Text

Charles A. Pierce Southern Nuclear Regulatory Affairs Director Operating Company, Inc.

40 Inverness Center Parkway Post Office Box 1295 Birmingham, AL 35201 APR 0 2 2015 Tel 205.992.7872 Fax 205.992.7601 Docket Nos.:

50-425 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Vogtle Electric Generating Plant, Unit 2 Seventeenth Maintenance/Refueling Outage Steam Generator Tube Inspection Report Ladies and Gentlemen:

SOUTHERN A COMPANY NL-15-0596 In accordance with the requirements of Vogtle Electric Generating Plant Technical Specification 5.6.1 0, Southern Nuclear Operating Company submits this report of the steam generator tube inspections performed during the seventeenth Unit 2 maintenance/refueling outage {2R17). Entry into Mode 4 occurred on October 9, 2014.

This letter contains no NRC commitments. If you have any questions, please contact Ken McElroy at {205) 992-7369.

C. R. Pierce Regulatory Affairs Director CRP/EGA

Enclosure:

2R17 Steam Generator Tube Inspection Report

U. S. Nuclear Regulatory Commission NL-15-0596 Page 2 cc:

Southern Nuclear Operating Company Mr. S. E. Kuczynski, Chairman, President & CEO Mr. D. G. Bast, Executive Vice President & Chief Nuclear Officer Mr. D. A. Madison, Vice President - Fleet Operations Mr. M. D. Meier, Vice President - Regulatory Affairs Mr. B. K. Taber, Vice President - Vogtle 1 & 2 Mr. B. J. Adams, Vice President - Engineering Mr. G.W. Gunn, Regulatory Affairs Manager - Vogtle 1 & 2 RType: CVC7000 U. S. Nuclear Regulatory Commission Mr. V. M. McCree, Regional Administrator Mr. A. E. Martin, NRR Senior Project Manager-Vogtle 1 & 2 Mr. L. M. Cain, Senior Resident Inspector - Vogtle 1 & 2

Vogtle Electric Generating Plant-Unit 2 Seventeenth Maintenance/Refueling Outage Steam Generator Tube Inspection Report Enclosure 2R17 Steam Generator Tube Inspection Report

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Introduction The Vogtle Electric Generating Plant (VEGP) seventeenth Unit 2 maintenance/refueling outage (2R17) was conducted in September 2014 after cumulative Steam Generator (SG) service equivalent to approximately 1.4 effective full power years (EFPY) from the previous eddy current inspections. No tube leakage was reported during this operating interval. At the start of VEGP 2R17, approximately 51.9 effective full power months (EFPM) of the 72 EFPM in the fourth sequential inspection period have accrued making 2R17 the second to last inspection of the period. Analyses based on conservative assumptions used in Condition Monitoring (CM) and Operational Assessments demonstrated that there were no tubes that exceeded Regulatory Guide (RG) 1.121 or Nuclear Energy Institute (NEI) Topical Report 97-06, Revision 3, criteria for tube integrity during fuel cycle 17. The eddy current inspections were performed by the Steam Generator Maintenance Services Group of the Westinghouse Nuclear Services Division.

Secondary data analysis was performed by NDE Technology under direct contract with Southern Nuclear Operating Company (SNC). No tubes required plugging in any of the four SGs inspected, and no tubes required in situ pressure testing. Permanent H* Alternate Repair Criteria (ARC) were approved by the NRC for implementation. Therefore, tube end +Point inspections below top of tubesheet (TIS) -15.2 inches were omitted, and the TIS inspections ranged from TIS +3 inches to TIS -15.2 inches. The scope of the inspections performed on each SG, and the results of those inspections, are described below.

2R17 SG Inspection Program -Primary Side Base Scope The inspection program, required by Revision 7 of the Electric Power Research Institute (EPRI)

Pressurized Water Reactor (PWR) SG Examination Guidelines, addressed the known degradation mechanisms observed in VEGP Unit 2 in prior inspections as well as those regarded as potential degradation mechanisms. The inspection program implemented during VEGP 2R17 is listed below.

