ULNRC-06169, Response to Request for Additional Information Round 3 Application for Amendment to Revision Final Safety Analysis Report Standard Plant Section 3.6 for High Density Polyethylene Pipe Crack Exclusion

From kanterella
(Redirected from ML15034A615)
Jump to navigation Jump to search

Response to Request for Additional Information Round 3 Application for Amendment to Revision Final Safety Analysis Report Standard Plant Section 3.6 for High Density Polyethylene Pipe Crack Exclusion
ML15034A615
Person / Time
Site: Callaway 
Issue date: 02/03/2015
From: Maglio S
Ameren Missouri, Union Electric Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LDCN 13-0016, TAC MF3202, ULNRC-06169
Download: ML15034A615 (9)


Text

~~

iiWAmeren MISSOURI Callaway Plant February 3, 2015 ULNRC-06169 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 Ladies and Gentlemen:

10 CFR 50.90 DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC CO.

FACILITY OPERATING LICENSE NPF-30 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION ROUND 3 RE: APPLICATION FOR AMENDMENT TO FACILITY OPERATING LICENSE NPF -30 REVISION TO FINAL SAFETY ANALYSIS REPORT STANDARD PLANT SECTION 3.6 FOR HIGH DENSITY POLYETHYLENE PIPE CRACK EXCLUSION (TAC NO. MF3202, LDCN 13-0016)

References:

1. ULNRC-06043 dated December 6, 2013, "Revision to FSAR Standard Plant Section 3.6 for HDPE Crack Exclusion (LDCN 13-0016)"
2. NRC Request for Additional Information, Carl F. Lyon (NRC) to Fadi Diya (Union Electric Company) dated July 1, 2014
3. ULNRC-0613 7 dated September 2, 2014, "Response to NRC Request for Additional Information Regarding Application for Amendment to Facility Operating License NPF-30 (TAC NO. MF3202, LDCN 13-0016) Revision to FSAR Standard Plant Section 3.6 for HDPE Crack Exclusion"
4. NRC Request for Additional Information Round 2, Carl F. Lyon (NRC) to Fadi Diya (Union Electric Company) dated October 28,2014
5. ULNRC-06152 dated December 11, 2014, "Response to Request for Additional Information Round 2 Re: Application for Amendment to Facility Operating License NPF-30 Revision to Final Safety Analysis Report Standard Plant Section 3.6 for High Density Polyethylene Pipe Crack Exclusion (TAC NO.

MF3202, LDCN 13-0016)"

6. NRC Request for Additional Information Round 3, Carl F. Lyon to Fadi Diya (Union Electric Company) dated December 22, 2014 PO Box 620 Fulton, MO 65251 AmerenMissouri.com STARS
  • Alliance

ULNRC-06169 February 3, 2015 Page2 In Reference 1 above, Ameren Missouri (Union Electric Company) submitted an application for amendment to Facility Operating License Number NPF-30 for the Callaway Plant. The proposed amendment would add a new pipe crack exclusion allowance to FSAR Standard Plant Section 3.6.2.1.2.4, "ASME Section III and Non-Nuclear Piping-Moderate-Energy," and FSAR Standard Plant Table 3.6-2, "Design Comparison to Regulatory Positions of Regulatory Guide 1.46, Revision 0, dated May 1973, titled 'Protection Against Pipe Whip Inside Containment,'" for the high density polyethylene (HDPE) piping installed in ASME Class 3 line segments of the essential service water (ESW) system. The amendment was submitted per the requirements of 10 CFR 50.59(c)(2)(viii).

In Reference 2 above, the NRC requested additional information to complete their review, which was provided by Ameren Missouri in Reference 3. In Reference 4 above, the NRC issued a second request for additional information, which was provided by Ameren Missouri in Reference 5. In Reference 6 above, the NRC issued a third request for additional information. The attachment to this letter provides the requested information.

No commitments are contained in this letter. If you have any questions on this amendment application, please contact me at (573) 676-8719 or Jim Kovar at (314) 225-1478.

