ML12334A557
| ML12334A557 | |
| Person / Time | |
|---|---|
| Site: | Indian Point |
| Issue date: | 12/14/2011 |
| From: | Atomic Safety and Licensing Board Panel |
| To: | |
| SECY RAS | |
| References | |
| RAS 21536, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01 | |
| Download: ML12334A557 (10) | |
Text
United States Nuclear Regulatory Commission Official Hearing Exhibit Entergy Nuclear Operations, Inc.
In the Matter of:
(Indian Point Nuclear Generating Units 2 and 3)
ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #: NYS000096-00-BD01 Identified: 10/15/2012 NYS000096 Admitted: 10/15/2012 Withdrawn: Submitted: December 14, 2011 Rejected: Stricken:
Other: EXCERPT OAGI0000361 001
INTRODUCTION This report presents New York Control Area (NYCA) system data and NYISO forecasts of:
- Peak demand, energy requirements and emergency demand response program.
- Existing resource capacity and planned changes.
- Existing and proposed transmission facilities.
The New York State Reliability Council (NYSRC) has the responsibility for establishing the annual minimum Installed Capacity Requirement (ICR) for the NYCA consistent with the NPCC and NYSRC resource adequacy criterion. The ICR is based on a corresponding Installed Reserve Margin (IRM) requirement, which also is established annually by the NYSRC for the upcoming capability period, and is expressed as a percentage of the forecasted peak demand.
The NYISO assigns a proportion of the ICR to each Load-Serving Entity (LSE) located within the NYC A. In doing so, NYISO establishes minimum installed capacity requirements, referred to as Locational Capacity Requirements (LCRs), for two specific load zones (or localities),
namely New York City and Long Island. The LCR is expressed as a percentage of the forecasted peak demand for the respective locality. The NYISO administers an installed capacity market that allows LSEs to procure installed capacity to meet their requirements either through bilateral arrangements or auctions conducted by the NYISO. Failure to meet these requirements will result in the imposition of financial penalties.
LSEs within the NYCA may meet their installed capacity requirements through procurement of qualified capacity from resources within the NYCA or from resources located in neighboring control areas directly interconnected to the NYCA, with the added proviso that the LCRs must be met by procurement of qualified capacity located within or interconnected to the respective locality. Resources located within the PJM, ISO-NE and Hydro Quebec control areas may qualify as installed capacity suppliers to the NYISO. Currently Ontario, the operator of the other directly interconnected control area to the NYCA, does not meet the NYISO's requirement relating to the recall of transactions associated with installed capacity sold to New York.
Therefore, resources located within this control area do not qualify as installed capacity suppliers to the NYISO.
OAGI0000361 007
LOAD AND CAPACITY
SUMMARY
The NYCA peak demand forecast developed for this report shows a compound growth rate of l.19% for the years 2007 through 2017. The forecast net energy for the same ten-year period shows a compound growth rate of l.34%.
The NYSRC has determined that an installed reserve of 16.5% over the NYC A summer peak demand for the year 2007 is required to meet the NPCC and NYSRC resource adequacy criterion. The NYSRC re-evaluates this IRM requirement each year. For the purposes of this report, the 16.5% IRM requirement was used throughout the 10 year reporting period as a reference.
The NYISO maintains a list of proposed generation and transmission projects in the NYISO interconnection process. Two projects on the list totaling approximately 930 MW that are under construction or otherwise have met the screening criteria for inclusion in the base case for the NYISO Reliability Needs Assessment (RNA) have been included as Resource Additions in the NYISO installed reserve margin calculation through 20 l7. These Resource Additions, existing capacity within the NYCA, and known purchases and sales with neighboring control areas would result in an installed reserve margin greater than or equal to 16.5% through the year 2010. Other projects on the list that have not met the criteria for inclusion in the RNA Base Case, but have qualified for inclusion in a class year, 1 have been categorized as Proposed Resource Additions.
2 These Proposed Resource Additions , if constructed, would result in an installed reserve margin greater than or equal to 16.5% through 2016.
Additionally, part of the New York installed capacity market design allows Special Case Resources (i.e., distributed generation and interruptible load customers that are not visible to the NYISO Market Information System) to participate in the installed capacity market. These customers become another source of capacity for LSEs.
