST FOR ADDITIONAL INFORMATION REGARDING ALTERNATIVE REQUEST (TAC NO. MF5612)
Dear Mr. Gatlin:
By letter dated January 20, 2015, the South Carolina Electric & Gas Company (SCE&G, the licensee) submitted an alternative request for Virgil C. Summer, Unit 1. SCE&G proposed to use a root mean square error criterion for sizing flaws that is greater than that allowed by American Society of Mechanical Engineers (ASME) Code for Reactor Pressure Vessel nozzles to safe-end cold leg welds.
The NRC staff has determined that additional information is needed to continue the review as discussed in the Enclosure. We request that SCE&G respond to these RAls within 30 days of the date of this letter. Please note that the NRC staff's review is continuing and further requests for information may be developed.
Docket No. 50-395
Enclosure:
Sincerely, IRA/
Shawn Williams, Senior Project Manager Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Request for Additional Information cc w/encl: Distribution via Listserv DISTRIBUTION:
PUBLIC RidsNrrDorlDpr Resource RidsNrrLASFigueroa Resource ARezai, NRR ADAMS A ccess1on N o.:
OFFICE LPL2-1/PM NAME SWilliams DATE 4/30/15 LPL2-1 R/F RidsNrrDorllpl2-1 Resource RidsNrrDRA Resource ML15118A459 RidsAcrsAcnw_MailCTR Resource RidsRgn2MailCenter Resource RidsNrrPMSummer Resource
- b,yema1 LPL2-1/LA NRR/DE/EPNB/BC*
LPL2-1/BC LPL2-1/PM SFigueroa DAiiey RPascarelli SWilliams 4/30/15 4/29/15 5/14/15 5/19/15 OFFICIAL RECORD COPY