I declare un~er penalty of perjury that the foregoing is true and correct Sincerely, Executed on: l/ ~ /l{) l6 Scott A. Maglio Manager, Regulatory Affairs JPK/nls

Attachment:

RAI Response

ULNRC-06169 February 3, 2015 Page 3 cc:

Mr. Marc L. Dapas Regional Administrator U.S. Nuclear Regulatory Commission Region IV 1600 East Lamar Boulevard Arlington, TX 76011-4511 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. Fred Lyon Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop 0-8B 1 Washington, DC 20555-2738

ULNRC-06169 February 3, 2015 Page4 Index and send hardcopy to QA File A160.0761 Hardcopy:

Certrec Corporation 4150 International Plaza Suite 820 Fort Worth, TX 76109 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.)

Electronic distribution for the following can be made via Responses and Reports ULNRC Distribution:

F. M. Diya D. W. Neterer L. H. Graessle T. E. Herrmann B.L.Cox S. A. Maglio T. B. Elwood Corporate Communications NSRB Secretary STARS Regulatory Affairs Mr. John O'Neill (Pillsbury Winthrop Shaw Pittman LLP)

Attachment to ULNRC-06169 ATTACHMENT RAI RESPONSE

Attachment to ULNRC-06169

References:

REQUEST FOR ADDITIONAL INFORMATION LICENSE AMENDMENT REQUEST TO REVISE FSAR-SP 3.6 UNION ELECTRIC COMPANY CALLAWAY PLANT, UNIT 1 DOCKET NO. 50-483

1. Letter No. ULNRC-06043, from Scott Maglio, Regulatory Affairs Manager, Ameren Missouri, to U. S. Nuclear Regulatory Commission, Document Control Desk, "Revision to FSAR Standard Plant Sections 3.6 for HOPE Crack Exclusion," December 6, 2013. (ML13340A775)
2. Letter No. ULNRC-06137, from Scott Maglio, Regulatory Affairs Manager, Ameren Missouri, to U.S. Nuclear Regulatory Commission, Document Control Desk, "Response to Request for Additional Information Round 2 Re: Application for Amendment, Revision to Final Safety Analysis Report Standard Plant Sections 3.6 for High Density Polyethylene Pipe Crack Exclusion," September 2, 2014. (ML14245A653)
3. Letter No. ULNRC-06152, from Scott Maglio, Regulatory Affairs Manager, Ameren Missouri, to U. S. Nuclear Regulatory Commission, Document Control Desk, "Response to NRC Request for Additional Information Regarding Application for Amendment, Revision to FSAR Standard Plant Sections 3.6 for HOPE Crack Exclusion (TAC No. MF3202, LDCN 13-0016,"

December 11, 2014 (ML143458052)

By application dated December 6, 2013 (Reference 1 ), as supplemented by letters dated September 2 and December 11, 2014 (References 2 and 3, respectively), to the U.S.

Nuclear Regulatory Commission (NRC), Union Electric Company (dba Ameren Missouri, the licensee) submitted a license amendment request to revise the Final Safety Analysis Report-Standard Plant (FSAR-SP) Section 3.6.2.1.2.4, "ASME [American Society of Mechanical Engineers] Section Ill and Non-Nuclear Piping-Moderate-Energy," to include a new pipe crack exclusion allowance at Callaway Plant, Unit 1.

The NRC staff has determined that the additional information requested below is needed to complete its review.

Fire Protection Branch (AFPB)-Callaway-MF3202-HDPE-RAI-9(d), Supplement 1 The NRC reviewed the information provided in the letter dated December 11, 2014. The response indicates that no insulation or fire barrier materials are used on the exposed High Density Polyethylene (HOPE) Essential Service Water pipe sections. For the Ultimate Heat Sink Penetration Room and the Yard Vault, the licensee assumes "whole room burn-up" to occur.

1. Please provide additional information regarding the expectation of performance of the HOPE piping in these areas, given failure of unprotected HOPE material in a whole room burnup scenario.

1

Attachment to ULNRC-06169

2. If the HOPE piping fails, provide a technical discussion of how plant safety is assured in the event of whole room burn-up of these areas, including HOPE pipe failure of exposed HOPE piping.

Response

HOPE Pipe Fire Hazard The HOPE pipe, which is composed of high density polyethylene, is considered a combustible material; however, its ignition temperature is >300 degrees C and its auto-ignition temperature is 349 degrees C. If ignited, HOPE pipe will create dense smoke. In terms of susceptibility to ignition and smoke generation should ignition occur, the exposed HOPE pipe fire hazard could be considered comparable to electrical cable trays filled with IEEE rated electrical cables, which are used throughout the plant. The HOPE pipe is not an ignition source, and consequently, its addition does not affect the probability of a fire occurring in any fire area.

