LIC-13-0102, OPPD Supplemental Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding the Flooding Aspects of Recommendations 2.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident

From kanterella
(Redirected from ML13228A098)
Jump to navigation Jump to search

OPPD Supplemental Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding the Flooding Aspects of Recommendations 2.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident
ML13228A098
Person / Time
Site: Fort Calhoun 
Issue date: 08/15/2013
From: Cortopassi L
Omaha Public Power District
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
LIC-13-0102
Download: ML13228A098 (12)


Text

444 South 16th Street Mall Omaha, NE 68102-2247 Employment with Equal Opportunity August 15, 2013 LIC-13-0102 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555

References:

1. Docket No. 50-285
2. Letter from NRC (E. J. Leeds & M. R. Johnson) to OPPD (D. J. Bannister),

"Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) Regarding Recommendations 2.1, 2.3, and 9.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident," dated March 12, 2012 (ML12053A340) (NRC-12-0021)

3. Letter from OPPD (L. P. Cortopassi) to NRC (Document Control Desk),

"OPPD 180-day Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding the Flooding Aspects of Recommendation 2.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident," dated November 27, 2012 (ML12334A449) (LlC-12-0170)

Subject:

OPPD Supplemental Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding the Flooding Aspects of Recommendations 2.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident On March 12, 2012, the NRC issued Reference 2 to all power reactor licensees and holders of construction permits in active or deferred status. Enclosure 4 of Reference 2 requested that each licensee perform flood protection walkdowns and report the results within 180 days of NRC endorsement of the flooding walkdown procedure (NEI 12-07). OPPD completed the flood protection walkdowns at Fort Calhoun Station (FCS) and submitted the results in Reference 3.

As noted on page 12 of Enclosure 1 of Reference 3, sixty-four (64) open items were identified where restricted access prevented walkdown of certain flood protection features. Walkdowns of the restricted access items have been completed and the attachment to this letter provides the results. This submittal closes all the open items in Reference 3.

The attached table provides a list of the restricted access items inspected, their respective disposition, and any action planned or taken. As a result of the inspections:

There were no additional deficiencies found in the supplemental walkdown.

Available Physical Margin (APM) was collected and documented in the walkdown record forms for each applicable item inspected.

All restricted access items inspected were within the plant maintenance and monitoring programs.

U.S. Nuclear Regulatory Commission LlC-13-0102 Page 2 None of the restricted access items were reclassified as inaccessible.

If you should you have questions, please contact Mr. Bill Hansher at (402) 533-6894.

No commitments to the NRC are contained in this letter.

I declare under penalty of perjury that the foregoing is true and correct. Executed on August 12, 2013.

Louis P. Cortopassi Site Vice President and CNO LPC/JKG/mle Attachment Flooding Walkdown - Restricted Access Items c:

E. J. Leeds, Director, Office of Nuclear Reactor Regulation S. A. Reynolds, Acting NRC Regional Administrator, Region IV J. M. Sebrosky, NRC Senior Project Manager L. E. Wilkins, NRC Project Manager J. C. Kirkland, NRC Senior Resident Inspector

LIC-13-0102 Attachment Page 1 Fort Calhoun Station Flooding Walkdown - Restricted Access Items

Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 1 IS-E-07 CW-14 Conduit Penetration from Control Station to Motor IS-Intake Structure 1004'-6" IS - Intake Structure CW-14 Conduit Penetration from Control Station to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 2

IS-E-08 CW-14E Conduit Penetration Power from Cable Tray to Motor IS-Intake Structure 1004'-6" IS-CELL -

Intake Structure, Intake Cell Space CW-14E Conduit Penetration Power from Cable Tray to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 3

IS-E-09 CW-14D Conduit Penetration from Control Station to Motor IS-Intake Structure 1004'-6" IS - Intake Structure CW-14D Conduit Penetration from Control Station to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 4

IS-E-10 CW-14D Conduit Penetration Power from Cable Tray to Motor IS-Intake Structure 1004'-6" IS-CELL -

Intake Structure, Intake Cell Space CW-14D Conduit Penetration Power from Cable Tray to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 2 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 5 IS-E-11 CW-14C Conduit Penetration from Control Station to Motor IS-Intake Structure 1004'-6" IS - Intake Structure CW-14C Conduit Penetration from Control Station to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 6

IS-E-12 CW-14C Conduit Penetration Power from Cable Tray to Motor IS-Intake Structure 1004'-6" IS-CELL -

Intake Structure, Intake Cell Space CW-14C Conduit Penetration Power from Cable Tray to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 7

IS-E-13 CW-14B Conduit Penetration from Control Station to Motor IS-Intake Structure 1004'-6" IS - Intake Structure CW-14B Conduit Penetration from Control Station to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 8

IS-E-14 CW-14B Conduit Penetration Power from Cable Tray to Motor IS-Intake Structure 1004'-6" IS-CELL -

Intake Structure, Intake Cell Space CW-14B Conduit Penetration Power from Cable Tray to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 9

IS-E-15 CW-14A Conduit Penetration from Control Station to Motor IS-Intake Structure 1004'-6" IS - Intake Structure CW-14A Conduit Penetration from Control Station to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 3 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 10 IS-E-16 CW-14A Conduit Penetration Power from Cable Tray to Motor IS-Intake Structure 1004'-6" IS-CELL -

Intake Structure, Intake Cell Space CW-14A Conduit Penetration Power from Cable Tray to Motor Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 11 IS-E-17 Compressed Air to Veranda Penetration IS-Intake Structure 1004' 0" IS - Intake Structure Compressed Air to Veranda Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 12 IS-E-21 Surface Sluice Penetration IS-Intake Structure 988'-6" IS-CELL -