100% Bobbin examination of tubes in SGs 1 and 4, full length except for Rows 1 and 2, which were inspected from tube end to the top tube support plate (TSP) from both the hot leg (HL) and cold leg (CL).

50% Rotating Pancake Coil (RPC), also known as "Plus Point/+Point, examination of Row 1 and Row 2 U-bends in SG1 and SG4 from the top TSP on the HL to the top TSP on the CL.

The sample was taken from the Row 1 and Row 2 U-bends not inspected in SG1 and SG4 during 2R15.

RPC Examination of Special Interest (possible flaw locations found with bobbin coil probe) including U-bends in both the HL and CL.

100% RPC examination of HL tubes in SG2 and 50% in SG1, SG3 and SG4 from three inches above the TIS to the licensed ARC depth for H* (TIS +3/-15.2 inches).

50% of the HL tube bulge (BLG) and overexpansion (OXP) populations in SG1 and SG4, defined as follows:

o Bulge: differential mix diameter discontinuity signal within the tubesheet of 18 volts or greater as measured by bobbin coil probe.

o Overexpansion: a tube diameter deviation within the tubesheet of 1.5 mils or greater as measured by bobbin coil probe.

E-1

Enclosure to N L 0596 2R17 Steam Generator Tube Inspection Report 50% RPC examination of dents and dings 9 2 volts in HL straight lengths and U-bends of SG 1 and SG4. This sample was taken from the total number of dents and dings identified during previous inspections and any additional identified by the bobbin program.

1 00% visual inspection of HL and CL installed tube plugs from the primary side in all four SGs.

Visual inspection in all SGs of channel head primary side HL and CL in accordance with Westinghouse Letter NSAL 12-1, "Steam Generator Channel Head Degradation" inclusive of the entire divider plate to channel head weld and all visible clad surfaces.

In addition, bobbin inspections were performed for tube slippage monitoring.

Inspection Expansion There was no Non-Destructive Examination (NDE) inspection scope expansion required during the VEGP 2R17 SG in-service inspections.

Damage Mechanisms Found and NDE Techniques Utilized All of the damage mechanisms found during 2R17 inspections were identified in previous inspections and in the 2R17 SG Degradation Assessment. Based on SG eddy current and visual inspection data, the existing degradation mechanisms in the VEGP Unit 2 SGs are described below.

Circumferential Outer Diameter Stress Corrosion Cracking (ODSCC) at Hot Leg Expansion Transitions o

+Point techniques were used to evaluate the indications Mechanical Wear due to Foreign Objects o

+Point and bobbin techniques were used to evaluate the wear indications Mechanical Wear at Anti-Vibration Bar (AVB) Supports o

Bobbin techniques were used to evaluate the wear indications Mechanical Wear and Wall Loss from Secondary Side Cleaning Processes o

Bobbin techniques were used to evaluate the wear indications Observed tube degradation indications were monitored and assessed to confirm the SG integrity performance criteria. The following sections discuss indications identified during the inspection.

Service Induced Indication Descriptions Mechanical Wear due to Foreign Objects Foreign objects were reported as the cause for tube wear at VEGP Unit 2 during prior inspections; therefore, wear due to foreign objects is classified as an existing degradation mechanism and has been addressed in the SG inspections during 2R17.

E-2

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Historical Possible Loose Part (PLP) signals were visually inspected during prior outages but show no significant change in eddy current signal response, and therefore, the SGs did not require a secondary side inspection during 2R17. No new foreign object wear associated with known foreign objects in the SG secondary side was observed. Historical indications in SG 1 and SG2 have been determined to be no more likely than any of the others to be affected by foreign objects during future operation.