In a whole room burn-up scenario, all equipment in the affected area is assumed to be adversely affected by the fire. It is assumed the fire fails the HOPE piping in that area.

As explained further below, and in light of the plant design for redundant and independent of the Essential Service Water (ESW) system, none of the equipment in the affected area would be required or credited for maintaining the reactor in a safe and stable condition regardless of the condition of the HOPE piping in the area of the fire. The effect of failed HOPE piping on equipment in applicable areas of the plant is location specific and is addressed in each of the sections below.

UHS Penetration Room The ESW HOPE piping at the UHS Cooling Tower is separated into two separate fire areas that are train related, UNCT, "Ultimate Heat Sink Cooling Tower A," and USCT, "Ultimate Heat Sink Cooling Tower B," which are separated by rated fire barriers. Fire damage is evaluated in these two fire areas as whole room burn-up, therefore, the inclusion of the HOPE pipe has no impact on the fire damage assumed for the safety related equipment in the affected fire area. No specific failure mechanism for the HOPE piping is postulated, and detailed fire modeling has not been performed. For a fire affecting one train (UNCT/USCT), the Nuclear Safety Capability Assessment performance goal is satisfied by maintaining the opposite ESW train free of fire damage and by having offsite power and non-safety related Service Water available.

The postulated fire and its effects (i.e., potential flooding due to failure of HOPE) do not damage the opposite train; therefore, the opposite train is assumed to be available. The UHS Penetration Rooms are located on opposite sides of the UHS Cooling Tower Basin, which is roughly 116' wide and 11 0' long. The UHS Cooling Tower Basin drains (by gravity) back to the UHS Pond. The drains are sized to keep up with the return flow with both ESW pumps running at full capacity. An HOPE pipe failed by fire would not pose a threat to overflowing the Cooling Tower Basin (i.e., by 2

Attachment to ULNRC-06169 flow of spilled ESW from the UHS Penetration Room), and therefore would not affect the opposite train.

The UHS Cooling Tower is located away from other safety related buildings. Thus, no equipment in other safety related structures would be susceptible to the effects of the HOPE failure in the UHS Cooling Tower Penetration Rooms.

Because the opposite train would remain free of fire and water damage due to a failed HOPE pipe, a failure of the HOPE piping (due to whole room burn-up), and the resulting loss of inventory would not prevent the opposite train from performing its intended design function. Offsite power would be available, as well as non-safety related service water. The Callaway Energy Center would be able to achieve a safe and stable plant condition using the opposite train of ESW in accordance with licensing requirements identified in FSAR SP Section 9.5.1.

Yard Vault The ESW HOPE piping in the yard vaults is ESW train specific and separated by rated fire barriers. There are no fixed ignition sources in the vaults, and fire damage is evaluated as whole room burn-up. No specific failure mechanism for the HOPE piping is postulated, and detailed fire modeling has not been performed. For a fire in one train of the ESW vaults, the Nuclear Safety Capability Assessment performance goal is satisfied by maintaining the opposite ESW train free of fire damage and by having offsite power and non-safety related Service Water available.

The postulated fire and its effects (i.e., loss of ESW inventory due to failure of HOPE) do not damage the opposite train; therefore, the opposite train is assumed to be available. The yard vaults are separated by a concrete wall such that no leak path exists. There are no safety related components in the yard vaults that would be susceptible to water intrusion (i.e. there are no electrical components or instrumentation).

In addition, the yard vaults are located away from the ESW Pumphouse, the UHS Cooling Tower, and the Control Building basement. Thus, no equipment in those structures would be susceptible to the effects of the HOPE failure.

Because there are no safety related components in the yard vaults that would be susceptible to water intrusion (i.e. there are no electrical components or instrumentation), a failure of the HOPE piping (due to whole room burn-up), and the resulting loss of inventory would not prevent the opposite train from performing its intended design function. Offsite power would be available, as well as non-safety related service water. The Callaway Plant would be able to achieve a safe and stable plant condition using the opposite train of ESW in accordance with the licensing requirements identified in FSAR SP Section 9.5.1.

3

Attachment to ULNRC-06169 Note that drawings M-U50211 and M-U50321 were included as enclosures in the response to previous RAis 1-8. These drawings depict the general layout of the UHS Cooling Tower and the ESW Yard Vaults.