Official Exhibit - ENT000436-00-BD01 - General Visual Inspection Report for 10-inch City Water/Fire Water Line at Maintenance Training Facility (Nov. 2009)
ML12339A518
Person / Time
Site: Indian Point  Entergy icon.png
Issue date: 11/23/2009
From:
Entergy Nuclear Operations
To:
Atomic Safety and Licensing Board Panel
SECY RAS
References
RAS 22156, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01
Download: ML12339A518 (6)


Text

ENT000436 Submitted: March 30, 2012 United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:

Entergy Nuclear Operations, Inc.

(Indian Point Nuclear Generating Units 2 and 3)

ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:

Identified:

Admitted:

Withdrawn:

Rejected:

Stricken:

Other:

ENT000436-00-BD01 10/15/2012 10/15/2012 c:..\\,.~p..R REGlI~;.

l~'~

0

~

~

....,,1-0....

?

~

        • il ENTERGY ATTACHMENT 7.1 Sheet 1 of 2 Piping / Tank 120' EL.

(approx.

ENGINEERING STANDARD Buried Piping and Tanks General Visual Inspection 10-inch City Water/Fire Water Line at the IP2 Maintenance Training Facility (MTF)

NYPA-3899-G-202-0, zone EN-EP-S-002-MULTI I REV. 0 PAGE 11 OF 12 INSPECTION CHECKLIST INSPECTION DATE:

11123/09 ELEVATION:

grade)

LOCATION DWG: _C-=.-....:..11-'---__

_ INSPECTOR:

R.Allen NOTE YES

1.

ANY BLISTERING (COATING)?

0 NO ~

YES

2.

ANY PEELING (COATING)?

0 NO ~

YES

3.

ANY FLAKING (COATING)?

0 NO ~

YES

4.

ANY DELAMINATION (COATING)?

0 NO ~

YES

5.

ANY EMBRITTLEMENT (COATING)?

0 NO ~

YES

6.

ANY EMBEDDED ROCKS (COATING ANDIOR METAL)?

0 NO [gI YES

7.

ANY CRACKING (COATING ANDIOR METAL)?

0 NO [gI YES

8.

ANY RUST (METAL)?

0 NO ~

YES

9.

ANY CORROSION (METAL)?

0 NO [gI YES

10.

ANY FLAKING OR SCALING (METAL)?

0 NO [gI YES 11.

ANY MECHANICAL DAMAGE (METAL)?

0 NO [gI YES

12.

ANY NICKS, GOUGES OR ARC STRIKES (METAL)?

0 NO (gJ YES

13.

ANY TUBERCLES (METAL - IF INTERNAL INSPECTION)?

0 NO 0 N/A-external inspection only GENERAL APPEARANCE (Inspector): See attached photo documentation. Piping at tile installed saddle (west) end of the excavation was relatively clean of soil adhering to the 00 of the pipe, without requiring much cleaning. The east end o/' the piping required use of a waler spray bOll Ie to wet and clean off the ha.'dened red clay-like soil adhering to the pipe 00 to get to the pipe exterior. 111e pipe was coated with a painted on protc<.:tive coating, which was observed to be in very good conuition with no signs of discontinuities, peeling, separation, blistering, Iiaking, etc.

DEGRADATION FOUND?

FURTHER EVALUATION REQUIRED?

YES 0 NO(gJ YES 0 NO(gJ CR-COMMENTS (Inspector): Oppo.tlll1isric inspection of underground I O-inch lire water main running from Broadway in Westerly direction to the Interim Radwa te Storage Facility. Section of line on the south side of dIe MainLenance Training Facility (MTF) ~xcavated as part of installaLion of a I-inch Lic-in to supply water to lhe MTF. (Ref. EC 133 14). Approx. 8 fOOl lcngth of piping was inspected. Section incluued a bell & spigOt pipingjoint. and new saddle for a I-inch branch supply to the MTF. Pipe in VelY good condition. no deficiencies noted.

INSPECTOR(S) PRINT/SIGN/DATE:

R. Allen

ENTERGY ENGINEERING STANDARD EN-EP-S-002-MULTI I REV. 0 Buried Piping and Tanks General Visual PAGE 11 OF 12 Inspection ATTACHMENT 7.1 INSPECTION CHECKLIST Sheet 2 of 2 EVALUATION:

ACCEPTABLE [8]

ACCEPTABLE WITH DEFICIENCIES 0 UNACCEPTABLE 0 RECOMMENDED ACTION (Program Owner): k~ "/').-1/0 '/

Capture the results of this piping inspection in the BPT Program database (IOJEAL Scheduleworks).

FUTURE MONITORING: 0 None required. Future insoections of this line will be as scheduled and managed under the IPEG Buried Pioe and Tank Program. Based on results of this inspection. any future inspections of this line should be at other locations.

PREVENTIVE MAINTENANCE: 0 None required.

CORRECTIVE ACTIONS: 0 None required.

PHOTOGRAPHIC OR VIDEO RECORDS ATTACHED?

Attachments: drawing showing excavated area location Pholographs (3 sheels)

YES [8]

NO D

F:E;::: *gsa 344 - FM -oos ECI 3 3 J tf

~

10 tt 8

_ ____ e I

'3

)it po1ieo.

f>. -~ I) {t(l.r::A LN'IPA - 38"1'i - (j- - L.. 0)

~

SECTION W-'tI', *X-X',

ry-Y' ANlI 'Z-Z' SEE DRA'WING 500194~

J T rJ,

~

  • v.. *l!.VT' lei I

t::,1./]-<./'

'v---../ vi

\\J~-

I I

V MAINTENANCE TRAINNING FACILITY

. '.-JIl.-.

,,1~J* *V.'".

//

/.,.-,..... '"

I

, ~,

//'.-

o

.. ;(/', r'-

-i: --,

//

I J

~

/

~.

<t

~

~