Text
1 NRR-PMDAPEm Resource From:
Saba, Farideh Sent:
Tuesday, March 03, 2015 9:30 AM To:
Cross, William (WILLIAM.CROSS@fpl.com)
Cc:
ken.frehafer@fpl.com; Lewis, Atanya (Atanya.Lewis@fpl.com); Moulton, Charles; Helton, Shana
Subject:
NEW St. Lucie FPE RAI 12 Attachments:
St Lucie FPE RAI 12.docx Importance:
High Bill, Attached is a request for additional information (RAI) related to Fire Protection Engineering regarding Florida Power and Light Company license amendment request for transitioning to National Fire Protection Association 805. I emailed you draft RAI 12 on February 6, and we discussed it during the clarification call on February 9, 2015. Per our discussions, you agreed to provide a response to this RAI by March 11, 2015. Also, you agreed with the staff determination that RAI 12 does not contain any sensitive information.
Thank you, Farideh Farideh E. Saba, P.E.
Senior Project Manager NRC/ADRO/NRR/DORL 301-415-1447 Mail Stop O-8G9A Farideh.Saba@NRC.GOV Tracking:
2 Recipient Read Cross, William (WILLIAM.CROSS@fpl.com) ken.frehafer@fpl.com Lewis, Atanya (Atanya.Lewis@fpl.com)
Moulton, Charles Helton, Shana Read: 3/3/2015 9:34 AM
Hearing Identifier:
NRR_PMDA Email Number:
1920 Mail Envelope Properties (308151458A298A44A2B1B8E880882DE10119E20847E4)
Subject:
NEW St. Lucie FPE RAI 12 Sent Date:
3/3/2015 9:29:46 AM Received Date:
3/3/2015 9:29:00 AM From:
Saba, Farideh Created By:
Farideh.Saba@nrc.gov Recipients:
"ken.frehafer@fpl.com" <ken.frehafer@fpl.com>
Tracking Status: None "Lewis, Atanya (Atanya.Lewis@fpl.com)" <Atanya.Lewis@fpl.com>
Tracking Status: None "Moulton, Charles" <Charles.Moulton@nrc.gov>
Tracking Status: None "Helton, Shana" <Shana.Helton@nrc.gov>
Tracking Status:: Response: Read : 3/3/2015 9:34:00 AM "Cross, William (WILLIAM.CROSS@fpl.com)" <WILLIAM.CROSS@fpl.com>
Tracking Status: None Post Office:
HQCLSTR02.nrc.gov Files Size Date & Time MESSAGE 752 3/3/2015 9:29:00 AM St Lucie FPE RAI 12.docx 20993 Options Priority:
High Return Notification:
No Reply Requested:
Yes Sensitivity:
Normal Expiration Date:
Recipients Received:
Additional St. Lucie RAI Fire Protection Engineering (FPE) RAI 12 10 CFR 50.48(c)(2)(vii) requires, in part, that performance-based alternatives used to demonstrate compliance with National Fire Protection Association Standard 805 (NFPA 805)
Chapter 3 elements maintain fire protection defense-in-depth.
The NRC staff has determined that there is insufficient detail regarding defense in depth to form a conclusion for license amendment request Attachment L Approval Requests 4 (NFPA 805 section 3.3.5.2) and 5 (NFPA 805 section 3.3.12(1)).
Provide additional detail regarding how each echelon of defense in depth is maintained for these two approval requests.
Also provide revised LAR Attachment L Approval Requests if appropriate.