Intake Structure, Intake Cell Space Surface Sluice Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 13 IS-E-23 "F" Cell Grid Backwash Penetration IS-Intake Structure 998'-10" IS-CELL -

Intake Structure, Intake Cell Space "F" Cell Grid Backwash Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 14 IS-E-24 "E" Cell Grid Backwash Penetration IS-Intake Structure 998'-10" IS-CELL -

Intake Structure, Intake Cell Space "E" Cell Grid Backwash Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 15 IS-E-25 "D" Cell Grid Backwash Penetration IS-Intake Structure 998'-10" IS-CELL -

Intake Structure, Intake Cell Space "D" Cell Grid Backwash Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 4 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 16 IS-E-26 "C" Cell Grid Backwash Penetration IS-Intake Structure 998'-10" IS-CELL -

Intake Structure, Intake Cell Space "C" Cell Grid Backwash Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 17 IS-E-27 "B" Cell Grid Backwash Penetration IS-Intake Structure 998'-10" IS-CELL -

Intake Structure, Intake Cell Space "B" Cell Grid Backwash Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 18 IS-E-28 "A" Cell Grid Backwash Penetration IS-Intake Structure 998'-10" IS-CELL -

Intake Structure, Intake Cell Space "A" Cell Grid Backwash Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 19 IS-N-08 Security System Conduit Penetration IS-Intake Structure 1008'-1" IS - Intake Structure Security System Conduit Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 20 IS-N-09 Security System Conduit Penetration IS-Intake Structure 1008'-1" IS - Intake Structure Security System Conduit Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 21 IS-N-10 Security System Conduit Penetration IS-Intake Structure 1007'-5" IS - Intake Structure Security System Conduit Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 5 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 22 IS-N-11 Security System Conduit Penetration IS-Intake Structure 1007'-5" IS - Intake Structure Security System Conduit Penetration Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 23 MH31-E-03 MH-31

Conduit, 1900 series instrument conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit, 1900 series instrument conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 24 MH31-E-04 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 25 MH31-E-05 MH-31 Conduit Yard 996'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 26 MH31-E-06 MH-31 Conduit Yard 997'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 27 MH31-E-07 MH-31 Conduit Yard 998'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 28 MH31-E-08 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 29 MH31-E-09 MH-31 Conduit Yard 997'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 6 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 30 MH31-E-10 MH-31 Conduit Yard 1001'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 31 MH31-E-11 MH-31 Conduit Yard 998'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 32 MH31-E-12 MH-31 Conduit Yard 998'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 33 MH31-E-13 MH-31 Conduit Yard 995'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 34 MH31-E-14 MH-31 Conduit Yard 995'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 35 MH31-E-15 MH-31 Conduit Yard 1001'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 36 MH31-E-16 MH-31 Conduit Yard 1001'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 37 MH31-E-17 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 38 MH31-E-18 MH-31 Conduit Yard 995'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 7 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 39 MH31-E-19 MH-31 Conduit Yard 997'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 40 MH31-E-20 MH-31 Conduit Yard 996'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 41 MH31-E-21 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 42 MH31-E-22 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 43 MH31-E-25 MH-31 Conduit Yard 998'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 44 MH31-E-26 MH-31 Conduit Yard 998'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 45 MH31-E-27 MH-31 Conduit Yard 1001'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 46 MH31-E-28 MH-31 Conduit Yard 997'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 47 MH31-E-29 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 8 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 48 MH31-E-30 MH-31 Conduit Yard 998'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 49 MH31-E-31 MH-31 Conduit Yard 997'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 50 MH31-E-32 MH-31 Conduit Yard 996'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 51 MH31-E-33 MH-31 Conduit Yard 996'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 52 MH31-E-34 MH-31 Conduit Yard 997'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 53 MH31-E-35 MH-31 Conduit Yard 996'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 54 MH31-E-36 MH-31 Conduit Yard 1002'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 55 MH31-E-37 MH-31 Conduit Yard 1001'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 56 MH31-E-38 MH-31 Conduit Yard 1001'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 9 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 57 MH31-E-39 MH-31 Conduit Yard 995'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 58 MH31-E-40 MH-31 Conduit Yard 995'-7" MH Man Hole 31 MH-31 Conduit Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 59 MH31-N-01 Conduit Penetration for RW strainer power Yard 1000'-0" MH Man Hole 31 Conduit Penetration for RW strainer power Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 60 MH31-N-02 Conduit Penetration for RW strainer power Yard 1000'-0" MH Man Hole 31 Conduit Penetration for RW strainer power Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 61 Room 06 Walls/Floors Walls and Floors Aux Bldg 989'-8" Room 6 Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 62 Room 07 Walls/Floors Walls and Floors Aux Bldg 989'-8" Room 7 Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No 63 Room 09 Walls/Floors Walls and Floors Aux Bldg 989'-8" Room 9 Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No

U.S. Nuclear Regulatory Commission LIC-13-0102 Page 10 Item Feature ID/

Procedure No.

Description Bldg./Area CLB Feature Elevation Room Other Description (if any)

Feature/Barrier Type CLB Flood El. At Feature Deficiency (yes/no)

Deficiency Description Actions Taken or Planned Inaccessible?

(yes/no, if yes, explain below) 64 Room 16 Walls/Floors Walls and Floors Aux Bldg 989'-8" Room 16 Incorporated or Exterior Passive (IEP) 1014 ft.

No N/A None No