ML12353A219

From kanterella
Jump to navigation Jump to search
12Q0108.50-R-002, Rev. 1, Seismic Walkdown Report in Response to the 50.54(f) Information Request Regarding Fukushima Near-Term Task Force Recommendation 2.3: Seismic for the LaSalle County Station, Unit 2, Part 11 of 16
ML12353A219
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 11/01/2012
From: Delaney M
Stevenson & Associates
To:
Exelon Generation Co, Office of Nuclear Reactor Regulation
References
RS-12-163 12Q0108.50-R-002, Rev 1
Download: ML12353A219 (62)


Text

12Q-108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 D Area Walk-By Checklists (AWCs)Table D-1 provides the building, elevation, and location of each area as well as a list of SWEL items associated with each area, and page numbers of each Area Walk-By Checklist.

D-1 12Q.108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Table D-1. Summary of Area Walk-By Checklists AWC-U2- BUILDING ELEVATION LOCATION COMPONENT PAGE-U2-xx 1-01 Diesel 736 DG Penthouse 2VY06C D- 5 2AP06E 2AP21E 2AP21 E-303B 2AP81E 1-02 Auxiliary 731 Division II Switchgear Room 2DC13E D- 8 2DC15E 2DC16E 2VX04C 2VX05C 1-03 Auxiliary 731 Division II 125VDC Battery Room 2DC14E D- 15 2DGOIA 2DG01K 2DG01S 1-07 Diesel 710 2A DG Room 2DG02JA D- 18 2DG03J 2DG061A 2PI-DG094 1-08 Diesel 710 2A DG Day Tank Room 2DO05T D- 24 2DG011 2DG01F 1-09 Diesel 674 Division II CSCS Pump Room 2DG01P D- 28 2E12-D300B 1-10 Diesel 674 2A DG Fuel Oil Tank Room 2DO01P D- 34 1-11 Reactor 820 West of SBGT 2AP78E D- 40 2HGO01A 1-12 Reactor 786 North of Containment 2VQ034 D- 45 2VQ035 1-13 Reactor 740 Near Elevator 2VQ029 D- 49 2VQ030 2VQ031 1-14 Reactor 710 North Side Overhead 2VQ03 D- 52 2VQ032 1-15 Reactor 710 Azimuth 2100 Overhead 2HGO05A D- 57 2E12-C002B 2E12-F068B 1-18 Reactor 673 2B RHR Pump Room 2E12-N007B D- 63 2E12-N015B 2E12-N034B 1-19 Reactor 694 Raceway 2E22-F023 D- 72 9T__ I_____ I_____ 1_____________2VY03C

___Table D-1 Page 1 of 3 D-2 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 AWC- BUILDING ELEVATION LOCATION COMPONENT PAGE U2-xx 2E12-F003B 2E12-F011B 2B/C RHR Heat Exchanger 2E12-F026B 1-20 Reactor 694 Corn er 2E12-F048B D- 76 Corner Room .21-O5 2E12-N005B 2E12-N027B 2PL33J 2E12-B001B 1-21 Reactor 710 2B RHR Heat Exchanger Room 2E12-F051B D- 84 2E12-F055B

