Official Exhibit - ENT000613-00-BD01 - EN-EP-S-002-MULTI, Rev. 1, Underground Piping and Tanks General Visual Inspection, 3-SI-161-3, 3-SI-161-4/3-inch Safety Injection Line 161 (June 7, 2013)
ML13241A481
Person / Time
Site: Indian Point  
Issue date: 06/07/2013
From: Peterson J
Entergy Nuclear Operations
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
RAS 24843, 50-247-LR, ASLBP 07-858-03-LR-BD01, 50-286-LR
Download: ML13241A481 (10)


Text



    

United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:

Entergy Nuclear Operations, Inc.

(Indian Point Nuclear Generating Units 2 and 3)

ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:

Identified:

Admitted:

Withdrawn:

Rejected:

Stricken:

Other:

ENT000613-00-BD01 8/20/2013 8/20/2013 1------

ot.'" COMAf/,s,s/O i

I.

1-o

~

~

{,

~

"'.$JJ..1.S07J'r'~

ENTERGY ENGINEERING STANDARD EN-EP-S-002-MULTI I REV. 1 Underground Piping and Tanks PAGE 15 OF 15 General Visual Inspection ATTACHMENT 7.3 PIPE/TANK BASE MATERIAL VISUAL INSPECTION CHECKLIST Sheet 1 of 2 Note: Any inspection photographs or videos should be included with the inspection report.

LinelTank 10 & Name:

3-SI-161-3, 3-Sf-161-4 1 3-in Sf Line 161 Work Order: 279577-02 System: Safety: Injection Base Material:

Location: IP3 NW WHUT PIT Thickness:

Previously Coated? Yes [ 1 No [Xl Backfill Contains Rocks? Yes [ 1 No [Xl Backfill Contains Other Objects? Yes [ 1 (circle one, Internal/tank or External/pipe) 1. Any Cracking?

2.

Any Rust?

3.

Any Corrosion?

4.

Any Flaking or Scaling?

No [Xl 304 SS Inspection Date: 5/14/2013 0.216" Inspector: J. Peterson

==

Description:==

==

Description:==

Note Yes [l No [Xl __________ _

Yes [ 1 No[Xl __________ _

Yes [l No [Xl __________ _

Yes [l No [Xl __________ _

5.

Any Mechanical Damage?

Yes [l No [Xl ___________ _

6.

Any Nicks, Gouges, Pitting or Arc Strikes?

Yes [l No [Xl ___________ _

7.

Any Tubercles (if Internal Inspection)

NIA [Xl Yes [l No [ 1 ___________ _

8.

Any MIC (if Internal Inspection)

NIA [Xl Yes [l No [ 1 ___ _______ _

9.

Any Indication of Selective Leaching?

10. Other?

Any yes answer requires a CR to be initiated Yes [l No [Xl __________ _

Yes [l No [Xl __________ _

General Appearance: A portion of the 3-inch Safety: Injection line 161 (SIP return to the RWST) was excavated and visually: inspected. The total length of the Safety: Injection line inspected was at least 16 ft.

The exposed piping was in good condition. No damage noted.

Degradation Found? Yes [l No [Xl Further Evaluation Required? Yes [l No [Xl Comments: Some discoloration exists along with what seems to be a light coating of concrete potentially:

from original construction. Even though no anomalies were found on this pipe still recommend performing UT thickness readings in selected sections of the pipe to verify: that wall thickness is within the acceptance criteria. Photos and sketch attached. Ref: Drawings 9321 - 26313.

ENTERGY ENGINEERING STANDARD EN-EP-S-002-MUL TI I REV. 1 Underground Piping and Tanks PAGE 15 OF 15 General Visual Inspection ATTACHMENT 7.3 PIPE/TANK BASE MATERIAL VISUAL INSPECTION CHECKLIST Sheet 2 of 2 Degradation Location:

Straight Pipe [ ]

Fitting [ ]

Weld [ ]

Position of leak (Le., 6 o'clock) -'-N=/A--'--____________________ _

CR Required? Yes []

No [X]

CR No. _________________ _

Date: 06/07/2013 Program Owner or Qualified Designee: Una Cossio-Gonzalez

" 'II I

'I' II

" l~

IP3Aerial View, A 15 ft (N*S) x 20 ft (E*WI x 8 ft (deep) excavation (grade is at apprax. EI. 54 ft) uncover too following lille5:

1, 6*irx:h WD Line 252 (RWST overtk>w to WHUTI 2,

3*irx:h SI Line 161 (SIP return to the RWST) 3, 12*ioch SI Line 161 (RWST to Cont. Spray Pumps) 4, IS*ioch SI Line 155 (RWSTto RHR Pumps) 5, IS*ioch outer pipe containing 6~nGh STM Lille 561 and 2*inch COND Line 678

Reference:

Drawing 9321-F-26323

~t.. tiL."'"

110-. ~'M"."

"-Inch WD LIne 252 {RWST WHUn

3-inch Siline 161 (SIP return to the RWST)