ML13093A191

From kanterella
Jump to navigation Jump to search
EOC Public NRC Meeting Slides Final
ML13093A191
Person / Time
Site: Palisades 
Issue date: 04/03/2013
From:
NRC/RGN-III
To:
References
Download: ML13093A191 (2)


Text

Palisades Surveillance Capsules

  • Purpose of surveillance

- Monitor embrittlement of specific steels in specific plants

- Provides advance information on pressure vessel condition

- Provides data for predictive models

  • Data sources for Palisades

- Initial program

  • 8 irradiation
  • 2 thermal

- Supplemental program

  • 2 irradiation

- Other Plants

  • Indian Point 2&3
  • H.B. Robinson 2 1

Pressure Vessel Surveillance Capsules Surveillance Samples

Palisades Surveillance Data Some Technical Details Program complies with ASTM-185(1966) 10 CFR 50 Appendix H not in force when Palisades was licensed Included high-Cu weld, but not exactly same as in Palisades pressure vessel Palisades supplemented surveillance program to get data on limiting weld 2 capsules in Palisades 8 capsules in other plants (HBR, IP) 4 capsules remain in Palisades. One more will be pulled before 2031.

2

  • Palisades embrittlement known from 1st capsule pull in 1978
  • Licensing dates lie well within data (no extrapolations)
  • Data follows expected trends Dates 78 83 93 03 98 00 Palisades End of License xx: Date capsule was pulled &

tested 10CFR50.61 Screening Criteria (Years of Reactor Operation)