ML15089A436

From kanterella
Jump to navigation Jump to search
Part-21 Report - Valve Seat Leakage Defect
ML15089A436
Person / Time
Site: Saint Lucie, Waterford  NextEra Energy icon.png
Issue date: 03/21/2015
From: Swanson D
Emerson Process Management
To: Huffman W
Office of Nuclear Reactor Regulation, NRC/RGN-III
References
50911
Download: ML15089A436 (5)


Text

0312112615 Pnap I

03/21/2015 U.S. Nuclear Repulatnrv Conmmksinn flnerations. Center Event Ronnrt pay" 1----------------------

Part 21 (PAR)

Event#

50911 Rep Org: EMERSON PROCESS MANAGEMENT Notification Date I Time: 03/20/2015 14:49 (EDT)

Supplier: FISHER CONTROLS INTERNATIONAL LLC Event Date I Time: 06/06/2014 (CDT)

Last Modification: 03/20/2015 Region:

3 Docket #:

City:

MARSHALLTOWN Agreement State:

Yes County:

License #:

State:

IA NRC Notified by: DENNIS SWANSON Notifications: GREGORY ROACH R3DO HQ Ops Officer: MARK ABRAMOVITZ BINOY DESAI R2DO Emergency Class: NON EMERGENCY HEATHER GEPFORD R4DO 10 CFR Section:

PART 21/50.55 REACTORS EMAIL 21.21(d)(3)(i)

DEFECTS AND NONCOMPLIANCE 50.55(e)

CONSTRUCT DEFICIENCY PART-21 REPORT - VALVE SEAT LEAKAGE DEFECT The following is a summary of a submitted facsimile:

"A valve plug originally supplied as a spare parts order was returned to Fisher after the customer discovered a machining error was present on the plug. The Type 461 valve plug has a groove machined across the seating surface of the plug. This groove is required to provide a controlled leak rate thru the valve when the plug is on the seat. The issue recently identified shows that the machined groove did not extend through the full length of the seat. This could lead to a situation in which the intended/required leakage for this design is not fully achieved."

Affected plants are: Waterford-3 and St Lucie.

Mar, 20. 2015 1:13PM EMERSON.

Process Management No. 0375 P. 1

[FISHE]

Facsimile 301 South First Ave Marshalltown, IA 50158 T 641-754-3011 F 641-754-2830 To':

NRC Operations Center - Alln: Bill Huffman Fax:

301-816-5151 From:

Dennis Swanson, Emerson Process Management Date:

03120/20 15 Pages:

4 (in ci cover)

Attachment:

Fisher Information Notice - (FIN) 2015-01 For technical questions please contact Dennis Swanson at (641) 754-2381.

Mar. 20.

2015 1:13PM EMERSON.

Process Management No. 0375 P. 2 Fisher Controls International LLC 301 South First Ave.

P.O. Box i90 Marshalltown, Iowa 50158-0190 USA T (641) 754-3011 F (641) 754-2830 March 20, 2015 To Whom It May Concern:

Attached is a Fisher Information Notice, (FIN) 2015-01.

Emerson Process Management - Fisher Valves complies with the reporting requirements of 10 CFR Part 21 Section 21.21 (b) and 10 CFR Part 50.55 (e) by informing the U.S. Nuclear Regulatory Commission Licensees or Purchaser of deviations or failures to comply.

Please review the attached FIN notice for applicability to your facility.

Dennis Swanson Director, Quality Valve Division - Americas Attachments (FISHER]

Mar.2Q. 2015 1:13PM No, 0375 P. 3 4

EMERSON.

Process Management Fisher Information Notice: FIN 2015-01 18 March 2015 Subiect: Fisher Type 461 Valve Plug Machining From:

Chad Engle Director, Nuclear Business Unit Fisher Controls International LLC 301 South 1st Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Fisher Controls International LLC 301 South First Ave.

P.O. Box 190 Marshalltown, Iowa 50158-0190 USA T (641) 754-3011 F (641) 754-2830 Equipment Affected By This Information Notice:

The equipment affected by this FIN notice are replacement Valve Plug/Stem Assemblies for Type 461 valves supplied under the following machining drawing numbers: 25A0413, 29A7841 or 27B5132. Fisher records indicate two sites were supplied the potentially affected assemblies.

Entergy Waterford 3:

Waterford PO:

FPL St. Lucie:

St. Lucie PO's:

29A7841X052 10297987 25A0413X112,25A0413X122,25A0413X142, 25A0413X162 and 27B5132X022 55205, 00109494 Rev 3, 02318525 Rev 2

Purpose:

The purpose of this Fisher Information Notice(FIN) is to alert Entergy and Florida Power and Light that as of 6 June 2014, Fisher Controls International LLC ("Fisher')

became aware of the possibility of a situation which may affect the performance of the applicable equipment.

Fisher is informing the NRC 'of this circumstance in accordance with Section 21.21(b) of 10CFR Part 21.

[FISHER Page 1

Mar.20. 2015 1:13PM No, 0375 P. 4 Fisher Information Notice: FIN 2015-01 Applicability:

This notice applies only to the subject equipment supplied by Fisher as identified above.

Discussion:

A valve plug originally supplied as a spare parts order was returned to Fisher after the customer discovered a machining error was present on the plug. The Type 461 valve plug has a groove machined across the seating surface of the plug. This groove is required to provide a controlled leak rate thru the valve when the plug is on the seat.

The issue recently identified shows that the machined groove did not extend through the full length of the seat. This could lead to a situation in which the intended I required leakage for this design is not fully achieved.

Action Required: Evaluate any affected Type 461 valve plugs in inventory to ensure the machined groove extends across the plug seating area.


U-- ----------------

VEE 6ROOVE

.A.------

Fisher is revising the affected drawings for increased clarity and implementing appropriate corrective actions per CAR 1727.

IOCFR2I Implications:

Fisher requests that the recipient of this notice review it and take appropriate action in accordance with I OCFR Part 21.

If there are any technical questions or concerns, please contact:

Benjamin Ahrens Manager, Quality Fisher Controls International LLC 301 South 1SIt Avenue Marshalltown, IA 50158 Fax: (641) 754-2854 Phone: (641) 754-2249 Beniamin.Ahrens(@Einerson.com Lln.

E!

!H 0

rn*u

_ uI tn.