The foreign object wear (PCT) indications in SG1 tubes R47C84 and R47C85 have been present for several cycles with no apparent growth or change in character. The PCT indications in SG 4 in tubes R12C57 and R42C93 show no change in sizing result from the prior inspection.

Based on the inspection data, the observed indications did not exceed the condition monitoring limits and did not require in-situ proof of pressure and leakage testing to demonstrate tube integrity.

Table 1 VEGP Unit 2 PLP/PC T for 2R17 SG Row Column Indication 1

49 86 PLP 1

49 86 PLP 1

48 86 PLP 1

48 86 PLP 1

48 86 PLP 1

47 85 PCT 1

47 84 PCT 2

1 118 PLP 2

33 50 PLP 2

32 50 PLP 2

32 49 PLP 2

31 49 PLP 4

12 57 PCT 4

42 93 PCT

% lWD - Percent Through-wall Depth PLP - Possible Loose Part PCT - Foreign Object Wear TSH - Tubesheet region on HL side TSC - Tubesheet region on CL side

%TWO 9

11 20 24 Mechanical Wear at Anti-Vibration Bar (AVB) Supports Location TSH +0.38 TSH +0.42 TSH +0.36 TSH +0.14 TSH +0.31 TSH +0.07 TSH +0.09 TSH +0.04 TSH +0.18 TSH +0.65 TSH +1.34 TSH +1.57 TSH +0.40 TSC +0.89 All AVB wear locations were examined in SG 1 and SG4. None of the wear locations exceeded the technical specification plugging limit of 40% through-wall. The corresponding inspection of AVB wear locations in SG2 and SG3 was last performed during 2R16, and the results were assessed for operation through 2R18. Based on the inspection data, Condition Monitoring was met in 2R17. None of the indications exceeded the condition monitoring limits and therefore did not require in-situ pressure and leakage testing to demonstrate tube integrity. AVB wear identified is provided in Table 2 (SG1) and Table 3 (SG4).

E-3

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Table 2 VEGP 2R17 SG1 AVB Wear Indications Row Column Location1 2R17% TWO Row Column 29 105 AV2 10 44 94 29 112 AV2 12 46 24 30 10 AV2 10 46 26 30 10 AV6 13 46 27 32 17 AV5 14 46 32 32 106 AV5 13 46 32 34 13 AV2 13 46 32 34 13 AV4 14 46 43 34 25 AV1 9

47 27 35 14 AV4 14 47 36 35 74 AV4 16 47 36 37 33 AV3 10 47 36 37 35 AV3 11 47 99 37 39 AV4 9

47 99 41 20 AV1 8

48 27 41 20 AV2 20 48 27 41 20 AV3 12 48 28 41 20 AV4 16 48 96 41 20 AV5 17 49 29 41 20 AV6 9

49 36 41 21 AV3 13 49 36 41 23 AV5 14 50 29 41 23 AV6 10 50 92 41 27 AV5 14 50 93 42 20 AV2 21 53 33 43 21 AV3 11 53 34 43 21 AV4 11 53 34 43 100 AV2 15 53 89 43 100 AV3 19 54 50 43 100 AV4 22 54 50 43 100 AV5 13 54 50 44 22 AV4 16 55 39 44 22 AV6 13 55 39 44 23 AV2 12 55 78 44 23 AV3 19 55 81 44 23 AV4 15 58 53 44 23 AV5 25 58 72 44 27 AV2 11 58 73 44 27 AV3 17 58 75 44 27 AV5 11 59 68 44 72 AV6 12 1AV# - Location of AVB intersection with the tube (there are up to 6)

% TWO-Percent Through-wall Depth E-4 Location1 2R17% TWD AV5 14 AV4 17 AV4 19 AV2 13 AV3 15 AV4 17 AV5 14 AV2 14 AV2 24 AV1 11 AV3 14 AV4 11 AV2 15 AV5 14 AV2 11 AV3 19 AV2 18 AV2 9

