Markup Regarding the License Amendment Reauest to the Fire Protection Program
ML15008A031
Person / Time
Site: South Texas  
Issue date: 12/17/2014
From: Rencurrel D
South Texas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NOC-AE-14003203
Download: ML15008A031 (6)


Text

Nuclear Operating Company South Te*s Pro/cct Electric Genrtatig Station P. Box 289,dsm~r*oI, Texas 77483 A ýAAA December 17, 2014 NOC-AE-14003203 1 OCFR50.90 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001 South Texas Project Units 1 & 2 Docket Nos. STN 50-498, STN 50-499 South Texas Project Operating License Markup Regarding the License Amendment Reauest to the Fire Protection Proqram

Reference:

Letter from D.W. Rencurrel, STP Nuclear Operating Company, to NRC Document Control Desk, "License Amendment Request for Approval of a Revision to the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability," dated July 23, 2013. (NOC-AE-1 3002962) (ML13212A243)

On July 23, 2013, STP Nuclear Operating Company (STPNOC) submitted a license amendment request to revise the South Texas Project Units 1 and 2 Fire Protection Program related to alternate shutdown capability (Reference 1). Specifically, STPNOC requested crediting the performance of certain operator actions in the Control Room, including one automatic operation in the event a fire requires Control Room evacuation. Enclosures 1 and 2 of this letter contain markup pages for the South Texas Project Unit 1 and Unit 2 Facility Operating Licenses.

There are no commitments in this letter.

If there are any questions regarding this correspondence, please contact Rafael Gonzales at (361) 972-4779 or me at (361) 972-7867.

I declare under penalty of perjury that the foregoing is true and correct.

Executed on D.W. Rencurrel Senior Vice President of Operations rjg

Enclosures:

1) South Texas Project Unit 1 Facility Operating License Markup Page, NPF 76-9
2) South Texas Project Unit 2 Facility Operating License Markup Page, NPF 80-8 AuYý STI: 33995266

NOC-AE-14003203 Page 2 of 2 cc:

(paper copy)

(electronic copy)

Regional Administrator, Region IV U. S. Nuclear Regulatory Commission 1600 East Lamar Boulevard Arlington, TX 76011-4511 Balwant K. Singal Senior Project Manager U.S. Nuclear Regulatory Commission One White Flint North (MS 8 B1) 11555 Rockville Pike Rockville, MD 20852 NRC Resident Inspector U. S. Nuclear Regulatory Commission P.O. Box 289, Mail Code: MNl16 Wadsworth, TX 77483 A. H. Gutterman, Esquire Morgan, Lewis & Bockius LLP Balwant K. Singal U. S. Nuclear Regulatory Commission John Ragan Chris O'Hara Jim von Suskil NRG South Texas LP Kevin Polio Cris Eugster L. D. Blaylock CPS Energy Peter Nemeth Crain Caton & James, P.C.

C. Mele John Wester City of Austin Richard A. Ratliff Texas Department of State Health Services Robert Free Texas Department of State Health Services

NOC-AE-1 4003203 South Texas Project Unit 1 Facility Operating License Markup Page, NPF 76-9

SOUTH TEXAS LICENSE (4)

The facility has been granted a schedular exemption from Section 50.71 (e)(3)(i) of 10 CFR 50 to extend the date for submittal of the updated Final Safety Analysis Report to no later than one year after the date of issuance of a low power license for the South Texas Project, Unit 2. This exemption is effective until August 1990. The staffs environmental assessment was published on December 16, 1987 (52 FR 47805).

E.

Fire Protection STPNOC shall implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report through Amendment No. 55 and the Fire Hazards Analysis Report through Amendment No. 23, and submittals dated April 29, May 7, 8 and 29, June 11, 25 and 26, 1987; February 3, March 3, and November 20, 2009; January 20, 2010; July 23, 2013; May 12 (two letters), May 19, December 17, 2014; and as approved in the SER (NUREG-0781) dated April 1986 and its Supplements, subject to the following provision:

STPNOC may make changes to the approved fire protection program without prior approval of the Commission, only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.

F.

Physical Security STPNOC shall fully implement and maintain in effect all provisions of the physical security, training and qualification, and safeguards contingency plans previously approved by the Commission and all amendments and revisions to such plans made pursuant to the authority under 10 CFR 50.90 and 10 CFR 50.54(p).

The licensee shall fully implement and maintain in effect all provisions of the Commission-approved physical security, training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822), and the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The combined set of plans, which contains Safeguards Information protected under 10 CFR 73.21, is entitled: "South Texas Project Electric Generating Station Security, Training and Qualification, and Safeguards Contingency Plan, Revision 2" submitted by letters dated May 17 and 18, 2006.

STPNOC shall fully implement and maintain in effect all provisions of the Commission-approved cyber security plan (CSP), including changes made pursuant to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). STPNOC CSP was approved by License Amendment No. 197.

G.

Not Used H.

Financial Protection The Owners shall have and maintain financial protection of such type and in such amounts as the Commission shall require in accordance with Section 170 of the Atomic Energy Act of 1954, as amended, to cover public liability claims.

Amendment No.

NOC-AE-14003203 South Texas Project Unit 2 Facility Operating License Markup Page, NPF 80-8 (2)

The facility was previously granted exemption from the criticality monitoring requirements of 10 CFR 70.24 (See Materials License No.

SNM-1983 dated August 30, 1988 and Section III.E. of the SER dated August 30, 1988). The South Texas Project Unit 2 is hereby exempted from the criticality monitoring provisions of 10 CFR 70.24 as applied to fuel assemblies held under this license.

(3)

The facility requires a temporary exemption from the scheduler requirements of the decommissioning planning rule, 10 CFR 50.33(k) and 10 CFR 50.75. The justification for this exemption is contained in Section 22.2 of Supplement 6 to the Safety Evaluation Report. The staff's environmental assessment was published on December 16, 1988 (53 FR 50604). Therefore, pursuant to 10 CFR 50.12(a)(1), 50.12(a)(2)(ii) and 50.12(a)(2)(v), the South Texas Project, Unit 2 is hereby granted a temporary exemption from the schedular requirements of 10 CFR 50.33(k) and 10 CFR 50.75 and is required to submit the decommissioning plan for both South Texas Project, Units 1 and 2 on or before July 26, 1990.

E.

Fire Protection STPNOC shall implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report through Amendment No. 62 and the Fire Hazards Analysis Report through Amendment No. 23, and submittals dated April 29, May 7, 8 and 29, June 11, 25, and 26, 1987; February 3, March 3, and November 20, 2009; January 20, 2010; July 23, 2013; May 12 (two letters), May 19, December 17, 2014; and as approved in the SER (NUREG-0781) dated April 1986 and its Supplements, subject to the following provisions:

STPNOC may make changes to the approved fire protection program without prior approval of the Commission, only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.

F.

Physical Security The licensee shall fully implement and maintain in effect all provisions of the Commission-approved physical security, training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822), and the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The combined set of plans, which contain Safeguards Information protected under 10 CFR 73.21, is entitled: "South Texas Project Electric Generating Station Security, Training and Qualification, and Safeguards Contingency Plan, Revision 2" submitted by letters dated May 17 and 18, 2006.

STPNOC shall fully implement and maintain in effect all provisions of the Commission-approved cyber security plan (CSP), including changes made pursuant to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). STPNOC CSP was approved by License Amendment No. 185.

Amendment No.