1 The class year is the step in the New York interconnection process where system upgrade facilities, or "but for" facilities, are detennined for proposed new interconnections and cost responsibility assigned.
2 See load and capacity schedule description (page 58) for a discussion of the treatment of intermittent generators for the purpose of determining their contribution toward installed capacity on a forward looking basis.
2 OAGI0000361 008
SECTION I PEAK DEMAND, EMERGENCY DEMAND RESPONSE PROGRAM AND ENERGY REQUIREMENT FORECASTS 3
OAGI0000361_009
Table 1-1 NYISO 2007 Long Term Forecast - 2007 to 2017 Energy -GWh Summer Peak Demand - MW Winter Peak Demand - MW Year Low Base Highl Year Low Base Highl Year Low Base Highl 2006 162,853 2006 32,992 2006-07 25,030 2007 160,258 165,214 170,170 2007 31,775 33,447 35,119 2007-08 23,045 25,324 27,603 2008 160,408 167,440 174,472 2008 31,331 33,871 36,411 2008-09 22,661 25,748 28,835 2009 160,319 169,470 178,621 2009 31,042 34,300 37,559 2009-10 22,911 26,048 29,185 2010 160,581 171,744 182,907 2010 30,901 34,734 38,567 2010-11 23,152 26,341 29,530 2011 162,074 174,032 185,990 2011 31,239 35,141 39,043 2011-12 23,413 26,656 29,899 2012 164,383 176,615 188,847 2012 31,591 35,566 39,541 2012-13 23,846 27,170 30,494 2013 166,277 178,759 191,241 2013 31,917 35,962 40,007 2013-14 24,136 27,522 30,908 2014 168,372 181,126 193,880 2014 32,247 36,366 40,485 2014-15 24,442 27,893 31,344 2015 170,508 183,544 196,580 2015 32,557 36,749 40,941 2015-16 24,724 28,238 31,752 2016 172,910 186,256 199,602 2016 32,874 37,141 41,408 2016-17 25,031 28,614 32,197 2017 175,082 188,728 202,374 2017 33,276 37,631 41,986 2017-18 25,350 28,978 32,606 Average Annual Growth - Percent Period Low Base Highl Period Low Base Highl Period Low Base Highl 2006-17 0.66% 1.35% 1.99% 2006-17 0.08% 1.20% 2.22% 2006-17 0.12% 1.34% 2.43%
2007-12 0.51% 1.34% 2.10% 2007-12 -0.12% 1.24% 2.40% 2007-12 0.69% 1.42% 2.01%
2012-17 1.27% 1.34% 1.39% 2012-17 1.04% 1.14% 1.21% 2012-17 1.23% 1.30% 1.35%
Notes
- 1. 2006 results are for weather-normalized energy and peak demand.
- 2. 2007 summer peak corresponds to the 2007 ICAP forecast
- 3. Summer Capability period is from April 1 to October 31. Winter Capability period is from November 1 of the current year to April 30 of the next year.