AV6 12 AV2 19 AV5 27 AV5 20 AV2 14 AV3 14 AV4 18 AV3 14 AV4 13 AV5 14 AV2 14 AV3 14 AV4 12 AV2 9

AV3 12 AV1 8

AV2 10 AV1 12 AV1 13 AV1 11 AV6 16 AV1 13

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Table 3 VEGP 2R17 SG4 AVB Wear Indications Row Column Location1 2R17% TWO Row Column 15 36 AV6 8

43 58 15 46 AV1 7

43 65 27 79 AV5 9

43 68 29 14 AV6 9

43 68 30 9

AV5 22 43 68 31 10 AV5 14 43 69 32 109 AV6 10 43 71 34 81 AV1 8

43 76 35 81 AV1 9

43 85 36 14 AV2 13 43 95 37 74 AV3 12 43 95 37 79 AV1 8

43 95 37 81 AV1 9

44 29 37 87 AV2 12 44 29 38 39 AV4 10 44 29 38 79 AV1 9

44 42 38 81 AV1 9

44 42 39 26 AV3 10 44 42 39 64 AV1 19 44 42 39 64 AV2 25 44 44 39 64 AV3 32 44 53 39 64 AV4 16 44 53 39 64 AV5 16 44 54 39 64 AV6 26 44 54 40 79 AV1 8

44 54 40 106 AV1 10 44 59 40 106 AV3 11 44 59 42 51 AV6 11 44 59 42 87 AV3 10 44 85 43 21 AV4 15 45 22 43 21 AV5 12 45 22 43 21 AV6 12 45 23 43 22 AV4 15 45 23 43 35 AV2 14 45 23 43 36 AV2 14 45 32 43 47 AV2 13 45 42 43 51 AV6 11 45 42 43 53 AV3 9

45 58 43 58 AV4 9

45 58 1AV# - Location of AVB intersection with the tube (there are up to 6)

% TWO-Percent Through-wall Depth E-5 Location1 2R17% TWO AV5 7

AV4 16 AV3 24 AV4 28 AV5 27 AV5 19 AV4 13 AV5 20 AV4 12 AV3 17 AV4 14 AV5 12 AV3 17 AV4 17 AV5 12 AV3 15 AV4 18 AV5 25 AV6 16 AV3 21 AV3 10 AV5 12

.AV1 11 AV2 16 AV5 26 AV1 14 AV3 18 AV4 15 AV3 10 AV2 9

AV3 12 AV2 10 AV3 10 AV5 9

AV3 22 AV4 30 AV5 13 AV3 25 AV4 10

Enclosure to N L ² 15³0596 2R17 Steam Generator Tube Inspection Report Table 3 (Continued)

VEGP 2R17 SG4 AVB Wear Indications Row Column Location1 2R17% TWO Row Column 45 58 AV5 15 51 35 45 66 AV2 18 51 37 45 66 AV3 19 51 39 45 66 AV5 22 51 39 46 26 AV4 13 51 39 46 26 AV6 15 51 43 46 31 AV2 10 51 43 46 31 AV3 26 51 43 46 31 AV4 14 51 54 46 31 AV5 19 51 54 46 51 AV6 11 51 54 46 88 AV3 10 51 55 47 33 AV5 12 51 55 47 36 AV4 11 51 55 47 36 AV6 13 51 60 47 41 AV2 15 51 65 47 41 AV3 13 51 65 48 31 AV3 10 51 76 48 31 AV4 13 51 76 48 57 AV3 13 51 76 48 57 AV4 13 51 92 48 57 AV5 19 52 33 48 58 AV4 7

52 33 48 79 AV2 10 52 33 48 79 AV3 8

52 33 48 81 AV1 7

52 33 48 97 AV2 11 52 45 48 97 AV3 13 52 45 49 53 AV3 11 52 45 49 53 AV4 11 52 45 49 58 AV4 10 52 66 49 83 AV3 16 52 66 49 93 AV4 20 52 66 49 93 AV5 26 52 71 49 96 AV2 12 52 71 50 53 AV3 8

