12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 5 Status: F-] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-02 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

Minor lack of thread engagement at some anchors judged to be acceptable.

3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Rod hanger in contact with robust valve motor. Judged to be acceptable.
4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping is welded and well-supported.

Judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?Nitrogen tanks adequately restrained.

Hydrogen piping well-supported and judged to be acceptable.

7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffolds adequately restrained.

Ladder rack, gang-boxes, chocked cart, and barrels stored acceptably.

D-81 12Q0108.50-R-OO1 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 5 Status: [-1 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-02 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Floor plug located on the 786' Elevation (A & 10) needed to be resealed.Sealant is missing between the south plug and the center plug. Per Engineering and LAP-300-44, Rev. 20 "Floor Plug Removal and Installation", this is not a seismic, flooding, or EQ issue with the sealant missing. It was verified with the Fire Marshall that this floor plug has no fire rating; therefore it is not a fire protection issue. This is a housekeeping issue only. See IR 1410959.Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/10/2012 Evaluated by: James Griffith Date: 10/17/2012 Michael Wodarcyk 10/17/2012 Photos D-82 12Q0108,50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 5 Status: I N U Area Walk-By Checklist (AWC)3 ZUIZUUflu-Lasaiie ui'o D-83 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 5 Status: FYJ N U Area Walk-By Checklist (AWC)Location Bid Elev Room/Area Area Walk- 3-02 2012091C0-asalle 077 20120910-Lasalle 078 D-84 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 5 Status: F-] N U Area Walk-By Checklist (AWC)3.D-85 1200108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 4 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-06 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

Contact between pipes and conduits judged to be acceptable due to flexibility of items.5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?Minor amount of oil absorbing rags on valve judged to be acceptable.

7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Mobile lead shielding frame with chocked wheels and adequate distance from sensitive targets judged to be acceptable.

D-86 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 4 Status: FY] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-06 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/10/2012 J. Griffith & M. Wodarcyk -9/14/2012 M. Etre & M. Wodarcyk -9/17/2012 Evaluated by: J. Griffith Date: 10/17/2012" M. Etre 1 ' ' M. Wodarcyk 10/17/2012 D-87 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 4 Status: EZY N U Area Walk-By Checklist (AWC)-- --w --.w D-88 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 4 Status: r N U Area Walk-By Checklist (AWC)3 D-89 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 12 Status: F-j N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-07 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Rugged cable trays contact support framing for stairway; judged to be acceptable.
4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping welded and well-supported.

Judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?Small quantities of rope, radiation bags, etc. judged to be acceptable.
7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffolds either restrained or tied to adjacent scaffolds to prevent tipping.Scaffolds are near robust targets (cable trays, cable risers, and pipes) and are judged to be acceptable.

Eyewash cart handle near junction box JB IEWO22R. Box confirmed by D-90 12-0108.50-R-oo1 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 12 Status: Y N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-07 Engineering to contain no relays. Therefore, there is no seismic interaction concern.Lead shielding scaffolds near rugged pipes judged to be acceptable.

8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/10/2012 Evaluated by: James Griffith Date: 10/25/2012 Michael Wodarcyk 10/25/2012 D-91 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 12 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-07 D-92 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 12 Status: F N U Area Walk-By Checklist (AWC)-by 3-07 D-93 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 12 Status: F N U Area Walk-By Checklist (AWC)D-94 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 12 Status: F N U Area Walk-By Checklist (AWC)D-95 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 7 of 12 Status: F N U Area Walk-By Checklist (AWC)D-96 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 8 of 12 Status: [Y N U Area Walk-By Checklist (AWC)3 D-97 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 9 of 12 Status: l N U Area Walk-By Checklist (AWC)ZUI ZUUI u-Lasalle zjo D-98 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 10 of 12 Status: N U Area Walk-By Checklist (AWC)3-07 D-99 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 11 of 12 Status: F] N U Area Walk-By Checklist (AWC)3-D-100 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 12 of 12 Status: l N U Area Walk-By Checklist (AWC)D-101 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 12 Status: rY_1 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-09 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping welded and well-supported.

Judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffolds adequately restrained.

Lead shielding scaffold located near robust items and judged to be acceptable.

Ladder chained to outside of storage cage and cannot interact with valve D-102 12Q0108.50-R-O01 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 12 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-09 handle. Ladder is near robust pipe and judged to be acceptable.

Carts stored near robust pipe and conduit judged to be acceptable.

8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/10/2012 M. Etre & M. Wodarcyk -9/17/2012 Evaluated by: ,',', M. Etre (1 I' J. Griffith Date: 10/17/2012 Michael Wodarcyk 10/17/2012 D-103 Area Walk-By Checklist (AWC)12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 12 Status: F N U Location (Bldg, Elev, Room/Area):

Area Walk-by 3-09 D-1 04 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 12 Status: FY] N U Area Walk-By Checklist (AWC)3 D-105 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 12 Status: F N U Area Walk-By Checklist (AWC)3 2012 D-106 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 12 Status: [7 N U Area Walk-By Checklist (AWC)3-09 D-107 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 7 of 12 Status: Fj N U Area Walk-By Checklist (AWC)3-09 D-108 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 8 of 12 Status: F N U Area Walk-By Checklist (AWC)3 D-109 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 9 of 12 Status: LII N U Area Walk-By Checklist (AWC)3 2012091 0-Lasalle 301 D-110 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 10 of 12 Status: F N U Area Walk-By Checklist (AWC)3.D-111 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 11 of 12 Status: F N U Area Walk-By Checklist (AWC)3.D-112 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 12 of 12 Status: Y N U Area Walk-By Checklist (AWC)3 2012091 0-Lasalle 309 D-1 13 12Q0108.50-R-001 Rev. I Correspondence No.: RS-12-163 Sheet 1 of 5 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-10 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Conduit in contact with braced HVAC support. Conduit is flexible with respect to the support. Judged to be acceptable.
4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping welded and well-supported.

Judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?"Heavy Load" sign and ALARA light stanchion located near robust items and judged to be acceptable.

Gang-box tied to support auxiliary steel. Wheel is chocked. Gang-box is near robust items. Judged to be acceptable.

D-1 14 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 5 Status: F] N U Area Walk-By Checklist (AWC)-Location (Bldg, Elev, Room/Area):

Area Walk-by 3-10 Spool pieces tie-wrapped to each other and around support auxiliary steel.Spool pieces are near robust items. Judged to be acceptable.

Insulation crushed on line that is 'jumping" near braced HVAC support. Line does not contact support. Support shows no signs of damage. Judged to be acceptable.

8. Have you looked for and found no other seismic conditions that could adversely affect the safety functions of the equipment in the area?Yes Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/10/2012 Evaluated by: (7 4 James Griffith Date: 10/17/2012 Michael Wodarcyk 10/17/2012 D-115 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 5 Status: N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-10 Photos ZU1IZUVnIU-LasaIle 31 o D-116 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 5 Status: FY7 N U Area Walk-By Checklist (AWC)Walk-by 3-10 D-117 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 5 Status: [] N U Area Walk-By Checklist (AWC)3-10 ZUIZuV1U-LaSaIne jzt D-118 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 3 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-13 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially adverse seismic conditions (if visible without necessarily opening cabinets)?

Yes 2. Does anchorage of equipment in the area appear to be free of significant degraded conditions?

Yes 3. Based on a visual inspection from the floor, do the cable/conduit raceways and HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Yes 4. Does it appear that the area is free of potentially adverse seismic spatial interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions that could cause flooding or spray in the area?Yes Yes 6. Does it appear that the area is free of potentially adverse seismic interactions that could cause a fire in the area?Yes 7. Does it appear that the area is free of potentially adverse seismic interactions associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffoldifence barrier for high-radiation area boundary adequately restrained.

