Regulatory Conference with Entergy Operations, Inc
ML15082A444
Person / Time
Site: Waterford 
Issue date: 03/23/2015
From: John Dixon
Region 4 Engineering Branch 1
To:
References
EA-14-228
Download: ML15082A444 (5)


Text

March 23, 2015

SUBJECT:

REGULATORY CONFERENCE WITH ENTERGY OPERATIONS, INC.

FACILITY:

Waterford Steam Electric Station, Unit 3 DOCKET:

50-382 EA:

14-228 DATE & TIME:

Tuesday, April 7, 2015 9:00 a.m. - 12:00 p.m. (CDT)

LOCATION:

U.S. Nuclear Regulatory Commission Region IV Office Conference Room 2 1600 E. Lamar Blvd.

Arlington, TX 76011 PURPOSE:

The purpose of this regulatory conference is to discuss a finding and apparent violation identified at Waterford Steam Electric Station, Unit 3.

This finding is associated with through-wall corrosion of vent piping for emergency diesel generator fuel oil day tanks. The holes in these vent pipes could allow water to enter the day tanks and contaminate the diesel fuel oil, challenging the operability and functionality of both safety-related emergency diesel generators. The apparent violation is discussed in NRC Inspection Report 05000382/2014007, dated January 22, 2015 (ADAMS Accession No. ML15022A637).

CATEGORY:

This is a Category 1 meeting. The public is invited to observe this meeting. After the business portion, but before the meeting is adjourned, the public will have one or more opportunities to communicate with the Nuclear Regulatory Commission.

A telephone bridge will be available for the public. Interested parties should call 888-957-9871 and enter passcode 2489913 to participate in this meeting.

UNITED STATES NUCLEAR REGULATORY COMMISSION REGION IV 1600 E. LAMAR BLVD ARLINGTON, TX 76011-4511

Waterford Steam Electric Station, Unit 3 PARTICIPANTS:

NRC M. Dapas, Regional Administrator, Region IV A. Vegel, Director, Division of Reactor Safety E. Ruesch, Acting Chief, Engineering Branch 1, Division of Reactor Safety R. Lantz, Chief, Branch E, Division of Reactor Projects N. Taylor, Acting Lead, Allegation Coordination and Enforcement Staff C. Maier, Enforcement Specialist J. Dixon, Senior Reactor Inspector LICENSEE M. Chisum, Entergy, Waterford 3 R. Gilmore, Entergy, Waterford 3 J. Clavelle, Entergy, Waterford 3 B. Lanka, Entergy, Waterford 3 J. Walker, Jensen-Hughes M. Chase, Entergy, Waterford 3 MEETING CONTACT:

John Dixon, NRC, RIV (817) 200-1434 John.Dixon@nrc.gov The NRC provides reasonable accommodation to individuals with disabilities where appropriate.

If you need a reasonable accommodation to participate in this meeting, or need this meeting notice or the transcript or other information from the meeting in another format (e.g., braille, large print), please notify the NRC's meeting coordinator. Determinations on requests for reasonable accommodation will be made on a case-by-case basis.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice and Procedure," a copy of this notice and its enclosure will be available electronically for public inspection in the NRC's Public Document Room or from the Publicly Available Records (PARS) component of the NRC's Agencywide Documents Access and Management System (ADAMS). ADAMS is accessible from the Public Electronic Reading Room page of the NRC's public web site at http://www.nrc.gov/reading-rm/adams.html.

Enclosure:

Agenda cc w/enclosure: Electronic Distribution

ML15082A444 SUNSI Review By: MSH ADAMS Yes No Publicly Available Non-Publicly Available Non-Sensitive Sensitive Keyword:

RGN-002 OFFICE RIV:DRS/EB1 TL:ACES C:EB1 RSLO PAO D:DRS NAME JDixon NTaylor ERuesch WMeier VDricks AVegel SIGNATURE

/RA/

/RA/

/RA/

/RA/

/RA/

/RA/

DATE 3/23/15 3/23/15 3/23/15 3/23/15 3/23/15 3/23/15

Meeting Notice to the Public from Region IV, dated March 23, 2015

SUBJECT:

REGULATORY CONFERENCE WITH ENTERGY OPERATIONS, INC.

Electronic distribution by RIV:

Regional Administrator (Marc.Dapas@nrc.gov)

Deputy Regional Administrator (Kriss.Kennedy@nrc.gov)

DRP Director (Troy.Pruett@nrc.gov)

Acting DRP Deputy Director (Thomas.Farnholtz@nrc.gov)

DRS Director (Anton.Vegel@nrc.gov)

DRS Deputy Director (Jeff.Clark@nrc.gov)

Senior Resident Inspector (Frances.Ramirez@nrc.gov)

Resident Inspector (Chris.Speer@nrc.gov)

WAT Administrative Assistant (Linda.Dufrene@nrc.gov)

Branch Chief, DRP/E (Ryan.Lantz@nrc.gov)

Senior Project Engineer, DRP/E (Cale.Young@nrc.gov)

Project Engineer, DRP/E (Jim.Melfi@nrc.gov)

Public Affairs Officer (Victor.Dricks@nrc.gov)

Public Affairs Officer (Lara.Uselding@nrc.gov)

Project Manager (Michael.Orenak@nrc.gov)

Branch Chief, DRS/TSB (Geoffrey.Miller@nrc.gov)

RITS Coordinator (Marisa.Herrera@nrc.gov)

ACES (R4Enforcement.Resource@nrc.gov)

Regional Counsel (Karla.Fuller@nrc.gov)

Congressional Affairs Officer (Jenny.Weil@nrc.gov)

Technical Support Assistant (Loretta.Williams@nrc.gov)

RIV Congressional Affairs Officer (Angel.Moreno@nrc.gov)

RIV/ETA: OEDO (Michael.Waters@nrc.gov)

RIV Guards (R4-Guards@nrc.gov)

Branch Chief, DRMA/AMB (Earnestine.Clay@nrc.gov)

Branch Chief, DRMA/IRMB (Harold.McElevey@nrc.gov)

DRMA/AMB Administrative Specialist (AnnMarie.Matilla@nrc.gov Support Services Assistant (Stacey.Munroe@nrc.gov)

Administrative Assistant (Anita.Tannenbaum@nrc.gov)

Administrative Assistant (Jenny.Murray@nrc.gov)

Add to Addressee List:

Institute of Nuclear Power Operations (INPO)

Records Center 700 Galleria Parkway SE, Suite 100 Atlanta, GA 30339

Enclosure AGENDA REGULATORY CONFERENCE ENTERGY OPERATIONS, INC.

WATERFORD STEAM ELECTRIC STATION, UNIT 3 April 7, 2015 9 a.m. - 12 p.m. (CDT)

U.S. NRC, Region IV Office Arlington, TX Topic Participant(s)

Introduction Eric Ruesch Regional Administrator Comments Marc Dapas Licensee Opening Remarks Entergy Operations, Inc.

Summary of Apparent Violation John Dixon Licensee Presentation Entergy Operations, Inc.

Questions and Discussion All NRC Caucus All NRC Questions and Discussion All Closing Remarks Marc Dapas/Anton Vegel Conference Adjournment Eric Ruesch