52 71 50 55 AV3 7

52 72 50 70 AV3 20 52 72 51 31 AV4 15 52 78 1AV# ' Location of AVB intersection with the tube (there are up to 6)

% TWO' Percent Through'wall Depth E'6 Location1 2R17% TWD AV4 19 AV4 13 AV2 13 AV3 14 AV4 18 AV3 12 AV4 15 AV5 16 AV3 11 AV4 20 AV5 12 AV2 15 AV3 23 AV5 12 AV3 13 AV4 18 AV5 20 AV2 15 AV4 20 AV5 24 AV1 12 AV2 19 AV3 19 AV4 19 AV5 39 AV6 17 AV2 14 AV3 22 AV4 21 AV5 14 AV1 12 AV2 23 AV3 14 AV1 10 AV2 21 AV3 24 AV2 29 AV3 13 AV4 15

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Table 3 (Continued)

VEGP 2R17 SG4 AVB Wear Indications Row Column Location1 2R17% TWO Row Column 52 85 AV1 8

58 75 53 34 AV2 11 59 63 53 34 AV6 11 59 66 53 36 AV5 14 53 36 AV6 12 53 44 AV3 17 53 74 AV4 18 53 80 AV5 16 53 89 AV6 11 54 35 AV4 11 54 35 AV5 19 54 35 AV6 12 54 37 AV1 12 54 37 AV6 12 54 83 AV5 11 55 41 AV5 15 55 83 AV5 13 56 42 AV5 13 56 42 AV6 13 56 45 AV4 16 56 45 AV5 12 56 47 AV3 20 56 76 AV5 12 56 82 AV2 14 56 82 AV6 10 57 48 AV2 18 57 48 AV3 23 57 48 AV4 18 57 48 AV5 37 57 48 AV6 15 57 71 AV6 13 57 73 AV2 15 57 76 AV5 16 57 78 AV2 15 57 78 AV4 12 57 78 AV6 14 58 47 AV5 13 58 47 AV6 14 1 AV# - Location of AVB intersection with the tube (there are up to 6)

% TWO-Percent Through-wall Depth E-7 Location1 2R17% TWO AV2 13 AV6 11 AV6 14

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Mechanical Wear and Wall Loss from Secondary Side Cleaning The tube locations and volumetric indications associated with the ultrasonic energy cleaning (UEC) and pressure pulse cleaning (PPC) secondary side cleaning processes for SG1 are listed in Table 4. The examinations required to be performed to address this existing degradation mechanism are an element of the bobbin inspection program which alternates between two SGs each inspection. Since 100% bobbin inspections in SG1 and SG4 were scheduled, only the tubes listed in SG1 were required to be examined during 2R17.

The volumetric indications reported in Row 1 tubes were also observed by visual inspection in prior outages. They were reported to visually resemble tube oxide removal patterns observed in qualification testing for UEC. No foreign objects were determined to be associated with these tube wear indications. These tubes were left in service for several inspection intervals with no indications of tube wall loss outside of NDE measurement uncertainties. Based on the inspection data, the indications did not exceed the condition monitoring limits and did not require in-situ proof of pressure and leakage testing to demonstrate tube integrity.

Table 4 VEGP Unit 2 Tube Wear and Wall Loss from Secondary Side Cleaning for 2R17 ODSCC SG Row Column Indication 1

1 42 PCT 1

1 45 PCT 1

1 46 PCT 1

1 78 PCT 1

1 78 PCT 1

1 78 PCT

% lWD - Percent Through-wall Depth PCT - Foreign Object Wear TSH - Tubesheet region on HL side TSC - Tubesheet region on CL side

%TWO Location 10 TSH +10.25 11 TSH +10.13 20 TSH +10.29 17 TSH +9.63 12 TSH+11.44 28 TSC +11.63 ODSCC at the hot leg expansion transitions is an existing degradation mechanism for VEGP Unit 2. This mechanism was considered in the VEGP 2R17 eddy current inspection scope development. There were no ODSCC indications reported at or near the top of the tubesheet hot leg expansion transitions from RPC inspection during VEGP 2R17.

