1 IPEC Medium-Voltage In-Scope Cable List Plant Supporting Equipment Manufacturer /
Cable Specs Insulation Type Installed Year Length Lead Sheath Shield Number of Splices /
Spec Cable Rated Voltage Safety Functions Notes IP2 21CWP-MTR
- 21 Circulating Water pump General /
Spec 7403, Spec PO 9321-01-113-4 XLPE /
PVC jacket
- 1973, 1984 215 + 80
= 295 Yes Yes 1 (splice M11 in MH22) /
Spec EO-10680-B 6.9 KV Non safety
- related, Maintenance Rule 52/21CWP to speed changer switch IP2 22CWP-MTR
- 22 Circulating Water pump General /
Spec 7403, Spec PO 9321-01-113-4 XLPE /
PVC jacket
- 1973, 1984 240 + 100
= 340 Yes Yes 1 (splice M12 in MH22) /
Spec EO-10680-B 6.9 KV Non safety
- related, Maintenance Rule 52/22CWP to speed changer switch IP2 23CWP-MTR
- 23 Circulating Water pump General /
Spec 7403, Spec PO 9321-01-113-4 XLPE /
PVC jacket
- 1973, 1984 210 + 115
= 325 Yes Yes 1 (splice M13 in MH22) /
Spec EO-10680-B 6.9 KV Non safety
- related, Maintenance Rule 52/23CWP to speed changer switch IP2 24CWP-MTR
- 24 Circulating Water pump General /
Spec 7403, Spec PO 9321-01-113-4 XLPE /
PVC jacket
- 1973, 1984 250 + 155
= 405 Yes Yes 1 (splice M14 in MH22) /
Spec EO-10680-B 6.9 KV Non safety
- related, Maintenance Rule 52/24CWP to speed changer switch IP2 25CWP-MTR
- 25 Circulating Water pump General /
Spec 7403, Spec PO 9321-01-113-4 XLPE /
PVC jacket
- 1973, 1984 225 + 165
= 390 Yes Yes 1 (splice M15 in MH22) /
Spec EO-10680-B 6.9 KV Non safety
- related, Maintenance Rule 52/25CWP to speed changer switch IP2 26CWP-MTR
- 26 Circulating Water pump General /
Spec 7403, Spec PO 9321-01-113-4 XLPE /
PVC jacket
- 1973, 1984 230 + 180
= 410 Yes Yes 1 (splice M16 in MH22) /
Spec EO-10680-B 6.9 KV Non safety
- related, Maintenance Rule 52/26CWP to speed changer switch ENT000243 Submitted: March 29, 2012 United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:
Entergy Nuclear Operations, Inc.
(Indian Point Nuclear Generating Units 2 and 3)
ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:
Identified:
Admitted:
Withdrawn:
Rejected:
Stricken:
Other:
ENT000243-00-BD01 10/15/2012 10/15/2012
2 IPEC 13W92 13.8KV Alternate offsite power recovery feeder Unknown /
Spec 366-1J EO-1 / Spec 7561E PILC, EPR,
- XLPE, POLY
- 1994, 2010 unknown
- Yes Yes 7
13.8 KV Non safety
- related, Maintenance Rule 52/GT-1 to breaker F2-3
- All underground sections are lead sheath.
IPEC 13W93 13.8KV Alternate offsite power recovery feeder Unknown /
Spec 366-1J EO-1, Spec 7561E, Spec 7402J
- PILC, XLPE, POLY 1994 245+425
+ 2450 =
3120 Yes Yes 6
13.8 KV Non safety
- related, Maintenance Rule 52/GT/2F to F3-1 and 52/GT-2 IP2 GT5 / GT6 13.8KV Alternate offsite power recovery feeder bus supply cables (Includes SBO section)
General /
Unknown Spec EPR / PILC 1970 435
- Yes Yes 1
6.9kv Non safety
- related, Maintenance Rule Substation GT (Appendix R crosstie feeder from splice box 4A to 52/GTBT)
(Rest of circuit cables are above ground to GT5 ad GT6 IP3 31 CWP (M)
- 31 Circulating Water pump Okonite /
Spec PO 9321-05-113-4 EPR 1985 197 No No 0
6.9 KV Non safety
- 32 Circulating Water pump Okonite /
Spec PO 9321-05-113-4 EPR 1985 190 No No 0
6.9 KV Non safety
- 33 Circulating Water pump Okonite /
Spec PO 9321-05-113-4 EPR 1985 164 No No 0
6.9 KV Non safety
- 34 Circulating Water pump Okonite /
Spec PO 9321-05-113-4 EPR 1985 198 No No 0
6.9 KV Non safety
- 35 Circulating Water pump Okonite /
Spec PO 9321-EPR 1985 198 No No 0
6.9 KV Non safety
- related, Maintenance Rule 52/CWP35 to LCI transformer
3 05-113-4 IP3 36 CWP (M)
- 36 Circulating Water pump Okonite /
Spec PO 9321-05-113-4 EPR 1985 215 No No 0
6.9 KV Non safety
- related, Maintenance Rule 52/CWP36 to LCI transformer IP3 GT35 to 6.9KV GT substation bus 13.8KV Alternate offsite power recovery feeder bus supply cables General /
Okonite 9321-05_113-4 / Spec AA15 /
Spec AA25 /
PO-025506-85
/ IEEE 383-74 PILC lead /
EPR 1970 323 + 145
= 468 YES Yes 3
6.9 KV Non safety
- related, Maintenance Rule 52/GT5 to 6.9KV GT substation bus, includes APP R EDG cable IP3 GT36 to 6.9KV GT substation bus 13.8KV Alternate offsite power recovery feeder bus supply cables General /
Okonite 9321-05_113-4 / Spec AA15 /
Spec AA25 /
PO-025506-85
/ IEEE 383-74 PILC lead /
EPR 1970 306 + 145
= 451
- YES Yes 2
6.9 KV Non safety
- related, Maintenance Rule 52/GT6 to 6.9kv GT substation
- Cables designated CWP under supporting equipment are in our CLB scope and do not have a license renewal function and therefore are not in the LR scope.
- One section of the cable has a shield and no lead sheath.
- Some sections have a shield and no lead sheath.
In conclusion, all License Renewal function cables have a shield throughout and are mostly lead sheath covered.