4 OAGI0000361 010
Table 1-2a Forecast of Annual Energy by Zone - GWh Year A B C D E F G H I J K NYCA 2007 15,654 10,472 17,181 6,783 6,849 11,523 10,770 2,677 6,741 53,921 22,643 165,214 2008 15,738 10,731 17,353 6,995 6,822 11,480 10,909 2,719 6,841 54,940 22,912 167,440 2009 15,855 10,959 17,518 7,147 6,846 11,563 11,050 2,772 6,966 55,719 23,075 169,470 2010 16,032 11,208 17,629 7,227 6,943 11,600 11,199 2,805 7,063 56,708 23,330 171,744 2011 16,261 11,454 17,733 7,285 7,054 11,641 11,345 2,830 7,150 57,709 23,570 174,032 2012 16,504 11,689 17,824 7,323 7,225 11,694 11,479 2,840 7,219 58,899 23,919 176,615 2013 16,776 11,915 17,939 7,346 7,410 11,752 11,602 2,844 7,283 59,770 24,122 178,759 2014 17,149 12,137 18,070 7,295 7,656 11,823 11,712 2,818 7,304 60,744 24,418 181,126 2015 17,548 12,357 18,199 7,230 7,911 11,901 11,820 2,785 7,315 61,747 24,731 183,544 2016 17,855 12,583 18,318 7,241 8,084 11,971 11,935 2,784 7,376 62,907 25,202 186,256 2017 18077 12827 18420 7307 8225 12025 12051 2806 7472 63977 25541 188728 Forecast of Coincident Summer Peak Demand by Zone - MW Before Reductions for Emergency Demand Response Programs Year A B C D E F G H I J K NYCA 2007 2,593 2,017 2,925 811 1,367 2,247 2,262 618 1,505 11,780 5,322 33,447 2008 2,607 2,067 2,956 837 1,361 2,238 2,291 627 1,528 11,975 5,384 33,871 2009 2,626 2,111 2,984 855 1,366 2,254 2,321 639 1,555 12,150 5,439 34,300 2010 2,656 2,159 3,003 864 1,386 2,262 2,352 647 1,577 12,325 5,503 34,734 2011 2,694 2,206 3,020 871 1,408 2,269 2,383 653 1,597 12,480 5,560 35,141 2012 2,734 2,251 3,036 876 1,442 2,280 2,411 655 1,612 12,645 5,624 35,566 2013 2,779 2,295 3,055 879 1,479 2,291 2,437 656 1,626 12,780 5,685 35,962 2014 2,841 2,338 3,078 873 1,528 2,305 2,460 650 1,631 12,915 5,747 36,366 2015 2,907 2,380 3,100 865 1,579 2,320 2,483 642 1,633 13,030 5,810 36,749 2016 2,958 2,423 3,120 866 1,613 2,334 2,507 642 1,647 13,140 5,891 37,141 2017 2994 2470 3137 874 1641 2344 2531 647 1669 13360 5964 37631 Forecast of Coincident Winter Peak Demand by Zone- MW Year A B C D E F G H I J K NYCA 2007-08 2,304 1,639 2,651 988 1,059 1,866 1,706 427 1,068 7,980 3,636 25,324 2008-09 2,321 1,674 2,676 1,009 1,063 1,880 1,728 436 1,088 8,111 3,762 25,748 2009-10 2,347 1,712 2,693 1,020 1,078 1,886 1,751 441 1,103 8,237 3,780 26,048 2010-11 2,380 1,749 2,709 1,029 1,096 1,892 1,774 445 1,116 8,344 3,807 26,341 2011-12 2,416 1,785 2,723 1,034 1,122 1,901 1,795 446 1,127 8,451 3,856 26,656 2012-13 2,455 1,819 2,740 1,037 1,151 1,911 1,814 447 1,137 8,758 3,901 27,170 2013-14 2,510 1,853 2,760 1,030 1,189 1,922 1,831 443 1,140 8,894 3,950 27,522 2014-15 2,568 1,887 2,780 1,021 1,228 1,935 1,848 438 1,142 9,044 4,002 27,893 2015-16 2,613 1,922 2,798 1,022 1,255 1,946 1,866 438 1,152 9,217 4,009 28,238 2016-17 2,646 1,959 2,814 1,032 1,277 1,955 1,884 441 1,167 9,367 4,072 28,614 2017-18 2674 1996 2828 1042 1298 1963 1902 445 1183 9522 4125 28978 5