_1-22 Reactor 694 Raceway 2E12-F036B D- 89 2E12-F004B 1-23 Reactor 673 Raceway 2FC133 D- 98 2HG01A 1-24 Reactor 761 SE Side 2HGO1A D- 106 2TE-HG014A 2-05 Reactor 761 2E22-F004 D- 114 2-06 Reactor 694 Raceway 2VY02C D- 118 2E22-CO01 2-07 Reactor 673 HPCS Corner Room 2E22-N004 D- 127 1 _2E22-N005 2-08 Reactor 673 Raceway 2E22-F015 D-134 3-03 Reactor 786 Heat Exchanger Area 2AP15E D- 138 2C11-DO01002 2C11-D001090 2C11-D2259-125 2C1 1-D2259-126 3-04 Reactor 761 South CRD/HCU Bank 2C11-D2259-126 D- 144 2C11-D2259-127 2C11 -D2603-125 2C 11 -D2603-126 2C11 -D2603-127 2C11-D001095 2C11-D001184 2C11 -D3459-125 3-05 Reactor 761 North CRD/HCU Bank 2C 11-D3459-1269 2C11-D3459-127 2C11-D3807-125 2C11-D3807-126 2C11-D3807-127 3-08 Reactor 740 NW Corner Valve Room 2E51-FO13 D- 155 3-11 Reactor 673 RCIC Pump Corner Room 2E51-CO01 D- 160 2E51-F045 3-12 Reactor 673 Raceway 2E51-F031 D- 163 3-20 Auxiliary 802 Near VR Isolation Dampers OVC03CA D- 165 3-24 Auxiliary 710 250VDC Battery Room 2DC01E D- 172 3-29 Reactor 807 FPC Pump Area 2FC140 D- 175 2H13-P601 3-32 Control Room --- Control Room 2113-P601 D- 178 1 21-113-P602 Table D-1 Page 2 of 3 D-3 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 AWC -U2- BUILDING ELEVATION LOCATION COMPONENT PAGE-U2-xx 4-02 Reactor 820 SBLC Room 2C41-AO01 D- 186 2C41-CO01A 4-04 Reactor 786 Heat Exchanger Area 2WR040 D- 190 4-05 Reactor 786 North Side Overhead 2VQ036 D- 195 4-06 Reactor 761 2AP71E D- 199 4-10 Reactor 694 NW Corner Room 2PL35J D- 202 4-11 Reactor 710 Overhead 2VQ040 D- 206 4-12 Reactor 694 Raceway 2PL34J D- 210 4-13 Reactor 740 2WR029 D- 214 2AP19E 2AP19E-103B 4-20 Auxiliary 710 Division I Switchgear Room 2AP73E D- 218 2DC02E 2DC03E 2DC05E 4-21 Diesel 674 Division I CSCS Pump Room 2E12-C300B D- 222 4-22 Diesel 736 DG Penthouse 2VY05C D- 226 4-24 Reactor 694 Raceway 2VY04C D- 229 2E21-C001 4-25 Reactor 673 LPCS/RCIC Pump Room 2E21-N003 D- 233 4-26 Reactor 673 Raceway 2E12-F068A D- 237 2B21-F022C 2B21 -AO04C 2B21-FO13C OUTAG --- E2B21-FO13C-A 2B21-F028C-P2 2B21 -F028C 2B21 -F067C Table D-1 Page 3 of 3 D-4 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet'1 of 3 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-01 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions

.(if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and- lighting)?

Overhead light fixtures judged to be acceptable.

Two light fixtures in room restrained laterally with rods. One unrestrained light fixture at door to room with open S-hooks. Fixture not near soft targets. Judged to be acceptable.

Broken plastic covers on two fixtures are not a seismic concern. See IR 1405563 and 1406922.5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Drain line in room. Drains are not typically full of water. Judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Cart with battery acceptably stored.D-5 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 3 Status: [i7 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-01 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/27/2012 Evaluated by: -)AIQ 4 L David Carter Date: 10/25/2012

-' James Griffith 10/25/2012 D-6 12QO108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 3 Status: N U Area Walk-By Checklist (AWC)1-01 Ld~dIIe UFIIL Z U I U kD)L D-7 12...08.50-R-002 Rev. I Correspondence No.: RS-12-163 Sheet 1 of 7 Status: jY] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-02 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Locations where conduits and cables in contact with rod hangers judged to be acceptable due to flexibility of items.4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Welded drain lines judged to be acceptable.
6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Breakers adequately restrained.

Cabinets stored in conformance with Procedure LAP- 100-56 (aspect ratio less than 2:1 and with at least 24" clearance to adjacent equipment).

D-8 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 7 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-02 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith-8/27/2012 Evaluated by: Q),IQ-k David Carter Date: 10/17/2012 James Griffith 10/17/2012 D-9 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 7 Status: F N U Area Walk-By Checklist (AWC)1.D-10 12Q0108 50-R-002 Rev 1 Correspondence No: RS-12-163 Sheet 4 of 7 Status: EYI N U Area Walk-By Checklist (AWC)1 D-11 12Q0108.50-R-002 Rev 1 Correspondence No.: RS-12-163 Sheet 5 of 7 Status: F N U Area Walk-By Checklist (AWC)1-D-12 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 7 Status: N U Area Walk-By Checklist (AWC)1 D-13 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 7 of 7 Status: Y N U Area Walk-By Checklist (AWC)Location (Blda. Elev. Room/Area):

Area Walk-by 1-02 LaSalle Unit 2 090 (9)D-14 12..108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 3 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-03 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Small toolbox on floor near rugged battery rack judged to be acceptable.

