Official Exhibit - NYS000479-00-BD01 - Underground Piping and Tanks General Visual Inspection, 8-in City Water Line 1502 (May 23, 2013) Engineering Standard EN-EP-S-002-MULTI, Rev. 1, Inspection Date: 10/10/2012
ML13169A116
Person / Time
Site: Indian Point  
Issue date: 05/23/2013
From: Guarnaccia S
Entergy Corp
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
RAS 24665, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01
Download: ML13169A116 (5)


Text

United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:

Entergy Nuclear Operations, Inc.

(Indian Point Nuclear Generating Units 2 and 3)

ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:

Identified:

Admitted:

Withdrawn:

Rejected:

Stricken:

Other:

NYS000479-00-BD01 6/12/2013 6/12/2013 NYS000479 Submitted: June 10, 2013 c:..\\,.~""R REGlI~;.

l~'~

0

~

~

....,,1-0....

?

~

        • il ENTERGY ENGINEERING STANDARD EN*Ep*S*002*MULTI I REV. 1 Underground Piping and Tanks PAGE 140F15 General Visual Inspection ATTACHMENT 7.2 PIPEITANK COATING VISUAL INSPECTION CHECKLIST Sheet 1 of2 NOTE: A photographic record of each indication should be retained with the inspection report.

LinefTank ID & Name: 8*in. City Water Line 1502 System: City Water Location: IP2 Transformer Yard Coating Material: coal tar enamel/saturated asbestos felt wrap Work Order:.i3!.l1.Q.5!...<72~0!...... __

Inspection Date: 10/10/2012 Inspector: S. Guarnaccia Thickness: iaw AWWA C203

] Not Coated Backfill Makeup:

Contains Rocks? Yes [ X )

No [ )

==

Description:==

Oil Containment MOAT Area. Rocks were in contact with the wrap but no damage was observed. The rocks were small ( i.e. < 2.0" in diameter). There were no large rocks in contact with the pipe.

Contains Other Foreign Objects? Yes [

No [X)

==

Description:==

Note

1. Any Mechanical Damage?

Yes [ )

No [X)

2.

Any Holiday/Hole?

Yes [ ]

No [X]

3.

Any Blistering?

Yes [ ]

No [X]

4.

Any Peeling?

Yes [ ]

No [X]

5.

Any Flaking?

Yes [ ]

No [X]

6. Any Delamination?

Yes [ ]

No [X]

7.

Any Embrittlement?

Yes [ ]

No [X]

8.

Any Embedded Rocks (Coating and/or Base)?

Yes [ ]

No [X]

9.

Any Cracking?

Yes [ ]

No [X]

10. Any Gouges?

Yes [ ]

No [X]

11. Any Rusting?

Yes [ ]

No [X]

12. Other?

Yes [ ] No [X]

Any Yes answer requires a CR to be initiated General Appearance: A portion of the 8-inch City Water line (# 1502) return to EDGs was excavated and visually inspected. The portion inspected was at least 10ft. of the straight section of the pipe. The entire inspected length of piping had no signs of coating degradation. The coating was observed to be intact. with no voids in the coating. or blistering. peeling. flaking. separation. etc. Further the coating was solid to the touch (no soft spots air pockets). However there were orange stains observed on several locations on the exterior. Note that a 4' section of this pipe was previously inspected in August 2012. some coating was

ENTERGY ENGINEERING STANDARD EN*EP-S-002*MUL n REV. 1 Underground Piping and Tanks PAGE 140F 15 General Visual Inspection ATTACHMENT 7.2 PIPEITANK COATING VISUAL INSPECTION CHECKLIST Sheet 2 of2 removed from discolored areas and a UT was performed as documented in report IP2*UT*12-030. The UT verified acceptable pipe thickness.

Degradation Found? Yes []

No [X]

Further Evaluation Required? Yes [

No [X]

Comments: Photos and sketch attached. Ref: Drawing 9321-2236 CR Required? Yes []

No [X]

CR No. ________ _

Performed By: Stephen Guarnaccia U A ~~

I Program Owner or Qualified Designee:

Una Cossio-Gonzalez f\\l\\.~\\£.

Date: 05/23/2013 Date: 05/23/2013

EXCAVATION OF 22 MT MOAT AREA

@ North Wall Piping Uncovered for Inspection: 8-inch SW Line 463 return to EDGs 8-inch HP Fire Protection Line 8-inich City Water Line 1502 to AFPs t'

§)

1+

E Il\\,"'!o,,0 4 " ~ Iltr. t><<.oT

~\\!,.It

__ 0 y,Jo:,., '!I'll -It.2.'il 0_

S.. SER,v,C "'.....,-et~ ~T\\lttN FR<:>~ c,e.'>~L. G-e.t.Jr,R~~

"1i,-. 11*-~:r4" 1. \\I'J~.~

f'!"N;2.4D 11111<1*

\\ Ii R~"<'( 'IV ",'-~E'I't -=-:~'" i "

se~Ic;.!. Wio.T8R ~,.iF'P1..'7' ill~ 13'- 0" Ref: Drawing 9321-2236

~

~ -:JON l AU 'I.. I ~\\ A.R'{ -

'R"\\J"",",O'Rt'!\\~R. _ i

~rOU~OA.=t\\Ow.. _ I


+/------=-r..

4£l-. ~'O(

\\ C!WN-24'!::)-----

__ t""f',c,,*'V ¥JA.'":Tgft S*OW I:"Tt~*

1_-TlOctlOn f>'l~,\\"'l~ ~ ~\\:~... :

~L.l1 3 -'$.(0/,

I?~"~.&O 011'(<<£

$#~ ~.)~/.~.21("

c

.3*:~4 *"'V. WI/reI(.

~

I 10:

~$T'"

c.owc. Fo::::na