OAGI0000361_011
Table 1-2b Forecast of Non-Coincident Summer Peak Demand by Zone - MW Year A B C D E F G H I J K 2007 2,709 2,079 3,022 899 1,505 2,288 2,340 649 1,634 11,780 5,422 2008 2,724 2,131 3,053 927 1,499 2,279 2,370 659 1,658 11,975 5,485 2009 2,744 2,176 3,082 948 1,504 2,296 2,401 672 1,689 12,150 5,541 2010 2,775 2,225 3,101 958 1,526 2,303 2,433 680 1,712 12,325 5,607 2011 2,814 2,274 3,120 966 1,550 2,311 2,465 686 1,733 12,480 5,664 2012 2,856 2,321 3,136 971 1,588 2,322 2,494 688 1,750 12,645 5,730 2013 2,903 2,365 3,156 974 1,628 2,333 2,521 689 1,766 12,780 5,791 2014 2,968 2,410 3,179 967 1,682 2,347 2,545 683 1,771 12,915 5,855 2015 3,037 2,453 3,202 959 1,738 2,363 2,568 675 1,773 13,030 5,919 2016 3,090 2,498 3,222 960 1,776 2,377 2,593 675 1,788 13,140 6,002 2017 3,128 2,547 3,240 969 1,807 2,387 2,619 680 1,812 13,360 6,076 Forecast of Non-Coincident Winter Peak Demand by Zone - MW Year A B C D E F G H I J K 2007-08 2,415 1,685 2,798 1,091 1,109 1,944 1,749 459 1,155 8,230 3,678 2008-09 2,433 1,721 2,825 1,115 1,113 1,958 1,772 468 1,176 8,365 3,806 2009-10 2,460 1,760 2,842 1,127 1,129 1,965 1,795 474 1,193 8,495 3,824 2010-11 2,495 1,799 2,859 1,136 1,147 1,972 1,819 478 1,207 8,605 3,852 2011-12 2,532 1,835 2,874 1,142 1,175 1,981 1,840 480 1,219 8,715 3,901 2012-13 2,574 1,871 2,892 1,146 1,205 1,990 1,860 480 1,230 9,032 3,947 2013-14 2,631 1,906 2,913 1,138 1,245 2,002 1,878 476 1,233 9,172 3,996 2014-15 2,692 1,940 2,934 1,128 1,286 2,016 1,895 470 1,235 9,327 4,049 2015-16 2,740 1,976 2,954 1,129 1,315 2,028 1,914 470 1,245 9,505 4,056 2016-17 2,774 2,014 2,970 1,140 1,338 2,037 1,932 474 1,262 9,660 4,119 2017-18 2,803 2,053 2,985 1,151 1,359 2,045 1,950 478 1,279 9,820 4,173 6
OAGI0000361_012
Table 1-2c Forecast of Coincident Summer Peak Demand by Zone - MW Before Reductions for Emergency Demand Response Programs Year A B C D E F G H I J K NYCA 2007 2,593 2,017 2,925 811 1,367 2,247 2,262 618 1,505 11,780 5,322 33,447 2008 2,607 2,067 2,956 837 1,361 2,238 2,291 627 1,528 11,975 5,384 33,871 2009 2,626 2,111 2,984 855 1,366 2,254 2,321 639 1,555 12,150 5,439 34,300 2010 2,656 2,159 3,003 864 1,386 2,262 2,352 647 1,577 12,325 5,503 34,734 2011 2,694 2,206 3,020 871 1,408 2,269 2,383 653 1,597 12,480 5,560 35,141 2012 2,734 2,251 3,036 876 1,442 2,280 2,411 655 1,612 12,645 5,624 35,566 2013 2,779 2,295 3,055 879 1,479 2,291 2,437 656 1,626 12,780 5,685 35,962 2014 2,841 2,338 3,078 873 1,528 2,305 2,460 650 1,631 12,915 5,747 36,366 2015 2,907 2,380 3,100 865 1,579 2,320 2,483 642 1,633 13,030 5,810 36,749 2016 2,958 2,423 3,120 866 1,613 2,334 2,507 642 1,647 13,140 5,891 37,141 2017 2994 2470 3137 874 1641 2344 2531 647 1669 13360 5964 37631 Emergency Demand Response Program Reductions by Zone - MW Year A B C D E F G H I J K NYCA 2007 20 2 15 50 20 21 17 2 2 65 60 274 2008 20 2 15 50 20 21 17 2 2 65 60 