D-1 5 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 3 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-03 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/27/2012 Evaluated by: 2,JAIQ.k David Carter Date: 10/17/2012 4ýý 6 "P James Griffith 10/17/2012 D-16 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 3 Status: [Y N U Area Walk-By Checklist (AWC)Location (Blda. Elev. Room/Area):

Area Walk-by 1-03 D-17 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 6 Status: r N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-07 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping well-supported and judged to be acceptable.

Drain line not normally full of water and judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Large toolbox with aspect ratio less than 2:1 is located less than 2' from robust drain line. Judged to be acceptable.

Scaffold adequately restrained.

D-1 8 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 6 Status: N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-07 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/28/2012 Evaluated by: David Carter Date: 10/17/2012 James Griffith 10/17/2012 L D-19 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 6 Status: F N U Area Walk-By Checklist (AWC)I D-20 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 6 Status: [Yj N U Area Walk-By Checklist (AWC)1-D-21 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 6 Status: F-1 N U Area Walk-By Checklist (AWC)1-07 D-22 12Q0108.50-R-002 Rev 1 Correspondence No.: RS-12-163 Sheet 6 of 6 Status: F N U Area Walk-By Checklist (AWC)1-D-23 12QO108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 4 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-08 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?
5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?One fire pipe beam clamp support is oriented incorrectly.

No sensitive equipment in room. Room has floor drain in floor. Judged to be acceptable.

Remaining fire piping is well-supported and judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?Covered waste oil can judged to be acceptable.
7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Covered waste oil can not near soft targets; judged to be acceptable.

b-24 12Q0108.50-R-002 Rev. I Correspondence No.: RS-12-163 Sheet 2 of 4 Status: F-7 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-08 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/28/2012 Evaluated by: QY.,Q:k David Carter Date: 10/17/2012 James Griffith 10/17/2012 Photos D-25 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 4 Status: Y N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-08 D-26 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 4 Status: F N U Area Walk-By Checklist (AWC)f1-D-27 12Q.108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet I of 6 Status: Y N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-09 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

For 2E12-D300B, 2 anchors at end bell (south) end with nut not tightened against base plate (maximum 1/2" gap between bottom of nut and top of base plate). Judged to be acceptable per station Engineering department.

Station Maintenace department tightened nuts against base plates. See IR 1406061.Minor spalling in grout pads judged to be acceptable.

3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping is welded and well-supported and therefore judged to be acceptable.
6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-28 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 6 Status: -FY N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-09 Ladders, scaffolding, and toolbox acceptably stored.8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/28/2012 Evaluated by: ,ZWO-4 David Carter Date: 10/17/2012 b A James Grffith 10/17/2012 Photos D-29 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 6 Status: F N U Area Walk-By Checklist (AWC)1 D-30 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 6 Status: Y N U Area Walk-By Checklist (AWC)1-D-31 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 6 Status: F N U Area Walk-By Checklist (AWC)1 D-32 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 6 Status: F N U Area Walk-By Checklist (AWC)Location Elev, Room/Area):

Area Walk-by 1-09 D-33 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 6 Status: FY] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-10 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Welded drain lines judged to be acceptable.
6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

D-34 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 6 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-10 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/28/2012 Evaluated by: David Carter Date: 10/17/2012 James Griffith 10/17/2012 Photos D-35 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 6 Status: Y N U Area Walk-By Checklist (AWC)1 Laballe a-zuJ-1z 1 r44 (%i D-36 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 6 Status: Y N U Area Walk-By Checklist (AWC)1 D-37 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 6 Status: [-1 N U Area Walk-By Checklist (AWC)1-10 L D-38 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 6 Status: FYI N U Area Walk-By Checklist (AWC)Location (BIda. Elev. Room/Area):

Area Walk-by 1-10 D-39 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet I of 5 Status: -Yi N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-11 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping well-supported and judged to be acceptable.
6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Lead shielding scaffold surrounds robust pipe and is judged to be acceptable.