Number of Tubes Plugged A 100% visual inspection of tube plugs in all four SGs was performed from the primary side during VEGP 2R17. There were no anomalous conditions, degraded tube plug or surrounding boron deposits reported during performance of the visual inspections.

No tubes were plugged in any of the four SGs during VEGP 2R17. The status of tubes plugged at VEGP Unit 2 after the outage remains as follows {Table 5):

E-8

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report Table 5 Total Plugged Tubes after VEGP 2R17 SG#

  1. Tubes 2R17 #Plugged Total # Plugged

%Plugging 1

5,626 0

6 0.11%

2 5,626 0

15 0.27%

3 5,626 0

5 0.09%

4 5,626 0

22 0.39%

Total 22,504 0

48 0.21%

Tube Axial Displacement (Slippage) Monitoring The bobbin data collected from SG1 and SG4 was screened for large amplitude tubesheet indications of greater than 50 volts with a phase angle between 25° and 50° suggestive of tube severance. No tube severance indications were reported; therefore, no indications of slippage were identified. None of the indications reported during the VEGP 2R17 SG inspections are evaluated to have primary to secondary leakage as accident induced conditions. There was no leakage from the portion of tubing within the H* depth for which to apply the leak rate factor associated with the alternate repair criteria. There was no calculated leakage from any other sources and none of the tube plugs installed in the VEGP Unit 2 SGs require considerations for leakage. Therefore, the accident induced leakage rate for these indications would be zero, and the accident induced leakage performance criterion is satisfied.

Other inspections SG Channel Head Primary Side Bow/Inspection A visual inspection of the SG channel head bowl in the vicinity of the drain line was performed in all SGs during VEGP 2R17. Visual inspections were performed of the SG hot leg and cold leg divider plate and drain line areas, inclusive of the entire divider plate to channel head weld and all visible clad surfaces. SG manway channel head bowl inspection was performed using cameras. Satisfactory inspection results were observed in all SGs; no unacceptable degradation was found.

Secondary Side Discussion The 1 00% bobbin full length inspection program in SG 1 and SG4, the 1 00% RPC Hot Leg TIS

+3/-15.2 inches in SG2, and the 50% RPC Hot Leg TIS +3/-15.2 inches in SG 1, SG3 and SG4 are adequate to address the potential for secondary side foreign object wear. All PLP calls identified during the eddy current program are historical, have been visually inspected during prior outages, show no significant change in eddy current signal response and therefore did not require a secondary side inspection during 2R17. No new foreign object wear indications associated with known foreign objects in the SG secondary side were detected during 2R17.

Condition Monitoring Conclusions Based on the inspection data and the condition monitoring assessment, no tubes exhibited degradation in excess of the condition monitoring limits. No tubes required in situ pressure testing to demonstrate structural and leakage integrity. No tubes required plugging in any of the four SGs inspected. There was no SG primary to secondary leakage prior to the end of the inspection interval. No secondary side tube degradation attributable to known foreign objects was identified (all PLPs identified have been confirmed as historical and unchanged). There was no recurrence of ODSCC at the hot leg tubesheet expansion transitions during 2R17 after one operating cycle since the initial observation in SG2. The condition monitoring limits, and correspondingly, the SG performance criteria for operating leakage and structural integrity were E-9

Enclosure to NL-15-0596 2R17 Steam Generator Tube Inspection Report satisfied for the preceding VEGP Unit 2 SG operating interval. None of the indications reported during the VEGP 2R17 SG inspections were evaluated to have primary to secondary leakage as accident induced conditions.

E-10