274 2009 20 2 15 50 20 21 17 2 2 65 60 274 2010 20 2 15 50 20 21 17 2 2 65 60 274 2011 20 2 15 50 20 21 17 2 2 65 60 274 2012 20 2 15 50 20 21 17 2 2 65 60 274 2013 20 2 15 50 20 21 17 2 2 65 60 274 2014 20 2 15 50 20 21 17 2 2 65 60 274 2015 20 2 15 50 20 21 17 2 2 65 60 274 2016 20 2 15 50 20 21 17 2 2 65 60 274 2017 20 2 15 50 20 21 17 2 2 65 60 274 Forecast of Coincident Summer Peak Demand by Zone - MW After Reductions for Emergency Demand Response Programs Year A B C D E F G H I J K NYCA 2007 2,573 2,015 2,910 761 1,347 2,226 2,245 616 1,503 11,715 5,262 33,173 2008 2,587 2,065 2,941 787 1,341 2,217 2,274 625 1,526 11,910 5,324 33,597 2009 2,606 2,109 2,969 805 1,346 2,233 2,304 637 1,553 12,085 5,379 34,026 2010 2,636 2,157 2,988 814 1,366 2,241 2,335 645 1,575 12,260 5,443 34,460 2011 2,674 2,204 3,005 821 1,388 2,248 2,366 651 1,595 12,415 5,500 34,867 2012 2,714 2,249 3,021 826 1,422 2,259 2,394 653 1,610 12,580 5,564 35,292 2013 2,759 2,293 3,040 829 1,459 2,270 2,420 654 1,624 12,715 5,625 35,688 2014 2,821 2,336 3,063 823 1,508 2,284 2,443 648 1,629 12,850 5,687 36,092 2015 2,887 2,378 3,085 815 1,559 2,299 2,466 640 1,631 12,965 5,750 36,475 2016 2,938 2,421 3,105 816 1,593 2,313 2,490 640 1,645 13,075 5,831 36,867 2017 2974 2468 3122 824 1621 2323 2514 645 1667 13295 5904 37357 7
OAGI0000361_013
Table 1-3a Historic Annual Energy by Zone - GWh Year A B C 0 E F G H I J K NYCA 1997 18,450 8,225 16,223 4,708 9,201 11,777 8,697 1,954 5,436 44,463 18,241 147,374 1998 18,207 8,408 14,878 5,488 9,545 11,781 8,956 1,958 5,702 46,076 18,856 149,855 1999 18,210 8,611 15,713 6,184 8,956 11,994 9,266 1,894 6,060 48,281 19,671 154,841 2000 16,785 9,635 16,182 6,527 8,182 11,398 9,304 1,942 5,929 49,183 20,072 155,140 2001 16,209 9,661 16,034 6,374 7,403 11,429 9,396 2,003 5,782 50,227 20,723 155,240 2002 16,355 9,935 16,356 6,450 7,116 11,302 9,970 2,162 5,962 51,356 21,544 158,507 2003 15,942 9,719 16,794 5,912 6,950 11,115 10,451 2,219 6,121 50,829 21,960 158,013 2004 16,102 9,888 16,825 5,758 7,101 11,161 10,696 2,188 6,216 52,073 22,203 160,211 2005 16,498 10,227 17,568 6,593 7,594 11,789 10,924 2,625 6,435 54,007 22,948 167,208 2006 15998 10003 16839 6289 7339 11337 10417 2461 6274 53096 22185 162237 Historic Summer Coincident Peak Demand by Zone - MW Year A B C 0 E F G H I J K NYCA 1997 2,837 1,529 2,718 559 1,411 2,188 2,109 349 1,198 9,596 4,205 28,699 1998 2,643 1,442 2,381 623 1,465 1,998 2,045 419 1,168 9,581 4,396 28,161 1999 2,769 1,564 2,615 669 1,273 2,169 2,321 429 1,277 10,467 4,758 30,311 2000 2,462 1,644 2,459 757 1,185 1,872 2,176 417 1,265 9,771 4,130 28,138 2001 2,519 1,889 2,719 780 1,260 2,068 2,361 537 1,347 10,602 4,900 30,982 2002 2,631 1,842 2,787 777 1,252 2,073 2,076 498 1,335 10,321 5,072 30,664 2003 2,510 1,782 2,727 671 1,208 2,163 2,146 498 1,395 10,240 4,993 30,333 2004 2,493 1,743 2,585 644 1,057 1,953 2,041 475 1,280 9,742 