D-40 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 5 Status: r-7 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-11 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/28/2012 Evaluated by: 9-Wak David Carter Date: 10/17/2012 James Griffith 10/17/2012 Photos L D-41 12Q0108.50-R-002 Rev 1 Correspondence No.: RS-12-163 Sheet 3 of 5 Status: F N U Area Walk-By Checklist (AWC)1-11 D-42 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 5 Status: F N U Area Walk-By Checklist (AWC)1-11 L D-43 12Q0108.50-R-002 Rev. I Correspondence No.: RS-12-163 Sheet 5 of 5 Status: Y N U Area Walk-By Checklist (AWC)D-44 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 4 Status: F-] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-12 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Ladders stored against walls and judged to be acceptable.

Scaffolds adequately restrained.

D-45 12QO108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 4 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-12 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/28/2012 Evaluated by: 9QJAAf-Q David Carter Date: 10/17/2012 b A James Griffith 10/17/2012 D-46 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 4 Status: F N U Area Walk-By Checklist (AWC)Location Bd Elev Room/Area rea 1-12 LaSalle 8-28-12 232 3 LaSalle 8-28-12 232 4 La~lle8-8-1 23 5LaSalle 8-28-12 232 6 LaSalle 8-28-12 232 (7) LaSalle 8-28-12 232 (8)D-47 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 4 Status: F N U Area Walk-By Checklist (AWC)Location (Bida. Elev. Room/Area):

Area Walk-bv 1-12 L D-48

Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 3 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-13 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Temporary cables for monitoring are tie-wrapped to robust structures approximately every 2 feet. Judged to be acceptable for temporary condition.
4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

Contact between conduits and pipes judged to be acceptable due to flexibility of items.5. Does itappear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Waste can near rugged items judged to be acceptable.

Radiation Protection survey barrel and table restrained and judged to be acceptable.

D-49 12QO108.50-R-002 Rev 1 Correspondence No.: RS-12-163 Sheet 2 of 3 Status: EYi- N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, RoomlArea):

Area Walk-by 1-13 Scaffold adequately restrained.

8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/29/2012 M. Etre & M. Wodarcyk -9/17/2012 Evaluated by: -J/1" D. Carter # J. Griffith Date: 10/17/2012 Zý//' / M. Etre 4 j At" M. Wodarcyk 10/17/2012 D-50 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 3 Status: F] N U Area Walk-By Checklist (AWC)1-13 D-51 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1of 5 Status: I N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

-Area Walk-by 1-14 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Valve 2B21R512DV touches rack 2H22-P010 near bottom. Rack displacement will not be significant near bottom and valve is robust. Judged to be acceptable.

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Lead shielding scaffolds near robust items judged to be acceptable.

Scaffold storage area judged to be acceptable.

D-52 1200108 50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 5 Status: tj7 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-14 Chocked cart approximately 18" from robust instrument support member judged to be acceptable.

Mop bucket and mop located away from soft targets and judged to be acceptable.

FME cabinet located away from soft targets and judged to be acceptable.

8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?Yes Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/29/2012 Evaluated by: )ý-JVOk David Carter Date: 10/17/2012 Vo James Griffith 10/17/2012 Photos D-53 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 5 Status: [ IN U Area Walk-By Checklist (AWC)1-D-54 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 5 Status: F N U Area Walk-By Checklist (AWC)Location Bid Elev Room/Area 1-14 LaSalle 8-29-12 036 LaSalle 8-29-12 037 LaSalle 8-29-12 039 LaSalle 8-29-12 038 D-55 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 5 Status: [-7 N U Area Walk-By Checklist (AWC)Location (Blda. Elev. Room/Area):

Area Walk-by 1-14 L D-56 12Q.108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 6 Status: Y N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-15 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Contact between adjacent conduits judged to be acceptable due to flexibility of items.4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Permanent scaffold adequately restrained to gallery.Carts and manlifts stored away from soft targets and judged to be acceptable.

D-57 1200108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 6 Status: Y N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 1-15 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: D. Carter & J. Griffith -8/29/2012 Evaluated by: David Carter Date: 10/17/2012

'e James Griffith 10/17/2012 Photo$D-58 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 6 Status: FT] N U Area Walk-By Checklist (AWC)1 D-59 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 6 Status: F N U Area Walk-By Checklist (AWC)1 D-60 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 6 Status: jYJ N U Area Walk-By Checklist (AWC)1.L D-61 12Q0108.50-R-002 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 6 Status: F N U Area Walk-By Checklist (AWC)Location Bid Elev Room/Area 1-15 LaSalle 8-29-12 057 D-62