ML12339A520

From kanterella
Jump to navigation Jump to search
Official Exhibit - ENT000434-00-BD01 - General Visual Inspection Report for 10-inch City Water Line from Catskill Water Supply (Oct. 2009)
ML12339A520
Person / Time
Site: Indian Point  Entergy icon.png
Issue date: 10/29/2009
From:
Entergy Nuclear Operations
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
RAS 22156, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01
Download: ML12339A520 (6)


Text

ENT000434 Submitted: March 30, 2012 United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:

Entergy Nuclear Operations, Inc.

(Indian Point Nuclear Generating Units 2 and 3)

ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:

Identified:

Admitted:

Withdrawn:

Rejected:

Stricken:

Other:

ENT000434-00-BD01 10/15/2012 10/15/2012 c",V'-'A AEG(J~~

.~~o."

I" 0

0

~

,,"I

~"'+.

~

o o

NOTE: This inspection report form is extracted from EN-EP-S-002-MUL TI (Rev. 0 target effective date 10/31/09)

ATTACHMENT 7.1 Sheet 1 of 2 Piping I Tank H)-inch City Water Line from Catskill Water Supply 120' EL.

(approx.

ELEVATION:

grade) 9321-F-41933, LOCATION DWG:

zone 0-5 YES

1.

ANY BLISTERING (COATING)?

0 YES

2.

ANY PEELING (COATING)?

0 YES

3.

ANY FLAKING (COATING)?

0 YES

4.

ANY DELAMINATION (COATING)?

0 YES

5.

ANY EMBRITTLEMENT (COATING)?

0 YES

6.

ANY EMBEDDED ROCKS (COATING AND/OR METAL)?

0 YES

7.

ANY CRACKING (COATING AND/OR METAL)?

0 YES

8.

ANY RUST (METAL)?

0 YES 9.

ANY CORROSION (METAL)?

0 YES

10.

ANY FLAKING OR SCALING (METAL)?

0 YES 11.

ANY MECHANICAL DAMAGE (METAL)?

0 YES

12.

ANY NICKS. GOUGES OR ARC STRIKES (METAL)?

0 YES

13.

ANY TUBERCLES (METAL -IF INTERNAL INSPECTION)?

0 INSPECTION CHECKLIST INSPECTION DATE:

INSPECTOR:

NO ~

NO ~

NO ~

NO ~

NO ~

NO [8J NO ~

NO ~

NO r81 NO 181 NO 181 NO 181 10/29/09 J. Peterson NOTE NO 0 NIA-extemal inspection only GENERAL APPEARANCE (Inspector): Exterior pipe coating round in good condition, with no observable discontinuities, peeling. blistering.

separation. embrilliement, flaking. etc. Coating also having good adhesion to the pipe with no bubbled spots (i.e., gaps between pipe and coating.).

Sec aUached photo documentation and Notes. Photo included or the backfill material, showing absence or any large rocks, or roreign material.

DEGRADATION FOUND?

FURTHER EVALUATION REQUIRED?

YEsO NO r81 YES 0 NO r81 CR-COMM ENTS (Inspector): I O*inch city water line rrom the City Watt r Storage TWlk was inspected at excavated location. Line runs approximately parallel with the 16-inch city water line (also excavation under the same modification, EC (3314). Approx. 8 loot length of pipe inspected.

INSPECTOR(S) PRINT/SIGNIDATE:

o NOTE: This inspection report form is extracted from EN-EP-S-002-MUL TI (Rev. 0 target effective date 10/31/09)

ATTACHMENT 7.1 INSPECTION CHECKLIST Sheet 2 of2 EVALUATION:

ACCEPTABLE I:8J ACCEPTABLE WITH DEFICIENCIES D UNACCEPTABLE D RECOMMENDED ACTION (Program Owner):

Capture the results of this piping inspection in the BPT Program database (IDDEAL Scheduleworks).

FUTURE MONITORING: D None required. Future inspections of this line will be as scheduled and managed under the IPEG Buried Pipe and Tank Program. Based on results of this inspection. any future inspections of this line should be at other locations.

o PREVENTIVE MAINTENANCE: D None required.

CORRECTIVE ACTIONS: D None required.

PHOTOGRAPHIC OR VIDEO RECORDS ATTACHED?

YES I:8J NO D o

o o

o

\\

~

.~

)

t

~

~z

/:'.

~

)..

"'l

~

AIJ.

4,

,.~

o *

-,,>::z

,