Yes D-119 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 3 Status: -FT] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-13 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/11/2012 J. Griffith & M. Wodarcyk -9/14/2012 Evaluated by: '00' James Griffith Date: 10/17/2012 Michael Wodarcyk 10117/2012 Photos D-120 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 3 Status: FI- N U Area Walk-By Checklist (AWC)3-13 D-121 12Q0108.50-R-O01 Rev. 1 Correspondence No.: RS-12-163 Sheet I of 6 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-14 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?

Minor lack of thread engagement at some anchors judged to be acceptable.

3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?Conduits and pipes in contact at several locations.

Conduits and valves in contact at several locations.

Judged to be acceptable due to flexibility of conduits and pipes.4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Scaffolds adequately restrained, including secured fiberglass ladder for scaffold access.Cart and ladder on floor near robust items judged to be acceptable.

D-122 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 6 Status: F] N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-14 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Pipe clamp missing from short span of tubing between valves 1B33NO18B-UDV and 1B33NO18B-RR mounted on rack 1H22-P021.

Judged to be acceptable.

See IR 1412069.Water-tight door with degraded alarm switch is not a seismic concern. See IR 1411647.Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/12/2012 Evaluated by: James Griffith Date: 10/17/2012 Michael Wodarcyk 10117/2012 Photos 2012 D-123

Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 6 Status: r-Y N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-14 D-1 24 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 6 Status: EY7 N U Area Walk-By Checklist (AWC)3-14 D-125 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 6 Status: FY-] IN U Area Walk-By Checklist (AWC)3-D-126 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 6 of 6 Status: F-] N U Area Walk-By Checklist (AWC)Location (B3da, Elev, Room/Area):

Area Walk-by 3-14 D-127 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet I of 4 Status: lY7 N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-15 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

Contact between robust duct and support brace judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?Fire piping welded and well-supported.

Judged to be acceptable.

6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Permanent scaffold adequately restrained.

Ladder stored on base of permanent scaffold not near soft targets and judged to be acceptable.

D-128 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 4 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-15 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/12/2012 Evaluated by: James Griffith Date: 10/17/2012 Michael Wodarcyk 10/17/2012 Photos D-129 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 4 Status: r N U Area Walk-By Checklist (AWC)3-15 D-130 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 4 Status: [Y N U Area Walk-By Checklist (AWC)3-D-131 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 1 of 5 Status: F N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-16 Instructions for Completing Checklist This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The space below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.1. Does anchorage of equipment in the area appear to be free of potentially Yes adverse seismic conditions (if visible without necessarily opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Yes degraded conditions?
3. Based on a visual inspection from the floor, do the cable/conduit raceways and Yes HVAC ducting appear to be free of potentially adverse seismic conditions (e.g., condition of supports is adequate and fill conditions of cable trays appear to be inside acceptable limits)?4. Does it appear that the area is free of potentially adverse seismic spatial Yes interactions with other equipment in the area (e.g., ceiling tiles and lighting)?

Overhead light fixtures judged to be acceptable.

5. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause flooding or spray in the area?6. Does it appear that the area is free of potentially adverse seismic interactions Yes that could cause a fire in the area?7. Does it appear that the area is free of potentially adverse seismic interactions Yes associated with housekeeping practices, storage of portable equipment, and temporary installations (e.g., scaffolding, lead shielding)?

Permanent lead shielding scaffolds adequately restrained.

D-132 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 2 of 5 Status: N U Area Walk-By Checklist (AWC)Location (Bldg, Elev, Room/Area):

Area Walk-by 3-16 8. Have you looked for and found no other seismic conditions that could Yes adversely affect the safety functions of the equipment in the area?Comments Seismic Walkdown Team: J. Griffith & M. Wodarcyk -9/12/2012 Evaluated by: James Griffith Date: 10/17/2012 Michael Wodarcyk 10/17/2012 Photos D-133 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 3 of 5 Status: F N U Area Walk-By Checklist (AWC)3-D-1 34 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 4 of 5 Status: EZIN U Area Walk-By Checklist (AWC)3 D-135 12Q0108.50-R-001 Rev. 1 Correspondence No.: RS-12-163 Sheet 5 of 5 Status: EZ- N U Area Walk-By Checklist (AWC)D-1 36