4,420 28,433 2005 2,726 1,923 2,897 768 1,314 2,164 2,236 592 1,409 10,810 5,236 32,075 2006 2735 2110 3128 767 1435 2380 2436 596 1467 11300 5585 33939 Historic Winter Coincident Peak Demand by Zone - MW Year A B C 0 E F G H I J K NYCA 1997-98 2,752 1,289 2,337 651 1,516 1,816 1,539 401 787 6,491 2,866 22,445 1998-99 2,616 1,273 2,330 849 1,555 2,030 1,712 369 852 7,161 3,131 23,878 1999-00 2,454 1,499 2,497 870 1,443 1,906 1,726 420 976 7,072 3,177 24,041 2000-01 2,489 1,510 2,506 880 1,263 1,798 1,690 366 877 7,206 3,188 23,774 2001-02* 2,248 1,455 2,340 843 1,129 1,742 1,626 344 860 7,013 3,198 22,798 2002-03 2,418 1,507 2,679 925 1,223 1,903 1,590 437 927 7,373 3,472 24,454 2003-04 2,433 1,576 2,755 857 1,344 1,944 1,720 478 981 7,527 3,647 25,262 2004-05 2,446 1,609 2,747 918 1,281 1,937 1,766 474 939 7,695 3,729 25,541 2005-06 2,450 1,544 2,700 890 1,266 1,886 1,663 515 955 7,497 3,581 24,948 2006-07 2382 1566 2755 921 1274 1888 1638 504 944 7680 3505 25057
- The 2001-2002 winter capability period peak was set on Apn117, 2002. The peak reported here is the highest coincident recorded from December 1, 2001 through March 31,2002.
8 OAGI0000361_014
Table 1-3b Historic Summer Non-Coincident Peak Demand by Zone - MW Year A B C D E F G H I J K 1997 2,936 1,582 2,728 609 1,432 2,195 2,133 452 1,225 9,670 4,273 1998 2,788 1,539 2,697 764 1,585 2,139 2,045 497 1,269 9,586 4,396 1999 2,976 1,583 2,627 789 1,446 2,225 2,321 543 1,358 10,473 4,782 2000 2,625 1,694 2,710 884 1,216 1,919 2,178 586 1,265 9,809 4,386 2001 2,745 1,938 2,764 806 1,304 2,107 2,401 549 1,397 10,602 4,901 2002 2,770 1,898 2,879 804 1,361 2,114 2,097 562 1,364 10,457 5,082 2003 2,611 1,790 2,745 762 1,223 2,170 2,146 579 1,395 10,240 4,993 2004 2,523 1,743 2,601 705 1,149 1,997 2,041 502 1,366 9,769 4,728 2005 2,787 2,037 3,042 823 1,360 2,254 2,296 632 1,492 11,162 5,295 2006 2,786 2,144 3,153 845 1,435 2,380 2,497 627 1,545 11,350 5,752 Historic Winter Non-Coincident Peak Demand by Zone - MW Year A B C D E F G H I J K 1997-98 2,752 1,289 2,531 762 1,718 1,968 1,647 473 991 6,693 2,928 1998-99 2,778 1,346 2,744 889 1,555 2,030 1,712 413 920 7,161 3,131 1999-00 2,739 1,547 2,665 1,094 1,471 1,912 1,749 502 998 7,072 3,245 2000-01 2,489 1,534 2,540 922 1,333 1,872 1,732 479 985 7,206 3,269 2001-02 2,329 1,511 2,611 872 1,190 1,792 1,646 470 1,005 7,067 3,296 2002-03 2,870 1,538 2,687 941 1,259 1,910 1,619 490 1,155 7,440 3,496 2003-04 2,434 1,576 2,966 1,052 1,362 1,944 1,720 530 1,286 7,595 3,647 2004-05 2,463 1,609 2,804 945 1,305 1,958 1,794 571 1,080 7,695 3,767 2005-06 2,450 1,546 2,700 912 1,266 2,196 1,663 541 1,058 7,668 3,584 2006-07 2,400 1,566 2,755 943 1,280 1,932 1,641 532 944 7,680 3,506 Note: Some non-coincident peaks in Zones G, H & I are different than in previous reports. Hourly data in these zones have been reviewed and edited to correct for apparent outliers.
9 OAGI0000361_015