Official Exhibit - NYS000477-00-BD01 - CR-IP2-2012-05324, Condition Report Regarding Visual Inspection of 4 Service Water Return Line (Sept. 11, 2012) Inspection Date: 08/22/2012
ML13169A114
Person / Time
Site: Indian Point  
Issue date: 06/10/2013
From: Richard Lee
Entergy Corp
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
RAS 24665, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01
Download: ML13169A114 (3)


Text

United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:

Entergy Nuclear Operations, Inc.

(Indian Point Nuclear Generating Units 2 and 3)

ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:

Identified:

Admitted:

Withdrawn:

Rejected:

Stricken:

Other:

NYS000477-00-BD01 6/12/2013 6/12/2013 NYS000477 Submitted: June 10, 2013 Entergy CONDITION REPORT CR-IP2-2012-05324 Originator: Lee.Robert C Originator Site Group: IP2 P&C Eng Codes Staff IP2 Originator Phone: 6612 Operability Required: Y Reportability Required: Y Supervisor Name: Azevedo.Nelson F Discovered Date: 0812212012 14:25 Condition

Description:

Initiated Date: 08/2212012 14:55 A visual inspection of an approx. 4 ft length of SW return line 463 in the 22 MT moat area (at the north curb wall) was performed. Coating degradation (including cracking, delamination, localized separation from the pipe OD) was evident along the entire length of the exposed piping, with surface corrosion at the areas of coating separation. This was an opportunistic buried piping inspection performed by the Underground Piping & Tank program owner during excavation in the 22 MT moat

. This portion of SW piping is downstream of the EDG SW FCVs, and is non-code piping.

Immediate Action

Description:

Discussed with Code Programs & E-FIN supervisor, wrote CR.

Suggested Action

Description:

Remove coating on SW line, prep piping for performing surface UTs to determine wall thickness.

Recommend site CoatingslE-FIN engineer also perform inspection of piping and provide coating repair recommendation.

TRENDING (For Reference Purposes Only):

Trend Type EU REPORT WEIGHT INPO BINNING KEYWORDS HEPFACTOR Trend Code ESPC I

ER3 KW-SERVICE WATER E

Entergy I CORRECTIVE ACTION I CR-IP2-2012-05324 CA Number:

Site I Group


~--------------~

Name Assigned By:

Assigned To:

Subassigned To :

1P2 IP2 1P2 P&C Eng Codes Mgmt IP2 P&C Eng Codes Mgmt IP2 P&C Eng Codes Staff 1P2 Tesoriero,Michael V Azevedo,Nelson F Lee,Robert C Originated By: Zzip2crg Performed By: De Donato,Anthony J Subperformed By: Lee,Robert C Approved By:

Closed By: De Donato,Anthony J Current Due Date: 09/19/2012 CA Type: DISP - CA Plant Constraint: NONE CA

Description:

8/271201212:32:11 9110/201214:17:29 9110/2012 12:20:38 9/101201214:17:29 Initial Due Date: 09/1912012 CA Priority: 3 You have been assigned as the Responsible Manager for this Category "C", Non-Significant Condition Report by the CRG Addresslcorrect the identified condition per EN-LI-I 02. Perform disposition review, investigate as needed, and ensure actions are assigned as applicable to correct the problem.

Response

See sub-response.

Subresponse :

The excavated piping SW line 463 was also subsequently inspected by the E-FIN/coatings engineer. Based on observations of similar (but to a lesser degree), indications of degraded coating on adjacent 8-inch city water Line 1502 and 8-inch HP fire protection lines, this investigation was expanded to include all three 8-inch lines. The piping areas having degraded coating were cleaned and prepped (coating and rough scale removed down to bare metal) for direct UT to verify wall thickness under WO #s 315720-09 & 315720-10. The UT results for ave. wall thickness were all SAT (greater than 87.5% of nominal wall).

UT report 1P2-UT 030 (includes UT for the 8-inch fire protection and 8-inch city water line 1502 at areas of degraded coating) is attached to this response. The piping was subsequently recoated to current requirements under WO # 315720-1),

and backfilled with soil.

The results of the visual and UT inspections of this excavated piping, will be captured in Underground Piping and Tank program and trended per program requirements. This CA may be closed without further actions.

Closure Comments:

Attachments:

Subresp Description UT Report IP2-UT-12-030

Entergy I CORRECTIVE ACTION I CR*IP2*2012*05324 CANumber:

2 Site J Group Name Assigned By:

IP2 P&C Eng Codes Staff IP2 Assigned To:

IP2 P&C Eng Codes Mgmt IP2 Kuran,Kathleen R Azevedo,Nelson F Subassigned To :

Originated By: Zzip2crg Performed By: Manzione,Stephen J Subperformed By:

Approved By:

Closed By: Manzione,Stephen J Current Due Date: 09120/2012 CA Type: CR CLOSURE REVIEW Plant Constraint: #NONE CA

Description:

91111201206:23:23 9/[1/2012 11:00:56 9/11/201211:01:42 Initial Due Date: 09/2012012 CA Priority: 4 CAT -C, ALL CORRECTIVE ACTIONS ARE CLOSED FOR THIS CR, THEREFORE THlS CR MAYBE READY TO CLOSE. REVIEW THE CR IN ACCORDANCE WITH EN-LI-102, SECTION 5.10. AND THE EN-LI-102-02 CLOSURE CHECKLIST AND APPROVE 1 DISAPPROVE FOR CLOSURE.

Response

This CR was reviewed in accordance with EN-LI-102, SECTION 5.1 O.and the EN-LI-I 02-02 closure checklist and is approved for closure.

Subresponse :

Closure Comments:

Approved